- IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
VRF BACnet gateway (multiple indoor units, Midea) · BACnet points list
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet points list
Updated 6 November 2026
Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP on a Midea commercial/VRF system. It publishes gateway-wide commands, outdoor-unit error objects at (OU x 10000) and one block per indoor unit at (unit index x 100): on/off, mode, setpoint, standard and extended fan speed, swing and vane positions, room temperature, error codes, remote and per-mode locks, operating-mode force and energy consumption.
This page lists 51 BACnet objects for the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
- Equipment
- VRF BACnet gateway (multiple indoor units, Midea)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 51 (23 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea
- Brands covered
- Midea
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Connect the Midea bus to the gateway, pick BACnet IP or BACnet MS/TP in Intesis MAPS, configure the units, send the project, then map each indoor unit's _C commands and _S status objects from its (index x 100) block.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | UXX_On/Off_C | Start/stop indoor unit | Command |
| MO 100 | UXX_Mode_C | Mode command | Command |
| AO 100 | UXX_Setpoint_C | Setpoint command | Command |
| MO 101 | UXX_FanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | UXX_On/Off_S | Run status | Read |
| AI 100 | UXX_Setpoint_S | Setpoint in use | Read |
| AI 101 | UXX_Room Temperature | Indoor unit room temperature, °C | Read |
| BI 102 | UXX_Communication Error IU | Unit offline on the Midea bus | Read |
| AI 102 | UXX_Unit Error Code | Fault code (0 = no error) | Read |
Enable & remote start
No enable point is documented. UXX_Remote control lock_C (BO 102) locks the remote controller of that unit.
Network setup
- Units are indexed in Intesis MAPS; the index (not the Midea address) sets the instance block.
- Send the project to the gateway after changes in MAPS.
Watch out for
- Global objects (BO 0-3, MO 0-4, AO 0) act on all units at once.
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 0 | On/Off (all units) | Start/stop every unit | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode for every unit | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MO | 1 | FanSpeed (all units) | Fan speed for every unit | Command | 1=Auto, 2=Low, 3=Med, 4=High | |
| MO | 2 | FanSpeed extended (all units) | Extended fan speed for every unit | Command | 1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7 | |
| MO | 3 | Vane Position LEFT/RIGHT (all units) | Left/right vane for every unit | Command | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| MO | 4 | Vane Position UP/DOWN (all units) | Up/down vane for every unit | Command | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| BO | 1 | Vane Position Swing (all units) | Swing for every unit | Command | 0=Swing Off, 1=Swing On | |
| AO | 0 | Temperature Setpoint (all units) | Setpoint for every unit (17-30 °C) | °C | Command | |
| BO | 2 | Operating mode force (all Units) | Operating mode force for every unit | Command | 0=No force, 1=Force | |
| BO | 3 | Remote control lock (all units) | Lock remotes of every unit | Command | 0=Unlock, 1=Lock | |
| AI | 10000 | OUXX_Unit Error Code | Outdoor unit error code | Read | 0=No error, 1..260=Error | |
| BI | 10000 | OUXX_Communication Error OU | Outdoor unit communication error | Read | 0=No error, 1=Error | |
| BImin | 100 | UXX_On/Off_S | On/off status | Read | 0=Off, 1=On | |
| BOmin | 100 | UXX_On/Off_C | Start/stop the indoor unit | Command | 0=Off, 1=On | |
| MI | 100 | UXX_Mode_S | Operating mode in use | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool, 8=AutoDry, 9=AutoFan | |
| MOmin | 100 | UXX_Mode_C | Operating mode command | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | UXX_Setpoint_S | Setpoint in use (17-30 °C) | °C | Read | |
| AOmin | 100 | UXX_Setpoint_C | Setpoint command (17-30 °C) | °C | Command | |
| MI | 101 | UXX_FanSpeed_S | Fan speed status | Read | 1=Auto, 2=Low, 3=Med, 4=High | |
| MOmin | 101 | UXX_FanSpeed_C | Fan speed command | Command | 1=Auto, 2=Low, 3=Med, 4=High | |
| MI | 102 | UXX_FanSpeed Extended_S | Extended fan speed status | Read | 1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7 | |
| MO | 102 | UXX_FanSpeed Extended_C | Extended fan speed command | Command | 1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4, 6=Speed 5, 7=Speed 6, 8=Speed 7 | |
| BI | 101 | UXX_Vane position swing_S | Swing status | Read | 0=Swing Off, 1=Swing On | |
| BO | 101 | UXX_Vane position swing_C | Swing command | Command | 0=Swing Off, 1=Swing On | |
| MI | 103 | UXX_Vane Position Left/Right_S | Left/right vane status | Read | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| MO | 103 | UXX_Vane Position Left/Right_C | Left/right vane command | Command | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| MI | 104 | UXX_Vane Position Up/Down_S | Up/down vane status | Read | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| MO | 104 | UXX_Vane Position Up/Down_C | Up/down vane command | Command | 1=Stop, 2=Step 1, 3=Step 2, 4=Step 3, 5=Step 4, 6=Step 5, 7=Swing | |
| AImin | 101 | UXX_Room Temperature | Room temperature | °C | Read | |
| AImin | 102 | UXX_Unit Error Code | Unit error code | Read | 0=No error, 1..255=Error | |
| AI | 112 | UXX_Unit Error Code Extended | Extended unit error code | Read | 0=No error, 1..260=Error | |
| BImin | 102 | UXX_Communication Error IU | Indoor unit communication error | Read | 0=No error, 1=Error | |
| BI | 103 | UXX_Remote control lock_S | Remote lock status | Read | 0=Unlock, 1=Lock | |
| BO | 102 | UXX_Remote control lock_C | Remote lock command | Command | 0=Unlock, 1=Lock | |
| BI | 107 | UXX_Control lock_Mode Heat_S | Heat mode lock status | Read | 0=Unlock, 1=Lock | |
| BO | 106 | UXX_Control lock_Mode Heat_C | Heat mode lock command | Command | 0=Unlock, 1=Lock | |
| BI | 108 | UXX_Control lock_Mode Cool_S | Cool mode lock status | Read | 0=Unlock, 1=Lock | |
| BO | 107 | UXX_Control lock_Mode Cool_C | Cool mode lock command | Command | 0=Unlock, 1=Lock | |
| BI | 109 | UXX_Control lock_Mode Fan_S | Fan mode lock status | Read | 0=Unlock, 1=Lock | |
| BO | 108 | UXX_Control lock_Mode Fan_C | Fan mode lock command | Command | 0=Unlock, 1=Lock | |
| BI | 104 | UXX_Operating mode force_S | Operating mode force status | Read | 0=No force, 1=Force | |
| BO | 103 | UXX_Operating mode force_C | Operating mode force command | Command | 0=No force, 1=Force | |
| AI | 103 | UXX_Consumption_Yesterday_S | Energy consumption, yesterday | Wh/kWh | Read | |
| AI | 104 | UXX_Consumption_Today_S | Energy consumption, today | Wh/kWh | Read | |
| AI | 105 | UXX_Consumption_Total_S | Energy consumption, total | Wh/kWh | Read | |
| AI | 106 | UXX_Consumption_Yesterday_Heat_S | Energy consumption, yesterday heat | Wh/kWh | Read | |
| AI | 107 | UXX_Consumption_Today_Heat_S | Energy consumption, today heat | Wh/kWh | Read | |
| AI | 108 | UXX_Consumption_Total_Heat_S | Energy consumption, total heat | Wh/kWh | Read | |
| AI | 109 | UXX_Consumption_Yesterday_Cool_S | Energy consumption, yesterday cool | Wh/kWh | Read | |
| AI | 110 | UXX_Consumption_Today_Cool_S | Energy consumption, today cool | Wh/kWh | Read | |
| AI | 111 | UXX_Consumption_Total_Cool_S | Energy consumption, total cool | Wh/kWh | Read |
No points match these filters.
Object ID lookup: Intesis Midea VRF Gateway IN770 point IDs by name
BO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)MO2FanSpeed extended (all units)MO3Vane Position LEFT/RIGHT (all units)MO4Vane Position UP/DOWN (all units)BO1Vane Position Swing (all units)AO0Temperature Setpoint (all units)BO2Operating mode force (all Units)BO3Remote control lock (all units)AI10000OUXX_Unit Error CodeBI10000OUXX_Communication Error OUBI100UXX_On/Off_SBO100UXX_On/Off_CMI100UXX_Mode_SMO100UXX_Mode_CAI100UXX_Setpoint_SAO100UXX_Setpoint_CMI101UXX_FanSpeed_SMO101UXX_FanSpeed_CMI102UXX_FanSpeed Extended_SMO102UXX_FanSpeed Extended_CBI101UXX_Vane position swing_SBO101UXX_Vane position swing_CMI103UXX_Vane Position Left/Right_SMO103UXX_Vane Position Left/Right_CMI104UXX_Vane Position Up/Down_SMO104UXX_Vane Position Up/Down_CAI101UXX_Room TemperatureAI102UXX_Unit Error CodeAI112UXX_Unit Error Code ExtendedBI102UXX_Communication Error IUBI103UXX_Remote control lock_SBO102UXX_Remote control lock_CBI107UXX_Control lock_Mode Heat_SBO106UXX_Control lock_Mode Heat_CBI108UXX_Control lock_Mode Cool_SBO107UXX_Control lock_Mode Cool_CBI109UXX_Control lock_Mode Fan_SBO108UXX_Control lock_Mode Fan_CBI104UXX_Operating mode force_SBO103UXX_Operating mode force_CAI103UXX_Consumption_Yesterday_SAI104UXX_Consumption_Today_SAI105UXX_Consumption_Total_SAI106UXX_Consumption_Yesterday_Heat_SAI107UXX_Consumption_Today_Heat_SAI108UXX_Consumption_Total_Heat_SAI109UXX_Consumption_Yesterday_Cool_SAI110UXX_Consumption_Today_Cool_SAI111UXX_Consumption_Total_Cool_S
Integration notes
- Indoor unit instance = (IU x 100) + offset, IU = unit index in Intesis MAPS; index 1 is shown (100-112).
- Outdoor unit instance = (OU x 10000) + offset; OU 1 is shown (10000).
- The BACnet table has no read/write column; access is inferred from object type.
- Consumption objects report Wh or kWh as set in MAPS.
- The manual names INBACMID004I000 (listed separately) as its legacy order code.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
How many BACnet points does the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) have?
This list has 51 BACnet objects: 14 analog inputs, 2 analog outputs, 9 binary inputs, 11 binary outputs, 5 multi-state inputs, 10 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet points are writable?
23 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway) BACnet documentation?
The source is 700 Series Air Gateway IN770AIR***O000 - Midea Commercial and VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2025-12-09 v1.0.22, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770midxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?
Start with BO 100 UXX_On/Off_C (Start/stop indoor unit); MO 100 UXX_Mode_C (Mode command); AO 100 UXX_Setpoint_C (Setpoint command); MO 101 UXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 UXX_On/Off_S (Run status); AI 100 UXX_Setpoint_S (Setpoint in use); AI 101 UXX_Room Temperature (Indoor unit room temperature, °C); BI 102 UXX_Communication Error IU (Unit offline on the Midea bus); AI 102 UXX_Unit Error Code (Fault code (0 = no error)).
How do I enable BMS control of the Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?
No enable point is documented. UXX_Remote control lock_C (BO 102) locks the remote controller of that unit.
How do I check these points on the real IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway IN770AIR***O000 - Midea Commercial and VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.0.22. Object names, instances and units are reproduced as published; descriptions are our own.