VRF BACnet gateway (multiple indoor units, Midea) · BACnet points list

Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet points list

Updated 6 November 2026

Short answer

Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP on a Midea commercial/VRF system. It publishes gateway-wide commands, outdoor-unit error objects at (OU x 10000) and one block per indoor unit at (unit index x 100): on/off, mode, setpoint, standard and extended fan speed, swing and vane positions, room temperature, error codes, remote and per-mode locks, operating-mode force and energy consumption.

This page lists 51 BACnet objects for the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Equipment
VRF BACnet gateway (multiple indoor units, Midea)
Equipment type
VRF & split air conditioners
BACnet objects
51 (23 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea
Brands covered
Midea
Source document
700 Series Air Gateway IN770AIR***O000 - Midea Commercial and VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.0.22
Download CSV 51 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.

BMS integration notes: Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)

Integration in brief

Connect the Midea bus to the gateway, pick BACnet IP or BACnet MS/TP in Intesis MAPS, configure the units, send the project, then map each indoor unit's _C commands and _S status objects from its (index x 100) block.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100UXX_On/Off_CStart/stop indoor unitCommand
MO 100UXX_Mode_CMode commandCommand
AO 100UXX_Setpoint_CSetpoint commandCommand
MO 101UXX_FanSpeed_CFan speed command (1 = auto)Command
BI 100UXX_On/Off_SRun statusRead
AI 100UXX_Setpoint_SSetpoint in useRead
AI 101UXX_Room TemperatureIndoor unit room temperature, °CRead
BI 102UXX_Communication Error IUUnit offline on the Midea busRead
AI 102UXX_Unit Error CodeFault code (0 = no error)Read

Enable & remote start

No enable point is documented. UXX_Remote control lock_C (BO 102) locks the remote controller of that unit.

Network setup

Watch out for

Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

51 of 51 shown
Type
Access
Show
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet Points List
DescriptionStates
BO0On/Off (all units)Start/stop every unitCommand0=Off, 1=On
MO0Mode (all units)Mode for every unitCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
MO1FanSpeed (all units)Fan speed for every unitCommand1=Auto, 2=Low, 3=Med, 4=High
MO2FanSpeed extended (all units)Extended fan speed for every unitCommand1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7
MO3Vane Position LEFT/RIGHT (all units)Left/right vane for every unitCommand1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing
MO4Vane Position UP/DOWN (all units)Up/down vane for every unitCommand1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing
BO1Vane Position Swing (all units)Swing for every unitCommand0=Swing Off, 1=Swing On
AO0Temperature Setpoint (all units)Setpoint for every unit (17-30 °C)°CCommand
BO2Operating mode force (all Units)Operating mode force for every unitCommand0=No force, 1=Force
BO3Remote control lock (all units)Lock remotes of every unitCommand0=Unlock, 1=Lock
AI10000OUXX_Unit Error CodeOutdoor unit error codeRead0=No error, 1..260=Error
BI10000OUXX_Communication Error OUOutdoor unit communication errorRead0=No error, 1=Error
BImin100UXX_On/Off_SOn/off statusRead0=Off, 1=On
BOmin100UXX_On/Off_CStart/stop the indoor unitCommand0=Off, 1=On
MI100UXX_Mode_SOperating mode in useRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool, 8=AutoDry, 9=AutoFan
MOmin100UXX_Mode_COperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin100UXX_Setpoint_SSetpoint in use (17-30 °C)°CRead
AOmin100UXX_Setpoint_CSetpoint command (17-30 °C)°CCommand
MI101UXX_FanSpeed_SFan speed statusRead1=Auto, 2=Low, 3=Med, 4=High
MOmin101UXX_FanSpeed_CFan speed commandCommand1=Auto, 2=Low, 3=Med, 4=High
MI102UXX_FanSpeed Extended_SExtended fan speed statusRead1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7
MO102UXX_FanSpeed Extended_CExtended fan speed commandCommand1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7
BI101UXX_Vane position swing_SSwing statusRead0=Swing Off, 1=Swing On
BO101UXX_Vane position swing_CSwing commandCommand0=Swing Off, 1=Swing On
MI103UXX_Vane Position Left/Right_SLeft/right vane statusRead1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing
MO103UXX_Vane Position Left/Right_CLeft/right vane commandCommand1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing
MI104UXX_Vane Position Up/Down_SUp/down vane statusRead1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing
MO104UXX_Vane Position Up/Down_CUp/down vane commandCommand1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing
AImin101UXX_Room TemperatureRoom temperature°CRead
AImin102UXX_Unit Error CodeUnit error codeRead0=No error, 1..255=Error
AI112UXX_Unit Error Code ExtendedExtended unit error codeRead0=No error, 1..260=Error
BImin102UXX_Communication Error IUIndoor unit communication errorRead0=No error, 1=Error
BI103UXX_Remote control lock_SRemote lock statusRead0=Unlock, 1=Lock
BO102UXX_Remote control lock_CRemote lock commandCommand0=Unlock, 1=Lock
BI107UXX_Control lock_Mode Heat_SHeat mode lock statusRead0=Unlock, 1=Lock
BO106UXX_Control lock_Mode Heat_CHeat mode lock commandCommand0=Unlock, 1=Lock
BI108UXX_Control lock_Mode Cool_SCool mode lock statusRead0=Unlock, 1=Lock
BO107UXX_Control lock_Mode Cool_CCool mode lock commandCommand0=Unlock, 1=Lock
BI109UXX_Control lock_Mode Fan_SFan mode lock statusRead0=Unlock, 1=Lock
BO108UXX_Control lock_Mode Fan_CFan mode lock commandCommand0=Unlock, 1=Lock
BI104UXX_Operating mode force_SOperating mode force statusRead0=No force, 1=Force
BO103UXX_Operating mode force_COperating mode force commandCommand0=No force, 1=Force
AI103UXX_Consumption_Yesterday_SEnergy consumption, yesterdayWh/kWhRead
AI104UXX_Consumption_Today_SEnergy consumption, todayWh/kWhRead
AI105UXX_Consumption_Total_SEnergy consumption, totalWh/kWhRead
AI106UXX_Consumption_Yesterday_Heat_SEnergy consumption, yesterday heatWh/kWhRead
AI107UXX_Consumption_Today_Heat_SEnergy consumption, today heatWh/kWhRead
AI108UXX_Consumption_Total_Heat_SEnergy consumption, total heatWh/kWhRead
AI109UXX_Consumption_Yesterday_Cool_SEnergy consumption, yesterday coolWh/kWhRead
AI110UXX_Consumption_Today_Cool_SEnergy consumption, today coolWh/kWhRead
AI111UXX_Consumption_Total_Cool_SEnergy consumption, total coolWh/kWhRead
Object ID lookup: Intesis Midea VRF Gateway IN770 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)

How many BACnet points does the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) have?

This list has 51 BACnet objects: 14 analog inputs, 2 analog outputs, 9 binary inputs, 11 binary outputs, 5 multi-state inputs, 10 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet points are writable?

23 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet documentation?

The source is 700 Series Air Gateway IN770AIR***O000 - Midea Commercial and VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2025-12-09 v1.0.22, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770midxxxo000.pdf.

What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?

Start with BO 100 UXX_On/Off_C (Start/stop indoor unit); MO 100 UXX_Mode_C (Mode command); AO 100 UXX_Setpoint_C (Setpoint command); MO 101 UXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 UXX_On/Off_S (Run status); AI 100 UXX_Setpoint_S (Setpoint in use); AI 101 UXX_Room Temperature (Indoor unit room temperature, °C); BI 102 UXX_Communication Error IU (Unit offline on the Midea bus); AI 102 UXX_Unit Error Code (Fault code (0 = no error)).

How do I enable BMS control of the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?

No enable point is documented. UXX_Remote control lock_C (BO 102) locks the remote controller of that unit.

How do I check these points on the real IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.