- IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Split air conditioner BACnet gateway (1 indoor unit) · BACnet points list
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP) BACnet points list
Updated 4 November 2026
Intesis interface for one Samsung NASA indoor unit (or a group of units that act as one) on the F3/F4 bus, with BACnet MS/TP or Modbus RTU selected on a DIP switch. It exposes 41 fixed objects: on/off, mode, setpoint, fan and vane commands with matching status objects, error and filter signals, WindFree and air-clean modes, Cassette 360 airflow and a dual-setpoint (DSP) function.
This page lists 41 BACnet objects for the Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
- Equipment
- Split air conditioner BACnet gateway (1 indoor unit)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 41 (16 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 246000
- Also known as
- IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP
- Brands covered
- Samsung
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Wire the gateway to the Samsung F3/F4 bus, leave SW1 position 5 OFF for BACnet MS/TP, set the MAC address on SW2, then write the _command objects and read back the _status objects. Several indoor units on one gateway behave as one unit.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 0 | OnOff_command | Start/stop the unit | Command |
| MO 0 | Mode_command | Heat/cool/fan/dry/auto selection | Command |
| AO 0 | SetPoint_command | Temperature setpoint from the BMS | Command |
| MO 1 | FanSpeed_command | Fan speed selection | Command |
| BI 0 | OnOff_status | Confirm the unit is running | Read |
| AI 0 | SetPoint_status | Setpoint the unit is really using | Read |
| AI 1 | RoomTemperature_status | Room/return temperature for trending | Read |
| BI 1 | ErrorActive | Unit alarm | Read |
| AI 2 | ErrorCode | Which fault is active | Read |
Enable & remote start
No enable point is documented. BV 2 LockRemoteControl can lock the wired remote.
Sensors & values from the BMS
To use a BMS room sensor, write its value to AO 1 RoomTemperature_command; the unit then uses it as its reference temperature. Only write it when a BMS sensor is meant to replace the unit's own reading, and write 0x8000 to stop using it.
Network setup
- SW1 position 5 OFF = BACnet MS/TP (default), ON = Modbus RTU.
- Baud rate on SW1; autobaud is the default and follows other MS/TP devices on the bus.
- Default device instance 246000; in automatic mode it is 246000 + the MAC address set on SW2. Writing Object_Identifier switches to manual addressing until a factory reset.
- SW2 position 8 selects °C (default) or °F.
- Factory reset: set all SW1 and SW2 switches ON, power-cycle, then set them all OFF within 30 seconds.
Watch out for
- The gateway cannot tell whether dual setpoint is enabled on the Samsung side. Turn it on from the BMS with BV 5 DualSetpoint_active = 2, then write AO 3 (heat) and AO 4 (cool); also set the wired remote to DSP mode or it shows the average.
- In Fan mode the unit keeps a new setpoint but the wired remote may still show the old one until the next write in a temperature mode.
- Write the _command object and read the _status object.
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | OnOff_status | Unit on/off status | Read | 1=Off, 2=On | |
| BOmin | 0 | OnOff_command | Start/stop the indoor unit | Command | 1=Off, 2=On | |
| MI | 0 | Mode_status | Operating mode in use | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| MOmin | 0 | Mode_command | Operating mode command | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | |
| AImin | 0 | SetPoint_status | Setpoint the indoor unit is using | °C | Read | |
| AOmin | 0 | SetPoint_command | Temperature setpoint from the BMS | °C | Command | |
| AI | 17 | UserSetPoint_status | User setpoint as reported by the gateway | °C | Read | |
| MI | 1 | FanSpeed_status | Current fan speed | Read | 1=Auto, 2=Fan speed 1, 3=Fan speed 2, 4=Fan speed 3, 5=Fan speed 4 | |
| MOmin | 1 | FanSpeed_command | Fan speed command | Command | 1=Auto, 2=Fan speed 1, 3=Fan speed 2, 4=Fan speed 3, 5=Fan speed 4 | |
| MI | 2 | AirDirectionUD_status | Up/down vane position | Read | 1=Auto/Stop, 2=Swing | |
| MO | 2 | AirDirectionUD_command | Up/down vane command | Command | 1=Auto/Stop, 2=Swing | |
| MI | 3 | AirDirectionLR_status | Left/right vane position | Read | 1=Auto/Stop, 2=Swing | |
| MO | 3 | AirDirectionLR_command | Left/right vane command | Command | 1=Auto/Stop, 2=Swing | |
| AImin | 1 | RoomTemperature_status | Room temperature used by the unit | °C | Read | |
| AO | 1 | RoomTemperature_command | Room temperature written by the BMS | °C | Command | |
| AImin | 2 | ErrorCode | Active error code (number) | Read | ||
| MI | 4 | ErrorCodeM | Active error code (multistate) | Read | ||
| BImin | 1 | ErrorActive | An error is active | Read | 1=No error, 2=Error | |
| AI | 4 | ErrorAddress | Address of the indoor unit with the error | Read | ||
| AV | 0 | OnTimeCounter | Run-hours counter | h | Write | |
| BI | 6 | FilterSign | Filter-clean indication | Read | 1=No, 2=Yes | |
| AI | 18 | FilterSignAddress | Address of the unit showing the filter sign | Read | ||
| BO | 4 | FilterReset | Reset the filter sign | Command | 1=Normal, 2=Reset | |
| BV | 2 | LockRemoteControl | Lock the wired remote controller | Write | 1=Unlocked, 2=Locked | |
| AI | 9 | DIP_SW_S1_status | DIP switch SW1 value (decimal) | Read | ||
| AI | 10 | DIP_SW_S2_status | DIP switch SW2 value (decimal) | Read | ||
| AI | 11 | SerialNumber | Gateway serial number | Read | ||
| AI | 19 | Number_of_IU_connected | Indoor units found on the RC bus | Read | ||
| AI | 20 | IU_Address_status_reported | Address of the indoor unit being reported | Read | ||
| AV | 7 | IU_Pos_status_reported | Position of the reported unit in the internal list | Read | ||
| BI | 16 | WindFree_mode_status | WindFree mode status | Read | 1=Off, 2=On | |
| BO | 13 | WindFree_mode_command | WindFree mode command | Command | 1=Off, 2=On | |
| BI | 17 | AirClean_mode_status | Air clean mode status | Read | 1=Off, 2=On | |
| BO | 14 | AirClean_mode_command | Air clean mode command | Command | 1=Off, 2=On | |
| MI | 12 | 360_CST_AirFlow_Direction_status | Cassette 360 airflow pattern | Read | 1=Spot, 2=Mid, 3=Wide, 4=Swing, 5=Other | |
| MO | 8 | 360_CST_AirFlow_Direction_command | Cassette 360 airflow pattern command | Command | 1=Spot, 2=Mid, 3=Wide, 4=Swing, 5=Other | |
| BV | 5 | DualSetpoint_active | Dual setpoint function on/off | Write | 1=Dual setpoint not active, 2=Dual setpoint active | |
| AI | 21 | DualSetpoint_Heat_Temperature_status | Dual setpoint heating value | °C | Read | |
| AO | 3 | DualSetpoint_Heat_Temperature_command | Dual setpoint heating command | °C | Command | |
| AI | 22 | DualSetpoint_Cool_Temperature_status | Dual setpoint cooling value | °C | Read | |
| AO | 4 | DualSetpoint_Cool_Temperature_command | Dual setpoint cooling command | °C | Command |
No points match these filters.
Object ID lookup: Intesis Samsung Gateway IN485SAM001R000 point IDs by name
BI0OnOff_statusBO0OnOff_commandMI0Mode_statusMO0Mode_commandAI0SetPoint_statusAO0SetPoint_commandAI17UserSetPoint_statusMI1FanSpeed_statusMO1FanSpeed_commandMI2AirDirectionUD_statusMO2AirDirectionUD_commandMI3AirDirectionLR_statusMO3AirDirectionLR_commandAI1RoomTemperature_statusAO1RoomTemperature_commandAI2ErrorCodeMI4ErrorCodeMBI1ErrorActiveAI4ErrorAddressAV0OnTimeCounterBI6FilterSignAI18FilterSignAddressBO4FilterResetBV2LockRemoteControlAI9DIP_SW_S1_statusAI10DIP_SW_S2_statusAI11SerialNumberAI19Number_of_IU_connectedAI20IU_Address_status_reportedAV7IU_Pos_status_reportedBI16WindFree_mode_statusBO13WindFree_mode_commandBI17AirClean_mode_statusBO14AirClean_mode_commandMI12360_CST_AirFlow_Direction_statusMO8360_CST_AirFlow_Direction_commandBV5DualSetpoint_activeAI21DualSetpoint_Heat_Temperature_statusAO3DualSetpoint_Heat_Temperature_commandAI22DualSetpoint_Cool_Temperature_statusAO4DualSetpoint_Cool_Temperature_command
Integration notes
- The manual's object table has no read/write column. Access here is inferred: AO/BO/MO command objects as commandable, AV/BV as writable (except IU_Pos_status_reported, which only reports), inputs as read-only.
- Binary objects are listed in the manual with values 1 and 2 (for example 1: Off, 2: On); they are kept as printed.
- Footnote numbers printed after some object names in the table (for example Mode_status2) are not part of the name and were removed.
- WindFree, air-clean and Cassette 360 airflow objects only apply to indoor units with those features; on Cassette 360 units the up/down airflow uses the 360_CST objects instead of AirDirectionUD.
- Temperature objects follow the °C/°F setting on DIP switch SW2 position 8.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
How many BACnet points does the Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP) have?
This list has 41 BACnet objects: 13 analog inputs, 4 analog outputs, 2 analog values, 5 binary inputs, 4 binary outputs, 2 binary values, 6 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP) BACnet points are writable?
16 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP) BACnet documentation?
The source is IN485SAM001R000 User Manual - Samsung NASA Systems to BACnet MS/TP and Modbus RTU, revision 2026-03-11 v1.0.0, published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in485sam001r000.pdf.
What are the minimum BACnet points to integrate the Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)?
Start with BO 0 OnOff_command (Start/stop the unit); MO 0 Mode_command (Heat/cool/fan/dry/auto selection); AO 0 SetPoint_command (Temperature setpoint from the BMS); MO 1 FanSpeed_command (Fan speed selection); BI 0 OnOff_status (Confirm the unit is running); AI 0 SetPoint_status (Setpoint the unit is really using); AI 1 RoomTemperature_status (Room/return temperature for trending); BI 1 ErrorActive (Unit alarm); AI 2 ErrorCode (Which fault is active).
How do I enable BMS control of the Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)?
No enable point is documented. BV 2 LockRemoteControl can lock the wired remote.
Can the BMS supply sensor values to the Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)?
To use a BMS room sensor, write its value to AO 1 RoomTemperature_command; the unit then uses it as its reference temperature. Only write it when a BMS sensor is meant to replace the unit's own reading, and write 0x8000 to stop using it.
How do I check these points on the real IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: IN485SAM001R000 User Manual - Samsung NASA Systems to BACnet MS/TP and Modbus RTU · rev. 2026-03-11 v1.0.0. Object names, instances and units are reproduced as published; descriptions are our own.