- Home
- BACnet points lists
- Intesis
- IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
VRF BACnet gateway (multiple indoor units, H-Link) · BACnet points list
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) BACnet points list
Updated 6 November 2026
Intesis 700 Series multi-protocol gateway set up for BACnet IP or BACnet MS/TP on a Hitachi or Hisense H-Link bus. It publishes gateway-wide commands, a block of outdoor-unit objects at (OU address x 25) + 20000 and a block of indoor-unit objects at (IU address x 100): on/off, mode, setpoint, fan, louver, coil and air temperatures, error code, filter, remote-controller permissions, dehumidification and energy consumption.
This page lists 60 BACnet objects for the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
- Equipment
- VRF BACnet gateway (multiple indoor units, H-Link)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 60 (16 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Wire the H-Link (TB2) bus to Port A (A1/A2), pick BACnet IP or BACnet MS/TP in Intesis MAPS, scan or add the units, send the project, then map each indoor unit's _C commands and _S status objects from its (IU address x 100) block. Instances 0-2 command every unit at once.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 100 | OXXUXX_On/Off_C | Start/stop indoor unit | Command |
| MO 100 | OXXUXX_Mode_C | Mode command | Command |
| AO 100 | OXXUXX_Setpoint_C | Setpoint command | Command |
| MO 101 | OXXUXX_FanSpeed_C | Fan speed command (1 = auto) | Command |
| BI 100 | OXXUXX_On/Off_S | Run status | Read |
| AI 100 | OXXUXX_Setpoint_S | Setpoint in use | Read |
| AI 102 | OXXUXX_Inlet Temp. | Return air temperature | Read |
| BI 102 | OXXUXX_Communication Status | Unit present on H-Link | Read |
| AI 106 | OXXUXX_Unit Error code | Fault code | Read |
Enable & remote start
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 102-105).
Network setup
- BACnet IP: DHCP for 30 seconds at first start-up, then the default IP 192.168.100.246.
- BACnet MS/TP uses the gateway's EIA-485 port.
- Units are found with the scan function in Intesis MAPS; send the project to the gateway after changes.
- With a Hitachi CSNET Manager on the bus the fan speed list shrinks to Low/Mid/High.
Watch out for
- On/Off, Mode, FanSpeed, Vane and Setpoint at instances 0-2 (BO 0, MO 0-2, AO 0) act on all units at once.
- Instance numbers follow the IU/OU address, so readdressing a unit changes its instances.
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 0 | On/Off (all units) | On/Off (all units) | Command | 0=Off, 1=On | |
| MO | 0 | Mode (all units) | Mode (all units) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MO | 1 | FanSpeed (all units) | FanSpeed (all units) | Command | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ (with a CSNET Manager: 1=Low, 2=Mid, 3=High) | |
| MO | 2 | Vane Position (all units) | Vane Position (all units) | Command | 1=Auto, 2..8=Pos1..Pos7 | |
| AO | 0 | Temperature Setpoint (all units) | Temperature Setpoint (all units) | °C | Command | |
| AI | 20000 | OUXX_Outdoor Air Temp. | Outdoor Air Temp. | °C | Read | |
| AI | 20001 | OUXX_Comp.Top Temp. | Comp.Top Temp. | °C | Read | |
| AI | 20002 | OUXX_Total Real Comp. Freq. | Total Real Comp. Freq. | Hz | Read | |
| AI | 20003 | OUXX_Total Comp. Current | Total Comp. Current | A | Read | |
| AI | 20004 | OUXX_Out Exp. Valve 1 Open | Out Exp. Valve 1 Open | % | Read | |
| AI | 20005 | OUXX_Discharge Pressure | Discharge Pressure | MPa | Read | |
| AI | 20006 | OUXX_Suction Pressure | Suction Pressure | MPa | Read | |
| BI | 20000 | OUXX_Communication Status | Communication Status | Read | 0=Not Exist, 1=Exist | |
| BImin | 100 | OXXUXX_On/Off_S | On/Off (status) | Read | 0=Off, 1=On | |
| BOmin | 100 | OXXUXX_On/Off_C | On/Off (command) | Command | 0=Off, 1=On | |
| MI | 100 | OXXUXX_Mode_S | Mode (status) | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MOmin | 100 | OXXUXX_Mode_C | Mode (command) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 100 | OXXUXX_Setpoint_S | Setpoint (status) | °C | Read | |
| AOmin | 100 | OXXUXX_Setpoint_C | Setpoint (command) | °C | Command | |
| MI | 101 | OXXUXX_FanSpeed_S | FanSpeed (status) | Read | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ (with a CSNET Manager: 1=Low, 2=Mid, 3=High) | |
| MOmin | 101 | OXXUXX_FanSpeed_C | FanSpeed (command) | Command | 1=Auto, 2=Low, 3=Mid, 4=High, 5=High+ (with a CSNET Manager: 1=Low, 2=Mid, 3=High) | |
| MI | 102 | OXXUXX_Vane Position_S | Vane Position (status) | Read | 1=Auto, 2..8=Pos1..Pos7 | |
| MO | 102 | OXXUXX_Vane Position_C | Vane Position (command) | Command | 1=Auto, 2..8=Pos1..Pos7 | |
| AI | 101 | OXXUXX_Remote Sensor Temp. | Remote Sensor Temp. | °C | Read | |
| AImin | 102 | OXXUXX_Inlet Temp. | Inlet Temp. | °C | Read | |
| AI | 103 | OXXUXX_Outlet Temp. | Outlet Temp. | °C | Read | |
| AI | 104 | OXXUXX_GasPipe Temp. | GasPipe Temp. | °C | Read | |
| AI | 105 | OXXUXX_LiquidPipe Temp. | LiquidPipe Temp. | °C | Read | |
| AImin | 106 | OXXUXX_Unit Error code | Unit error code | Read | ||
| BI | 101 | OXXUXX_FilterSign | FilterSign | Read | 0=Normal, 1=Alarm | |
| BO | 101 | OXXUXX_FilterReset | FilterReset | Command | 1=Reset | |
| BImin | 102 | OXXUXX_Communication Status | Communication Status | Read | 0=Not Exist, 1=Exist | |
| BI | 103 | OXXUXX_Allow On/Off from RC_S | Allow On/Off from RC (status) | Read | 0=Allowed, 1=Not allowed | |
| BO | 102 | OXXUXX_Allow On/Off from RC_C | Allow On/Off from RC (command) | Command | 0=Allowed, 1=Not allowed | |
| BI | 104 | OXXUXX_Allow Mode from RC_S | Allow Mode from RC (status) | Read | 0=Allowed, 1=Not allowed | |
| BO | 103 | OXXUXX_Allow Mode from RC_C | Allow Mode from RC (command) | Command | 0=Allowed, 1=Not allowed | |
| BI | 105 | OXXUXX_Allow Setpoint from RC_S | Allow Setpoint from RC (status) | Read | 0=Allowed, 1=Not allowed | |
| BO | 104 | OXXUXX_Allow Setpoint from RC_C | Allow Setpoint from RC (command) | Command | 0=Allowed, 1=Not allowed | |
| BI | 106 | OXXUXX_Allow Fan from RC_S | Allow Fan from RC (status) | Read | 0=Allowed, 1=Not allowed | |
| BO | 105 | OXXUXX_Allow Fan from RC_C | Allow Fan from RC (command) | Command | 0=Allowed, 1=Not allowed | |
| MI | 103 | OXXUXX_Unit type | Unit type | Read | 1=Not Defined, 2=SS, 3=FC, 4=VRF, 5=IU, 6=ES | |
| AI | 107 | OXXUXX_Unit Address | Unit Address (0-63) | Read | ||
| AI | 108 | OXXUXX_System Address | System Address (0-63) | Read | ||
| BI | 107 | OXXUXX_Dehumidification | Dehumidification | Read | 0=Disabled, 1=Enabled | |
| MI | 104 | OXXUXX_Dehum. Correction_S | Dehum. Correction (status) | Read | 1=0, 2=(-1), 3=(-2) | |
| MO | 103 | OXXUXX_Dehum. Correction_C | Dehum. Correction (command) | Command | 1=0, 2=(-1), 3=(-2) | |
| AI | 109 | OXXUXX_Comp. Stop Cause | Comp. Stop Cause | Read | 255=Operation Off; other values per the Hitachi manual | |
| AI | 110 | OXXUXX_Exp. Valve Open | Exp. Valve Open | % | Read | |
| MI | 105 | OXXUXX_Operat. Condition | Operat. Condition | Read | 1=Off, 2=Thermo Off, 3=Thermo On, 4=Alarm | |
| AI | 111 | OXXUXX_RC SW Temp. | RC SW Temp. | °C | Read | |
| BI | 108 | OXXUXX_RC SW Config | RC SW Config | Read | 0=Without RCS, 1=With RCS | |
| AI | 112 | OXXUXX_Consumption Yesterday_S | Consumption Yesterday (status) | Wh/kWh | Read | |
| AI | 113 | OXXUXX_Consumption Today_S | Consumption Today (status) | Wh/kWh | Read | |
| AI | 114 | OXXUXX_Consumption Total_S | Consumption Total (status) | Wh/kWh | Read | |
| AI | 115 | OXXUXX_Consumption Yesterday_S Heat | Consumption Yesterday, heat (status) | Wh/kWh | Read | |
| AI | 116 | OXXUXX_Consumption Today_S Heat | Consumption Today, heat (status) | Wh/kWh | Read | |
| AI | 117 | OXXUXX_Consumption Total_S Heat | Consumption Total, heat (status) | Wh/kWh | Read | |
| AI | 118 | OXXUXX_Consumption Yesterday_S Cool | Consumption Yesterday, cool (status) | Wh/kWh | Read | |
| AI | 119 | OXXUXX_Consumption Today_S Cool | Consumption Today, cool (status) | Wh/kWh | Read | |
| AI | 120 | OXXUXX_Consumption Total_S Cool | Consumption Total, cool (status) | Wh/kWh | Read |
No points match these filters.
Object ID lookup: Intesis Hitachi/Hisense VRF Gateway IN770 point IDs by name
BO0On/Off (all units)MO0Mode (all units)MO1FanSpeed (all units)MO2Vane Position (all units)AO0Temperature Setpoint (all units)AI20000OUXX_Outdoor Air Temp.AI20001OUXX_Comp.Top Temp.AI20002OUXX_Total Real Comp. Freq.AI20003OUXX_Total Comp. CurrentAI20004OUXX_Out Exp. Valve 1 OpenAI20005OUXX_Discharge PressureAI20006OUXX_Suction PressureBI20000OUXX_Communication StatusBI100OXXUXX_On/Off_SBO100OXXUXX_On/Off_CMI100OXXUXX_Mode_SMO100OXXUXX_Mode_CAI100OXXUXX_Setpoint_SAO100OXXUXX_Setpoint_CMI101OXXUXX_FanSpeed_SMO101OXXUXX_FanSpeed_CMI102OXXUXX_Vane Position_SMO102OXXUXX_Vane Position_CAI101OXXUXX_Remote Sensor Temp.AI102OXXUXX_Inlet Temp.AI103OXXUXX_Outlet Temp.AI104OXXUXX_GasPipe Temp.AI105OXXUXX_LiquidPipe Temp.AI106OXXUXX_Unit Error codeBI101OXXUXX_FilterSignBO101OXXUXX_FilterResetBI102OXXUXX_Communication StatusBI103OXXUXX_Allow On/Off from RC_SBO102OXXUXX_Allow On/Off from RC_CBI104OXXUXX_Allow Mode from RC_SBO103OXXUXX_Allow Mode from RC_CBI105OXXUXX_Allow Setpoint from RC_SBO104OXXUXX_Allow Setpoint from RC_CBI106OXXUXX_Allow Fan from RC_SBO105OXXUXX_Allow Fan from RC_CMI103OXXUXX_Unit typeAI107OXXUXX_Unit AddressAI108OXXUXX_System AddressBI107OXXUXX_DehumidificationMI104OXXUXX_Dehum. Correction_SMO103OXXUXX_Dehum. Correction_CAI109OXXUXX_Comp. Stop CauseAI110OXXUXX_Exp. Valve OpenMI105OXXUXX_Operat. ConditionAI111OXXUXX_RC SW Temp.BI108OXXUXX_RC SW ConfigAI112OXXUXX_Consumption Yesterday_SAI113OXXUXX_Consumption Today_SAI114OXXUXX_Consumption Total_SAI115OXXUXX_Consumption Yesterday_S HeatAI116OXXUXX_Consumption Today_S HeatAI117OXXUXX_Consumption Total_S HeatAI118OXXUXX_Consumption Yesterday_S CoolAI119OXXUXX_Consumption Today_S CoolAI120OXXUXX_Consumption Total_S Cool
Integration notes
- Indoor unit instance = (IU address x 100) + offset; IU address 1 is shown (100-120). Outdoor unit instance = (OU address x 25) + 20000 + offset; OU address 0 is shown (20000-20006).
- The Hitachi and Hisense manuals (both v1.1.8, 2025-12-09) print the same BACnet object table; this one entry covers both.
- With an SPX-RAMHLK adapter only part of the objects is supported (marked in the Hitachi manual).
- The BACnet table has no read/write column; access is inferred from object type (outputs commandable, inputs read-only).
- Consumption objects report Wh or kWh as set in Intesis MAPS.
- Replaces the older INBACHIT016O000/064O000 BACnet server (listed separately), which used different outdoor-unit instances.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
How many BACnet points does the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) have?
This list has 60 BACnet objects: 28 analog inputs, 2 analog outputs, 10 binary inputs, 7 binary outputs, 6 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) BACnet points are writable?
16 of the 60 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway) BACnet documentation?
The source is 700 Series Air Gateway IN770AIR***O000 - Hitachi VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual, revision 2025-12-09 v1.1.8, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770hitxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)?
Start with BO 100 OXXUXX_On/Off_C (Start/stop indoor unit); MO 100 OXXUXX_Mode_C (Mode command); AO 100 OXXUXX_Setpoint_C (Setpoint command); MO 101 OXXUXX_FanSpeed_C (Fan speed command (1 = auto)); BI 100 OXXUXX_On/Off_S (Run status); AI 100 OXXUXX_Setpoint_S (Setpoint in use); AI 102 OXXUXX_Inlet Temp. (Return air temperature); BI 102 OXXUXX_Communication Status (Unit present on H-Link); AI 106 OXXUXX_Unit Error code (Fault code).
How do I enable BMS control of the Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)?
No enable point is documented. Remote-controller permissions can be removed per unit with the Allow ... from RC_C objects (BO 102-105).
How do I check these points on the real IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway IN770AIR***O000 - Hitachi VRF Systems to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · rev. 2025-12-09 v1.1.8. Object names, instances and units are reproduced as published; descriptions are our own.