- IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
VRF BACnet gateway (City Multi groups via centralized controller) · BACnet points list
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway) BACnet points list
Updated 6 November 2026
Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP that talks to Mitsubishi Electric City Multi centralized controllers and serves each group as BACnet objects. It publishes gateway-wide commands, a block per group at ((CC# - 1) x 8000) + (G x 100): on/off, mode (indoor, Lossnay and air-to-water variants), fan, vanes, setpoints and limits, ambient temperature, errors, panel-permission locks, sensors, filter and energy consumption, plus optional per-unit error codes.
This page lists 101 BACnet objects for the Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway) — 44 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
- Equipment
- VRF BACnet gateway (City Multi groups via centralized controller)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 101 (44 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi
- Brands covered
- Mitsubishi Electric
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Connect the gateway to the City Multi centralized controller(s), pick BACnet IP or BACnet MS/TP in Intesis MAPS, load the groups, send the project, then map each group's _C commands and _S status objects from its instance block.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | CXGX_On/Off_C | Start/stop the group | Command |
| MO 100 | CXGX_Mode_C | Indoor-unit mode command | Command |
| AO 100 | CXGX_Setpoint_C | Setpoint command | Command |
| MO 103 | CXGX_FanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | CXGX_On/Off_S | Run status | Read |
| AI 100 | CXGX_Setpoint_S | Setpoint in use | Read |
| AI 102 | CXGX_AmbientTemp_S | Group room temperature, °C | Read |
| BI 101 | CXGX_ErrorStatus_S | Group alarm | Read |
| AI 105 | CXGX_ErrorCode_S | Fault code (0 = no error) | Read |
Enable & remote start
No enable point is documented. The CXGX_Allow_..._Panel_C objects (BO 102-108) block local remote functions per group.
Network setup
- Groups and centralized controllers (up to 2) are set up in Intesis MAPS; send the project after changes.
- Fan speed state lists follow the number of fan speeds selected in MAPS.
Watch out for
- BI 0 shows loss of communication with the centralized controller; all group data is stale while it is 1.
- Global objects (BO 0-1, MO 0-4, AO 0) act on every group of that controller.
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 0 | Centralized controller communication error | Link to the centralized controller | Read | 0=Ok, 1=Communication error | |
| BO | 0 | Reset errors (all groups) | Reset errors on every group | Command | 0=No Reset, 1=Reset errors | |
| BO | 1 | On/Off (all groups) | Start/stop every group | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all IC groups) | Mode for every indoor-unit group | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=Setback | |
| MO | 1 | Mode (all Lossnay groups) | Mode for every Lossnay group | Command | 1=LC_Auto, 2=HeatRecovery, 3=Bypass | |
| MO | 2 | Fan Speed (all IC groups) | Fan speed for every indoor-unit group | Command | 1=Auto, 2=Low, 3=Mid1, 4=Mid2, 5=High | |
| MO | 3 | Fan Speed (all Lossnay groups) | Fan speed for every Lossnay group | Command | 1=Low, 2=Mid1, 3=Mid2, 4=High | |
| MO | 4 | Vane Position (all IC groups) | Vane position for every indoor-unit group | Command | 1=Auto, 2=Horizontal, 3=Pos. 2, 4=Pos. 3, 5=Pos4, 6=Vertical, 7=Swing | |
| AO | 0 | Setpoint (all the groups) | Setpoint for every group (5-90 °C) | °C | Command | |
| BImin | 100 | CXGX_On/Off_S | Group on/off status | Read | 0=Off, 1=On | |
| BOmin | 100 | CXGX_On/Off_C | Start/stop the group | Command | 0=Off, 1=On | |
| MI | 100 | CXGX_Mode_S | Mode status, indoor units | Read | 1=Auto, 2=Heat, 3=Dry, 4=Fan, 5=Cool, 6=AutoHeat, 7=AutoCool, 8=Setback, 9=Setbackheat, 10=Setbackcool | |
| MI | 101 | CXGX_Mode_S | Mode status, Lossnay | Read | 1=LC_Auto, 2=Heat Recovery, 3=Bypass | |
| MI | 102 | CXGX_Mode_S | Mode status, air-to-water units | Read | 1=Hot_Water, 2=Heating, 3=Heating_Eco, 4=Anti_Freeze, 5=Cooling | |
| MOmin | 100 | CXGX_Mode_C | Mode command, indoor units | Command | 1=Auto, 2=Heat, 3=Dry, 4=Fan, 5=Cool, 6=Setback | |
| MO | 101 | CXGX_Mode_C | Mode command, Lossnay | Command | 1=LC_Auto, 2=Heat Recovery, 3=Bypass | |
| MO | 102 | CXGX_Mode_C | Mode command, air-to-water units | Command | 1=Hot_Water, 2=Heating, 3=Heating_Eco, 4=Anti_Freeze, 5=Cooling | |
| MI | 103 | CXGX_FanSpeed_S | Fan speed status | Read | Depends on fan speeds set in MAPS: 2 speeds 1=Auto, 2=Low, 3=High; 3 speeds 1=Auto, 2=Low, 3=Mid1, 4=High; 4 speeds 1=Auto, 2=Low, 3=Mid2, 4=Mid1, 5=High | |
| MI | 104 | CXGX_FanSpeed_S | Fan speed status | Read | Depends on fan speeds set in MAPS: 2 speeds 1=Auto, 2=Low, 3=High; 3 speeds 1=Auto, 2=Low, 3=Mid1, 4=High; 4 speeds 1=Auto, 2=Low, 3=Mid2, 4=Mid1, 5=High | |
| MOmin | 103 | CXGX_FanSpeed_C | Fan speed command | Command | Depends on fan speeds set in MAPS: 2 speeds 1=Auto, 2=Low, 3=High; 3 speeds 1=Auto, 2=Low, 3=Mid1, 4=High; 4 speeds 1=Auto, 2=Low, 3=Mid2, 4=Mid1, 5=High | |
| MO | 104 | CXGX_FanSpeed_C | Fan speed command | Command | Depends on fan speeds set in MAPS: 2 speeds 1=Auto, 2=Low, 3=High; 3 speeds 1=Auto, 2=Low, 3=Mid1, 4=High; 4 speeds 1=Auto, 2=Low, 3=Mid2, 4=Mid1, 5=High | |
| MI | 105 | CXGX_Vanes_S | Vane position status | Read | 1=Auto, 2=Horizontal, 3=Pos. 2, 4=Pos. 3, 5=Pos. 4, 6=Vertical, 7=Swing | |
| MO | 105 | CXGX_Vanes_C | Vane position command | Command | 1=Auto, 2=Horizontal, 3=Pos. 2, 4=Pos. 3, 5=Pos. 4, 6=Vertical, 7=Swing | |
| AImin | 100 | CXGX_Setpoint_S | Setpoint status (cool/dry 19-30 °C, heat/auto 17-28 °C) | °C | Read | |
| AI | 101 | CXGX_Setpoint_S | Setpoint status, 5-90 °C range | °C | Read | |
| AOmin | 100 | CXGX_Setpoint_C | Setpoint command (cool/dry 19-30 °C, heat/auto 17-28 °C) | °C | Command | |
| AO | 101 | CXGX_Setpoint_C | Setpoint command, 5-90 °C range | °C | Command | |
| AImin | 102 | CXGX_AmbientTemp_S | Group ambient temperature | °C | Read | |
| MI | 106 | CXGX_OperationalStatus_LS_OA_S | Lossnay / outdoor-air operating status | Read | 1=Off, 2=Low, 3=High | |
| MO | 106 | CXGX_OperationalStatus_LS_OA_C | Lossnay / outdoor-air operating command | Command | 1=Off, 2=Low, 3=High | |
| AI | 103 | CXGX_OperationTimex100_S | Operating time, hundreds (0-9999) | Read | ||
| AI | 104 | CXGX_OperationTime%100_S | Operating time, remainder (0-99) | Read | ||
| BImin | 101 | CXGX_ErrorStatus_S | Group error | Read | 0=No error, 1=Group error | |
| AImin | 105 | CXGX_ErrorCode_S | Group error code | Read | 0=No Error, 1..255=Error | |
| BO | 101 | CXGX_ErrorReset_C | Reset group error | Command | 0=No Reset, 1=Reset | |
| MI | 107 | CXGX_Model_S | Group model type | Read | 1=IC, 2=KIC, 3=AIC, 4=LC, 5=FU, 6=BU, 7=WH, 8=CEh, 9=DC, 10=AHC, 11=RC, 12=ME, 13=RC, 14=URC, 15=GW, 16=TR, 17=AN, 18=GR, 19=SR, 20=ST, 21=SC, 22=??, 23=NONE | |
| BI | 102 | CXGX_Allow_ONOFF_Panel_S | Local ON/OFF allowed from panel (status) | Read | 0=Allow, 1=Not allowed | |
| BO | 102 | CXGX_Allow_ONOFF_Panel_C | Allow local ON/OFF from panel | Command | 0=Allow, 1=Not allowed | |
| BI | 103 | CXGX_Allow_MODE_Panel_S | Local mode allowed from panel (status) | Read | 0=Allow, 1=Not allowed | |
| BO | 103 | CXGX_Allow_MODE_Panel_C | Allow local mode from panel | Command | 0=Allow, 1=Not allowed | |
| BI | 104 | CXGX_Allow_SETPOINT_Panel_S | Local setpoint allowed from panel (status) | Read | 0=Allow, 1=Not allowed | |
| BO | 104 | CXGX_Allow_SETPOINT_Panel_c | Allow local setpoint from panel | Command | 0=Allow, 1=Not allowed | |
| BI | 105 | CXGX_Allow_FILTERRESET_Panel_S | Local filter reset allowed from panel (status) | Read | 0=Allow, 1=Not allowed | |
| BO | 105 | CXGX_Allow_FILTERRESET_Panel_C | Allow local filter reset from panel | Command | 0=Allow, 1=Not allowed | |
| BI | 106 | CXGX_Allow_FANSPEED_Panel_S | Local fan speed allowed from panel (status) | Read | 0=Allow, 1=Not allowed | |
| BO | 106 | CXGX_Allow_FANSPEED_Panel_C | Allow local fan speed from panel | Command | 0=Allow, 1=Not allowed | |
| BI | 107 | CXGX_Allow_VANES_Panel_S | Local vanes allowed from panel (status) | Read | 0=Allow, 1=Not allowed | |
| BO | 107 | CXGX_Allow_VANES_Panel_C | Allow local vanes from panel | Command | 0=Allow, 1=Not allowed | |
| BI | 108 | CXGX_Allow_TIMER_Panel_S | Local timer allowed from panel (status) | Read | 0=Allow, 1=Not allowed | |
| BO | 108 | CXGX_Allow_TIMER_Panel_C | Allow local timer from panel | Command | 0=Allow, 1=Not allowed | |
| BI | 109 | CXGX_SetbackControl_S | Setback control status | Read | 0=Disable, 1=Enable | |
| BO | 109 | CXGX_SetbackControl_C | Setback control command | Command | 0=Disable, 1=Enable | |
| AI | 106 | CXGX_Min_Cool_Setpoint_S | min cool setpoint limit (status) | °C | Read | |
| AO | 102 | CXGX_Min_Cool_Setpoint_C | min cool setpoint limit (command) | °C | Command | |
| AI | 107 | CXGX_Max_Cool_Setpoint_S | max cool setpoint limit (status) | °C | Read | |
| AO | 103 | CXGX_Max_Cool_Setpoint_C | max cool setpoint limit (command) | °C | Command | |
| AI | 108 | CXGX_Min_Heat_Setpoint_S | min heat setpoint limit (status) | °C | Read | |
| AO | 104 | CXGX_Min_Heat_Setpoint_C | min heat setpoint limit (command) | °C | Command | |
| AI | 109 | CXGX_Max_Heat_Setpoint_S | max heat setpoint limit (status) | °C | Read | |
| AO | 105 | CXGX_Max_Heat_Setpoint_C | max heat setpoint limit (command) | °C | Command | |
| AI | 110 | CXGX_Min_Auto_Setpoint_S | min auto setpoint limit (status) | °C | Read | |
| AO | 106 | CXGX_Min_Auto_Setpoint_C | min auto setpoint limit (command) | °C | Command | |
| AI | 111 | CXGX_Max_Auto_Setpoint_S | max auto setpoint limit (status) | °C | Read | |
| AO | 107 | CXGX_Max_Auto_Setpoint_C | max auto setpoint limit (command) | °C | Command | |
| AI | 112 | CXGX_CoolDryAuto_Upper_DualSetpoint_S | Cool/dry/auto upper dual setpoint (status) | °C | Read | |
| AO | 108 | CXGX_CoolDryAuto_Upper_DualSetpoint_C | Cool/dry/auto upper dual setpoint (command) | °C | Command | |
| AI | 113 | CXGX_Heating_ATW_HWHP_Setpoint_S | Heating setpoint, ATW / hot-water heat pump (status) | °C | Read | |
| AO | 109 | CXGX_Heating_ATW_HWHP_Setpoint_C | Heating setpoint, ATW / hot-water heat pump (command) | °C | Command | |
| AI | 114 | CXGX_AutoHeat_Lower_DualSetpoint_S | Auto/heat lower dual setpoint (status) | °C | Read | |
| AO | 110 | CXGX_AutoHeat_Lower_DualSetpoint_C | Auto/heat lower dual setpoint (command) | °C | Command | |
| AI | 115 | CXGX_HeatingECO_Setpoint_S | Heating eco setpoint (status) | °C | Read | |
| AO | 111 | CXGX_HeatingECO_Setpoint_C | Heating eco setpoint (command) | °C | Command | |
| AI | 116 | CXGX_AutoSingle_Setpoint_S | Auto single setpoint (status) | °C | Read | |
| AO | 112 | CXGX_AutoSingle_Setpoint_C | Auto single setpoint (command) | °C | Command | |
| AI | 117 | CXGX_HotWater_Setpoint_S | Hot water setpoint (status) | °C | Read | |
| AO | 113 | CXGX_HotWater_Setpoint_C | Hot water setpoint (command) | °C | Command | |
| AI | 118 | CXGX_Setback_Upper_Setpoint_S | Setback upper setpoint (status) | °C | Read | |
| AO | 114 | CXGX_Setback_Upper_Setpoint_C | Setback upper setpoint (command) | °C | Command | |
| AI | 119 | CXGX_Setback_Lower_Setpoint_S | Setback lower setpoint (status) | °C | Read | |
| AO | 115 | CXGX_Setback_Lower_Setpoint_C | Setback lower setpoint (command) | °C | Command | |
| AI | 120 | CXGX_Antifreeze_Setpoint_S | Antifreeze setpoint (status) | °C | Read | |
| AO | 116 | CXGX_Antifreeze_Setpoint_C | Antifreeze setpoint (command) | °C | Command | |
| AI | 121 | CXGX_Cooling_Setpoint_S | Cooling setpoint (status) | °C | Read | |
| AO | 117 | CXGX_Cooling_Setpoint_C | Cooling setpoint (command) | °C | Command | |
| AI | 122 | CXGX_Room_Humidity_S | Room humidity | % | Read | |
| BI | 110 | CXGX_Brightness_S | Brightness sensor | Read | 0=Dark, 1=Bright | |
| BI | 111 | CXGX_Occupancy_S | Occupancy sensor | Read | 0=Absence, 1=Occupancy | |
| AI | 123 | CXGX_Outdoor_Temperature_S | Outdoor temperature | °C | Read | |
| BI | 112 | CXGX_FilterStatus_S | Filter status | Read | 0=Ok, 1=Dirty | |
| BO | 110 | CXGX_DirtyFilter_Reset_C | Reset dirty filter sign | Command | 0=No Reset, 1=Reset | |
| AI | 124 | CXGX_Consumption Yesterday_S | Energy consumption yesterday | Wh/kWh | Read | |
| AI | 125 | CXGX_Consumption Today_S | Energy consumption today | Wh/kWh | Read | |
| AI | 126 | CXGX_Consumption Total_S | Energy consumption total | Wh/kWh | Read | |
| AI | 127 | CXGX_Consumption Yesterday_S_Heat | Energy consumption yesterday heat | Wh/kWh | Read | |
| AI | 128 | CXGX_Consumption Today_S_Heat | Energy consumption today heat | Wh/kWh | Read | |
| AI | 129 | CXGX_Consumption Total_S_Heat | Energy consumption total heat | Wh/kWh | Read | |
| AI | 130 | CXGX_Consumption Yesterday_S_Cool | Energy consumption yesterday cool | Wh/kWh | Read | |
| AI | 131 | CXGX_Consumption Today_S_Cool | Energy consumption today cool | Wh/kWh | Read | |
| AI | 132 | CXGX_Consumption Total_S_Cool | Energy consumption total cool | Wh/kWh | Read | |
| AI | 15001 | CXIndoorUnitX_ErrorCode_S | Indoor unit 1 error code (disabled by default) | Read | 0=No alarm, 1..9999=Error code | |
| AI | 15051 | CXOutdoorUnitX_ErrorCode_S | Outdoor unit 1 error code (disabled by default) | Read | 0=No alarm, 1..9999=Error code |
No points match these filters.
Object ID lookup: Intesis City Multi Gateway IN770 point IDs by name
BI0Centralized controller communication errorBO0Reset errors (all groups)BO1On/Off (all groups)MO0Mode (all IC groups)MO1Mode (all Lossnay groups)MO2Fan Speed (all IC groups)MO3Fan Speed (all Lossnay groups)MO4Vane Position (all IC groups)AO0Setpoint (all the groups)BI100CXGX_On/Off_SBO100CXGX_On/Off_CMI100CXGX_Mode_SMI101CXGX_Mode_SMI102CXGX_Mode_SMO100CXGX_Mode_CMO101CXGX_Mode_CMO102CXGX_Mode_CMI103CXGX_FanSpeed_SMI104CXGX_FanSpeed_SMO103CXGX_FanSpeed_CMO104CXGX_FanSpeed_CMI105CXGX_Vanes_SMO105CXGX_Vanes_CAI100CXGX_Setpoint_SAI101CXGX_Setpoint_SAO100CXGX_Setpoint_CAO101CXGX_Setpoint_CAI102CXGX_AmbientTemp_SMI106CXGX_OperationalStatus_LS_OA_SMO106CXGX_OperationalStatus_LS_OA_CAI103CXGX_OperationTimex100_SAI104CXGX_OperationTime%100_SBI101CXGX_ErrorStatus_SAI105CXGX_ErrorCode_SBO101CXGX_ErrorReset_CMI107CXGX_Model_SBI102CXGX_Allow_ONOFF_Panel_SBO102CXGX_Allow_ONOFF_Panel_CBI103CXGX_Allow_MODE_Panel_SBO103CXGX_Allow_MODE_Panel_CBI104CXGX_Allow_SETPOINT_Panel_SBO104CXGX_Allow_SETPOINT_Panel_cBI105CXGX_Allow_FILTERRESET_Panel_SBO105CXGX_Allow_FILTERRESET_Panel_CBI106CXGX_Allow_FANSPEED_Panel_SBO106CXGX_Allow_FANSPEED_Panel_CBI107CXGX_Allow_VANES_Panel_SBO107CXGX_Allow_VANES_Panel_CBI108CXGX_Allow_TIMER_Panel_SBO108CXGX_Allow_TIMER_Panel_CBI109CXGX_SetbackControl_SBO109CXGX_SetbackControl_CAI106CXGX_Min_Cool_Setpoint_SAO102CXGX_Min_Cool_Setpoint_CAI107CXGX_Max_Cool_Setpoint_SAO103CXGX_Max_Cool_Setpoint_CAI108CXGX_Min_Heat_Setpoint_SAO104CXGX_Min_Heat_Setpoint_CAI109CXGX_Max_Heat_Setpoint_SAO105CXGX_Max_Heat_Setpoint_CAI110CXGX_Min_Auto_Setpoint_SAO106CXGX_Min_Auto_Setpoint_CAI111CXGX_Max_Auto_Setpoint_SAO107CXGX_Max_Auto_Setpoint_CAI112CXGX_CoolDryAuto_Upper_DualSetpoint_SAO108CXGX_CoolDryAuto_Upper_DualSetpoint_CAI113CXGX_Heating_ATW_HWHP_Setpoint_SAO109CXGX_Heating_ATW_HWHP_Setpoint_CAI114CXGX_AutoHeat_Lower_DualSetpoint_SAO110CXGX_AutoHeat_Lower_DualSetpoint_CAI115CXGX_HeatingECO_Setpoint_SAO111CXGX_HeatingECO_Setpoint_CAI116CXGX_AutoSingle_Setpoint_SAO112CXGX_AutoSingle_Setpoint_CAI117CXGX_HotWater_Setpoint_SAO113CXGX_HotWater_Setpoint_CAI118CXGX_Setback_Upper_Setpoint_SAO114CXGX_Setback_Upper_Setpoint_CAI119CXGX_Setback_Lower_Setpoint_SAO115CXGX_Setback_Lower_Setpoint_CAI120CXGX_Antifreeze_Setpoint_SAO116CXGX_Antifreeze_Setpoint_CAI121CXGX_Cooling_Setpoint_SAO117CXGX_Cooling_Setpoint_CAI122CXGX_Room_Humidity_SBI110CXGX_Brightness_SBI111CXGX_Occupancy_SAI123CXGX_Outdoor_Temperature_SBI112CXGX_FilterStatus_SBO110CXGX_DirtyFilter_Reset_CAI124CXGX_Consumption Yesterday_SAI125CXGX_Consumption Today_SAI126CXGX_Consumption Total_SAI127CXGX_Consumption Yesterday_S_HeatAI128CXGX_Consumption Today_S_HeatAI129CXGX_Consumption Total_S_HeatAI130CXGX_Consumption Yesterday_S_CoolAI131CXGX_Consumption Today_S_CoolAI132CXGX_Consumption Total_S_CoolAI15001CXIndoorUnitX_ErrorCode_SAI15051CXOutdoorUnitX_ErrorCode_S
Integration notes
- Group instance = ((CC# - 1) x 8000) + (G x 100) + offset, CC# = centralized controller 1 or 2, G = group 1-50; controller 1 group 1 is shown (100-132). Global objects add (CC# - 1) x 8000.
- Per-unit error codes: ((CC# - 1) x 8000) + IU address + 15000 and + OU address + 15050; address 1 shown (15001, 15051). They are disabled by default and enabled per controller in MAPS.
- Three CXGX_Mode_S/_C pairs share a name: offset 0 for indoor units, 1 for Lossnay, 2 for air-to-water units. Two CXGX_FanSpeed_S/_C pairs (offsets 3 and 4) also share a name; the manual does not say which unit kind each serves.
- CXGX_Allow_SETPOINT_Panel_c is printed with a lower-case c.
- The BACnet table has no read/write column; access is inferred from object type. Consumption is Wh or kWh as set in MAPS.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
How many BACnet points does the Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway) have?
This list has 101 BACnet objects: 35 analog inputs, 19 analog outputs, 14 binary inputs, 13 binary outputs, 8 multi-state inputs, 12 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway) BACnet points are writable?
44 of the 101 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway) BACnet documentation?
The source is 700 Series Air Gateway IN770AIR***O000 - Mitsubishi Electric City Multi Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2026-03-16 v1.0.19, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770mitxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)?
Start with BO 100 CXGX_On/Off_C (Start/stop the group); MO 100 CXGX_Mode_C (Indoor-unit mode command); AO 100 CXGX_Setpoint_C (Setpoint command); MO 103 CXGX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 CXGX_On/Off_S (Run status); AI 100 CXGX_Setpoint_S (Setpoint in use); AI 102 CXGX_AmbientTemp_S (Group room temperature, °C); BI 101 CXGX_ErrorStatus_S (Group alarm); AI 105 CXGX_ErrorCode_S (Fault code (0 = no error)).
How do I enable BMS control of the Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)?
No enable point is documented. The CXGX_Allow_..._Panel_C objects (BO 102-108) block local remote functions per group.
How do I check these points on the real IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway IN770AIR***O000 - Mitsubishi Electric City Multi Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2026-03-16 v1.0.19. Object names, instances and units are reproduced as published; descriptions are our own.