VRF / split air conditioner BACnet gateway (1 indoor unit or group) · BACnet points list

Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

Intesis interface for one Daikin Sky or VRV indoor unit (or a group run as one) on the P1P2 remote-controller bus. DIP switch SW1-5 selects BACnet MS/TP (default) or Modbus RTU. It exposes 41 fixed objects: on/off, mode, setpoint, fan and both vane directions as _command/_status pairs, error and filter signals, occupancy logic, a remote lock and a virtual-temperature function.

This page lists 41 BACnet objects for the Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP) — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.

Manufacturer
Intesis
Model
IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Equipment
VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Equipment type
VRF & split air conditioners
BACnet objects
41 (19 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
246000
Also known as
IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP
Brands covered
Daikin
Source document
IN485DAI001R000 Gateway - Daikin Sky and VRV Systems to BACnet MS/TP and Modbus RTU - User Manual · rev. 2026-06-09 v1.0.20
Download CSV 41 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.

BMS integration notes: Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)

Integration in brief

Connect the gateway anywhere on the P1P2 bus, leave SW1-5 off for BACnet MS/TP, set the MAC address on SW2, then write the _command objects (on/off, mode, setpoint, fan) and read the _status objects. Several indoor units on one P1P2 bus behave as one unit.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0OnOff_commandStart/stop the indoor unitCommand
MO 0Mode_commandHeat/cool/fan/dry/auto selectionCommand
AO 0SetPoint_commandTemperature setpoint from the BMSCommand
MO 1FanSpeed_commandFan speed selectionCommand
BI 0OnOff_statusConfirm the unit is runningRead
AI 0SetPoint_statusSetpoint the unit is really usingRead
AI 1RoomTemperature_statusRoom/return temperature for trendingRead
BI 1ErrorActiveUnit alarmRead
AI 2ErrorCodeWhich fault is activeRead

Enable & remote start

No enable point is documented; the gateway accepts commands once it talks to the unit. BV 2 LockRemoteControl can lock the wired remote.

Sensors & values from the BMS

Two options. With the gateway as P1P2 header (SW1-1 on), reading temperature from the remote (SW1-2 on) and the Daikin system set to use the remote's sensor, the value written to AO 1 RoomTemperature_command replaces the unit's reference temperature. Until a valid value is written the unit shows error CJ (45 on BACnet). Otherwise the Virtual Temperature function recalculates the setpoint from AO 1; BI 14 shows when it is active and AI 17 shows the BMS setpoint.

Network setup

Watch out for

Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

41 of 41 shown
Type
Access
Show
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP) BACnet Points List
DescriptionStates
BImin0OnOff_statusUnit on/off statusRead0=Off, 1=On
BOmin0OnOff_commandStart/stop the indoor unitCommand0=Off, 1=On
MI0Mode_statusOperating mode in useRead1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto, 6=AutoHeat, 7=AutoCool, 8=AutoFan
MOmin0Mode_commandOperating mode commandCommand1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto
AImin0SetPoint_statusSetpoint the indoor unit is using°CRead
AI17UserSetPoint_statusBMS setpoint while virtual temperature is active°CRead
AOmin0SetPoint_commandTemperature setpoint from the BMS°CCommand
BI14VirtualTempActiveVirtual temperature function in useRead0=No, 1=Yes
MI1FanSpeed_statusCurrent fan speedRead1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MOmin1FanSpeed_commandFan speed commandCommand1=Auto, 2=Fan Speed 1, 3=Fan Speed 2, 4=Fan Speed 3, 5=Fan Speed 4, 6=Fan Speed 5
MI2AirDirectionUD_statusUp/down vane positionRead1=Pos 1, 2=Pos 2, 3=Pos 3, 4=Pos 4, 5=Pos 5, 6=Swing
MO2AirDirectionUD_commandUp/down vane commandCommand1=Pos 1, 2=Pos 2, 3=Pos 3, 4=Pos 4, 5=Pos 5, 6=Swing
MI3AirDirectionLR_statusLeft/right vane positionRead1=Position 1, 2=Position 2, 3=Position 3, 4=Position 4, 5=Position 5, 6=Swing
MO3AirDirectionLR_commandLeft/right vane commandCommand1=Position 1, 2=Position 2, 3=Position 3, 4=Position 4, 5=Position 5, 6=Swing
AImin1RoomTemperature_statusRoom temperature used by the unit°CRead
AO1RoomTemperature_commandRoom temperature written by the BMS°CCommand
AImin2ErrorCodeActive error code (number)Read
MI4ErrorCodeMActive error code (multistate)Read1=-, 2=CommError, 3=Initialization, ... (144 states; full table in the manual)
BImin1ErrorActiveAn error is activeRead0=No, 1=Error
AI4ErrorAddressAddress of the indoor unit reporting the errorRead
AV0OnTimeCounterRun-hours counterhWrite
BI6FilterSignFilter dirty signalRead0=OK, 1=Dirty
BO4FilterResetReset the filter signalCommand0=Normal, 1=Reset
MV0OccupancyOccupancy input for built-in occupancy logicWrite1=Occupied, 2=Unoccupied, 3=Disabled
AV1OccupiedCoolSetPointCooling setpoint when occupied°CWrite
AV2OccupiedHeatSetPointHeating setpoint when occupied°CWrite
AV3UnoccupiedCoolSetPointCooling setpoint when unoccupied°CWrite
AV4UnoccupiedHeatSetPointHeating setpoint when unoccupied°CWrite
BV0OccupancyContinuousCheckRe-run occupancy logic on temperature changeWrite0=Disabled, 1=Enabled
BV1UnoccupiedDeadbandActionUnoccupied action inside the deadbandWrite0=Off, 1=CurrentMode
BV2LockRemoteControlLock the wired remote controllerWrite0=Unlocked, 1=Locked
BI7ThermostatONUnit is actively heating or cooling (thermo on)Read0=Off, 1=On
AI9DIP_SW_S1_statusDIP switch SW1 value (decimal)Read
AI10DIP_SW_S2_statusDIP switch SW2 value (decimal)Read
AI11SerialNumberGateway serial numberRead
AV8WaitInit_as_MasterStart-up delay before the gateway talks on the bussWrite
MI13Indoor_Unit_Operation_Mode_RoleIndoor unit mode role (master/slave/free)Read1=Master Unit, 2=Slave Unit, 3=Free Unit
AI18FilterSignAddressAddress of the indoor unit reporting the filter signRead
MV1AC_IU_addressIndoor unit address to read (multi-unit buses)Write1-64 = indoor unit address 0-63
AI19Number_of_IU_ConnectedNumber of indoor units on the busRead
AV9Reserved_1Reserved, internal use onlyRead
Object ID lookup: Intesis Daikin VRV Gateway IN485DAI001R000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)

How many BACnet points does the Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP) have?

This list has 41 BACnet objects: 10 analog inputs, 2 analog outputs, 7 analog values, 5 binary inputs, 2 binary outputs, 3 binary values, 6 multi-state inputs, 4 multi-state outputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP) BACnet points are writable?

19 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP) BACnet documentation?

The source is IN485DAI001R000 Gateway - Daikin Sky and VRV Systems to BACnet MS/TP and Modbus RTU - User Manual, revision 2026-06-09 v1.0.20, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user_manual_in485dai001r000.pdf.

What are the minimum BACnet points to integrate the Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)?

Start with BO 0 OnOff_command (Start/stop the indoor unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).

How do I enable BMS control of the Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)?

No enable point is documented; the gateway accepts commands once it talks to the unit. BV 2 LockRemoteControl can lock the wired remote.

Can the BMS supply sensor values to the Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)?

Two options. With the gateway as P1P2 header (SW1-1 on), reading temperature from the remote (SW1-2 on) and the Daikin system set to use the remote's sensor, the value written to AO 1 RoomTemperature_command replaces the unit's reference temperature. Until a valid value is written the unit shows error CJ (45 on BACnet). Otherwise the Virtual Temperature function recalculates the setpoint from AO 1; BI 14 shows when it is active and AI 17 shows the BMS setpoint.

How do I check these points on the real IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Intesis BACnet points lists

Source: IN485DAI001R000 Gateway - Daikin Sky and VRV Systems to BACnet MS/TP and Modbus RTU - User Manual · rev. 2026-06-09 v1.0.20. Object names, instances and units are reproduced as published; descriptions are our own.