 "manufacturer": "Intesis",
 "manufacturer_slug": "intesis",
 "model": "IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)",
 "model_slug": "in485mit001a000",
 "aliases": [
  "IN485MIT001A000",
  "Mitsubishi Ecodan BACnet",
  "Ecodan BACnet MS/TP",
  "Mitsubishi air-to-water heat pump BACnet",
  "Ecodan CN105 BACnet",
  "Intesis Ecodan"
 ],
 "equipment_type": "Air-to-water heat pump BACnet gateway",
 "applies_to": "Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.",
 "summary": "Intesis interface for one Mitsubishi Electric Ecodan air-to-water system, plugged into CN105 and speaking BACnet MS/TP (default) or Modbus RTU. It exposes 115 objects: system and zone on/off, heat/cool mode, zone 1 and zone 2 setpoints with limits and water temperatures, DHW control (eco, boost, legionella), holiday mode, compressor, pump and backup-heater status, flow and energy counters.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": 246000,
 "access_inferred": true,
 "notes": [
  "The manual's object table has no read/write column. Access is inferred: AO/BO/MO command objects as commandable, inputs as read-only.",
  "Footnote numbers printed after some object names in the table (for example ErrorCode_status2) are not part of the name and were removed.",
  "ErrorCode_status (AI 2) shows the code as a Mitsubishi centralized controller shows it; ErrorSubCode_status (AI 3) shows it as the Ecodan unit shows it.",
  "Run-hour and flow counters roll back to 0 at 720896; energy counters at 2147483647 kWh.",
  "Temperatures follow the °C/°F setting on DIP switch SW2 position 8."
 ],
 "source": {
  "title": "IN485MIT001A000 User Manual - Mitsubishi Electric Ecodan Air-to-Water Units to BACnet MS/TP and Modbus RTU",
  "doc_number": null,
  "revision_date": "2025-12-02 v1.0.3",
  "url": "https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in485mit001a000.pdf"
 },
 "integration": {
  "summary": "Plug the gateway into CN105 on the Ecodan board, leave SW1 position 5 OFF for BACnet MS/TP and set the MAC address on SW2. Turn the system on with OnOff_command, set heat or cool with ZonesMode_command (both zones follow), and write zone and DHW setpoints to their _command objects.",
  "minimum_points": [
   {
    "ref": "BO 4",
    "name": "OnOff_command",
    "why": "Turn the Ecodan system on/off"
   },
   {
    "ref": "MO 0",
    "name": "ZonesMode_command",
    "why": "Heat or cool for both zones"
   },
   {
    "ref": "BO 15",
    "name": "DHWOnOff_command",
    "why": "Domestic hot water on/off"
   },
   {
    "ref": "AO 3",
    "name": "Zone1TempSetpoint_command",
    "why": "Zone 1 setpoint from the BMS"
   },
   {
    "ref": "AO 24",
    "name": "DHWTempSetpoint_command",
    "why": "DHW tank setpoint"
   },
   {
    "ref": "BI 5",
    "name": "OnOff_status",
    "why": "Confirms the system is on"
   },
   {
    "ref": "AI 74",
    "name": "TempOutletWaterRef_status",
    "why": "Flow water temperature"
   },
   {
    "ref": "BI 1",
    "name": "ErrorFlag_status",
    "why": "Unit alarm"
   },
   {
    "ref": "AI 2",
    "name": "ErrorCode_status",
    "why": "Which fault is active"
   }
  ],
  "enable": "BO 3 RemoteControlLock_command = 1 lets only the BMS control the unit; remote-controller commands are then ignored.",
  "heartbeat": null,
  "remote_sensors": "Write a BMS room temperature to AO 8 Zone1TempBACnetRoomThermAmbientRef_command (AO 22 for zone 2). Once a valid value is written, the gateway's Virtual Temperature function uses it to offset the setpoint.",
  "setup": [
   "SW1 P5: OFF = BACnet MS/TP (default), ON = Modbus RTU; SW1 P6-P8 baud rate, autobaud by default.",
   "MS/TP MAC address on SW2 P1-P7; SW2 P8 selects °C (default) or °F.",
   "Default device instance 246000; in automatic mode it is 246000 + the MAC address. Writing Object_Identifier switches to manual addressing until a factory reset.",
   "DIP switch changes take effect after a reboot."
  ],
  "gotchas": [
   "Write the _command object and read the matching _status object; they have different object types and instance numbers.",
   "Custom setpoint limits cannot go past the unit's own limits (the Unit...Limit objects); the Applied...Limit objects show the range in force.",
   "Write 0 to CompressorOperatingTime_command or CirculationPumpOperatingTime_command to reset that run-hour counter."
  ]
 },
 "covers_brands": [
  "Mitsubishi Electric"
 ],
 "short_model": "Mitsubishi Electric Ecodan Gateway IN485MIT001A000",
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "SerialNumber",
   "description": "Gateway serial number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "DIP_SW_1_status",
   "description": "DIP SW1 (status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "DIP_SW_2_status",
   "description": "DIP SW2 (status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "IndoorUnitAddress_status",
   "description": "Indoor unit address (status)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "IndoorUnitAddress_command",
   "description": "Indoor unit address (command)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "ErrorFlag_status",
   "description": "Error flag (status)",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=Error"
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "ErrorCode_status",
   "description": "Error code (status)",
   "units": "",
   "access": "R",
   "states": "0=No error, other=error code"
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "ErrorSubCode_status",
   "description": "Error sub code (status)",
   "units": "",
   "access": "R",
   "states": "0=No error, other=error code"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "RefrigerantLeakDetectorSignalFlag_status",
   "description": "Refrigerant leak detector signal flag (status)",
   "units": "",
   "access": "R",
   "states": "0=No Error, 1=Error"
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "OperatingTimeCountHour_status",
   "description": "Operating time count hours (status)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "RemoteControlLock_status",
   "description": "Remote control lock (status)",
   "units": "",
   "access": "R",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "RemoteControlLock_command",
   "description": "Remote control lock (command)",
   "units": "",
   "access": "C",
   "states": "0=Unlocked, 1=Locked"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "OnOff_status",
   "description": "Unit on/off status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "OnOff_command",
   "description": "Start/stop the indoor unit",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Operation_status",
   "description": "Operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Not Operating, 1=Operating"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "ZonesOnOff_status",
   "description": "Zones on/off (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "ZonesOperation_status",
   "description": "Zones operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Not Operating, 1=Operating"
  },
  {
   "type": "MI",
   "instance": 0,
   "name": "ZonesMode_status",
   "description": "Zones mode (status)",
   "units": "",
   "access": "R",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "MO",
   "instance": 0,
   "name": "ZonesMode_command",
   "description": "Zones mode (command)",
   "units": "",
   "access": "C",
   "states": "1=Heat, 2=Cool"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Zone1OnOff_status",
   "description": "Zone 1 on/off (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Zone1Operation_status",
   "description": "Zone 1 operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Not Operating, 1=Operating"
  },
  {
   "type": "MI",
   "instance": 2,
   "name": "Zone1ControlType_status",
   "description": "Zone 1 control type (status)",
   "units": "",
   "access": "R",
   "states": "1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "Zone1ControlType_command",
   "description": "Zone 1 control type (command)",
   "units": "",
   "access": "C",
   "states": "1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve"
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Zone1TempSetpoint_status",
   "description": "Zone 1 temperature setpoint (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "Zone1TempSetpoint_command",
   "description": "Zone 1 temperature setpoint (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Zone1TempSetpointLowCustomerLimitHeat_status",
   "description": "Zone 1 temperature setpoint lower customer limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "Zone1TempSetpointLowCustomerLimitHeat_command",
   "description": "Zone 1 temperature setpoint lower customer limit heat (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Zone1TempSetpointUpCustomerLimitHeat_status",
   "description": "Zone 1 temperature setpoint upper customer limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "Zone1TempSetpointUpCustomerLimitHeat_command",
   "description": "Zone 1 temperature setpoint upper customer limit heat (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Zone1TempSetpointLowCustomerLimitCool_status",
   "description": "Zone 1 temperature setpoint lower customer limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "Zone1TempSetpointLowCustomerLimitCool_command",
   "description": "Zone 1 temperature setpoint lower customer limit cool (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Zone1TempSetpointUpCustomerLimitCool_status",
   "description": "Zone 1 temperature setpoint upper customer limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 7,
   "name": "Zone1TempSetpointUpCustomerLimitCool_command",
   "description": "Zone 1 temperature setpoint upper customer limit cool (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Zone1TempSetpointUnitLowLimitHeat_status",
   "description": "Zone 1 temperature setpoint unit lower limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Zone1TempSetpointUnitUpLimitHeat_status",
   "description": "Zone 1 temperature setpoint unit upper limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Zone1TempSetpointUnitLowLimitCool_status",
   "description": "Zone 1 temperature setpoint unit lower limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Zone1TempSetpointUnitUpLimitCool_status",
   "description": "Zone 1 temperature setpoint unit upper limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Zone1TempSetpointAppliedLowLimitHeat_status",
   "description": "Zone 1 temperature setpoint applied lower limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Zone1TempSetpointAppliedUpLimitHeat_status",
   "description": "Zone 1 temperature setpoint applied upper limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Zone1TempSetpointAppliedLowLimitCool_status",
   "description": "Zone 1 temperature setpoint applied lower limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Zone1TempSetpointAppliedUpLimitCool_status",
   "description": "Zone 1 temperature setpoint applied upper limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Zone1TempRef_status",
   "description": "Zone 1 temperature reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 8,
   "name": "Zone1TempBACnetRoomThermAmbientRef_command",
   "description": "Zone 1 temperature BMS room sensor ambient reading (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Zone1TempOutletWaterRef_status",
   "description": "Zone 1 temperature outlet water reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Zone1TempInletWaterRef_status",
   "description": "Zone 1 temperature inlet water reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "Zone2OnOff_status",
   "description": "Zone 2 on/off (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "Zone2Operation_status",
   "description": "Zone 2 operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Not Operating, 1=Operating"
  },
  {
   "type": "MI",
   "instance": 5,
   "name": "Zone2ControlType_status",
   "description": "Zone 2 control type (status)",
   "units": "",
   "access": "R",
   "states": "1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve"
  },
  {
   "type": "MO",
   "instance": 3,
   "name": "Zone2ControlType_command",
   "description": "Zone 2 control type (command)",
   "units": "",
   "access": "C",
   "states": "1=Outlet Water Temperature, 2=Room Thermostat Ambient Temperature, 3=Weather Compensation Curve"
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Zone2TempSetpoint_status",
   "description": "Zone 2 temperature setpoint (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 17,
   "name": "Zone2TempSetpoint_command",
   "description": "Zone 2 temperature setpoint (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Zone2TempSetpointLowCustomerLimitHeat_status",
   "description": "Zone 2 temperature setpoint lower customer limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 18,
   "name": "Zone2TempSetpointLowCustomerLimitHeat_command",
   "description": "Zone 2 temperature setpoint lower customer limit heat (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Zone2TempSetpointUpCustomerLimitHeat_status",
   "description": "Zone 2 temperature setpoint upper customer limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 19,
   "name": "Zone2TempSetpointUpCustomerLimitHeat_command",
   "description": "Zone 2 temperature setpoint upper customer limit heat (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "Zone2TempSetpointLowCustomerLimitCool_status",
   "description": "Zone 2 temperature setpoint lower customer limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 20,
   "name": "Zone2TempSetpointLowCustomerLimitCool_command",
   "description": "Zone 2 temperature setpoint lower customer limit cool (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "Zone2TempSetpointUpCustomerLimitCool_status",
   "description": "Zone 2 temperature setpoint upper customer limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 21,
   "name": "Zone2TempSetpointUpCustomerLimitCool_command",
   "description": "Zone 2 temperature setpoint upper customer limit cool (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "Zone2TempSetpointUnitLowLimitHeat_status",
   "description": "Zone 2 temperature setpoint unit lower limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "Zone2TempSetpointUnitUpLimitHeat_status",
   "description": "Zone 2 temperature setpoint unit upper limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "Zone2TempSetpointUnitLowLimitCool_status",
   "description": "Zone 2 temperature setpoint unit lower limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "Zone2TempSetpointUnitUpLimitCool_status",
   "description": "Zone 2 temperature setpoint unit upper limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "Zone2TempSetpointAppliedLowLimitHeat_status",
   "description": "Zone 2 temperature setpoint applied lower limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "Zone2TempSetpointAppliedUpLimitHeat_status",
   "description": "Zone 2 temperature setpoint applied upper limit heat (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "Zone2TempSetpointAppliedLowLimitCool_status",
   "description": "Zone 2 temperature setpoint applied lower limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "Zone2TempSetpointAppliedUpLimitCool_status",
   "description": "Zone 2 temperature setpoint applied upper limit cool (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "Zone2TempRef_status",
   "description": "Zone 2 temperature reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 22,
   "name": "Zone2TempBACnetRoomThermAmbientRef_command",
   "description": "Zone 2 temperature BMS room sensor ambient reading (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "Zone2TempOutletWaterRef_status",
   "description": "Zone 2 temperature outlet water reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "Zone2TempInletWaterRef_status",
   "description": "Zone 2 temperature inlet water reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "DHWOnOff_status",
   "description": "DHW on/off (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 15,
   "name": "DHWOnOff_command",
   "description": "DHW on/off (command)",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "DHWOperation_status",
   "description": "DHW operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Not Operating, 1=Operating"
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "DHWTempSetpoint_status",
   "description": "DHW temperature setpoint (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 24,
   "name": "DHWTempSetpoint_command",
   "description": "DHW temperature setpoint (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "DHWTempSetpointCustomLowLimit_status",
   "description": "DHW temperature setpoint custom lower limit (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 25,
   "name": "DHWTempSetpointCustomLowLimit_command",
   "description": "DHW temperature setpoint custom lower limit (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "DHWTempSetpointCustomUpLimit_status",
   "description": "DHW temperature setpoint custom upper limit (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 26,
   "name": "DHWTempSetpointCustomUpLimit_command",
   "description": "DHW temperature setpoint custom upper limit (command)",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "DHWTempSetpointTankLowLimit_status",
   "description": "DHW temperature setpoint tank lower limit (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "DHWTempSetpointTankUpLimit_status",
   "description": "DHW temperature setpoint tank upper limit (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "DHWTempSetpointAppliedLowLimit_status",
   "description": "DHW temperature setpoint applied lower limit (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "DHWTempSetpointAppliedUpLimit_status",
   "description": "DHW temperature setpoint applied upper limit (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "DHWTempTankRef_status",
   "description": "DHW temperature tank reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "DHWEcoMode_status",
   "description": "DHW eco mode (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 18,
   "name": "DHWEcoMode_command",
   "description": "DHW eco mode (command)",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "DHWPowerfulOperation_status",
   "description": "DHW powerful operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 21,
   "name": "DHWPowerfulOperation_command",
   "description": "DHW powerful operation (command)",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "DHWDisinfectionMode_status",
   "description": "DHW disinfection mode (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "TempA2WUnitOutdoorAmbientRef_status",
   "description": "Temperature heatpump unit outdoor ambient reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "TempRefrigerantRef_status",
   "description": "Temperature refrigerant reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "TempOutletWaterRef_status",
   "description": "Temperature outlet water reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "TempInletWaterRef_status",
   "description": "Temperature inlet water reading (status)",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "HolidayMode_status",
   "description": "Holiday mode (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BO",
   "instance": 23,
   "name": "HolidayMode_command",
   "description": "Holiday mode (command)",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "EmergencyOperation_status",
   "description": "Emergency operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "DefrostStartUp_status",
   "description": "Defrost startup (status)",
   "units": "",
   "access": "R",
   "states": "0=Defrost/Start Up, 1=Hot Start"
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "ThreeWayValveOperation_status",
   "description": "Three way valve operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Climatize, 1=DHW"
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "BackUpHeaterOperationLevel1_status",
   "description": "Backup heater operation level 1 (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "BackUpHeaterOperationLevel2_status",
   "description": "Backup heater operation level 2 (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "CompressorOperation_status",
   "description": "Compressor operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "CompressorOperatingTime_status",
   "description": "Compressor operating time (status)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 30,
   "name": "CompressorOperatingTime_command",
   "description": "Compressor operating time (command)",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "CirculationPumpOperation_status",
   "description": "Circulation pump operation (status)",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "CirculationPumpOperatingTime_status",
   "description": "Circulation pump operating time (status)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 31,
   "name": "CirculationPumpOperatingTime_command",
   "description": "Circulation pump operating time (command)",
   "units": "h",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "WaterFlowRate_status",
   "description": "Water flow rate (status)",
   "units": "l/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "EnergyConsumptionTotal_status",
   "description": "Energy consumption total (status)",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "EnergyConsumptionZonesHeat_status",
   "description": "Energy consumption zones heat (status)",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "EnergyConsumptionZonesCool_status",
   "description": "Energy consumption zones cool (status)",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "EnergyConsumptionDHW_status",
   "description": "Energy consumption DHW (status)",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 45,
   "name": "ZonesHeatModeSupport_status",
   "description": "Zones heat mode support (status)",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BI",
   "instance": 46,
   "name": "ZonesCoolModeSupport_status",
   "description": "Zones cool mode support (status)",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  },
  {
   "type": "BI",
   "instance": 47,
   "name": "DHWSupport_status",
   "description": "DHW support (status)",
   "units": "",
   "access": "R",
   "states": "0=No, 1=Yes"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/intesis/in485mit001a000",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}