- Home
- BACnet points lists
- Intesis
- IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
VRF BACnet gateway (Mitsubishi Heavy Industries, multi-unit) · BACnet points list
Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet) BACnet points list
Updated 12 November 2026
The IN776MHI***O000 is a multi-protocol Intesis 700 Series gateway for Mitsubishi Heavy Industries VRF systems that serves them as BACnet IP or BACnet MS/TP objects (one map for both). It has global (all units) objects, an outdoor-unit block with compressor, temperature and pressure readings, and a 25-object-wide block per indoor unit; instances follow fixed formulas.
This page lists 66 BACnet objects for the Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet) — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Intesis’s own free documentation, linked below.
- Manufacturer
- Intesis
- Model
- IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
- Equipment
- VRF BACnet gateway (Mitsubishi Heavy Industries, multi-unit)
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 66 (19 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- IN776MHI, IN776MHIO000, IN776MHI***O000, IN776MHI00LO000, 700 Series Air MHI, Intesis MHI VRF BACnet gateway, Mitsubishi Heavy Industries VRF BACnet, MHI KX VRF BACnet
Reference only, provided as-is: verify against Intesis’s current documentation and the live device before use. Not official Intesis information. Terms of use.
BMS integration notes: Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
Connect the gateway to the MHI VRF bus, configure the units in Intesis MAPS, then map each indoor unit's _C/_S objects from its block (IU x 25). Use the all-units objects (15000+) for global commands.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 25 | IUXX_On/Off_C | Start/stop indoor unit | Command |
| MO 25 | IUXX_Operation Mode_C | Mode command | Command |
| AO 25 | IUXX_Temperature Setpoint_C | Setpoint command | Command |
| MO 26 | IUXX_FanSpeed_C | Fan speed command | Command |
| BI 26 | IUXX_On/Off_S | Run status | Read |
| AI 25 | IUXX_Temperature Setpoint_S | Setpoint in use | Read |
| AI 26 | IUXX_Room Temperature_S | Room temperature | Read |
| BI 25 | IUXX_Communication Status_S | Unit offline alarm | Read |
| AI 27 | IUXX_Unit Error code_S | Fault code (0 = no error) | Read |
| BI 15000 | Gateway Communication Status | Gateway communication error | Read |
Enable & remote start
No enable point is documented; remote controllers can be locked per unit with IUXX_Remote Lock_C or globally with Remote Lock.
Network setup
- BACnet IP or BACnet MS/TP is selected in Intesis MAPS; the object map is the same for both.
Watch out for
- Instances are formula-based: indoor unit n uses n x 25 + offset, outdoor unit n uses n x 20 + 10000 + offset.
- Use the Dualsetpoint objects instead of the single setpoint when Dual-Setpoint is enabled.
Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 15000 | Gateway Communication Status | Read | 0=No error, 1=Error | ||
| BO | 15000 | On/Off (all units) | Command | 0=Off, 1=On | ||
| MO | 15000 | Mode (all units) | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | ||
| AO | 15000 | Temperature Setpoint (all units) | Only when the Dual-Setpoint function is disabled | °C/°F | Command | |
| MO | 15001 | FanSpeed (all units) | Command | 1=Low, 2=Medium, 3=High, 4=Powerful | ||
| BO | 15001 | Remote Lock | Command | 0=Unlock, 1=Lock | ||
| AO | 15001 | Dualsetpoint Cool Temperature (all units) | Only when the Dual-Setpoint function is enabled | °C/°F | Command | |
| AO | 15002 | Dualsetpoint Heat Temperature (all units) | Only when the Dual-Setpoint function is enabled | °C/°F | Command | |
| AO | 15003 | Dualsetpoint Auto Temperature (all units) | Only when the Dual-Setpoint function is enabled | °C/°F | Command | |
| AI | 10020 | OUXX_Compressor 1 Frequency | Hz | Read | ||
| AI | 10021 | OUXX_Compressor 2 Frequency | Hz | Read | ||
| AI | 10022 | OUXX_Heat Exchange low 1 temperature | °C/°F | Read | ||
| AI | 10023 | OUXX_Heat Exchange low 2 temperature | °C/°F | Read | ||
| AI | 10024 | OUXX_Heat Exchange low 3 temperature | °C/°F | Read | ||
| AI | 10025 | OUXX_Heat Exchange low 4 temperature | °C/°F | Read | ||
| AI | 10026 | OUXX_Heat exchange high 1 temperature | °C/°F | Read | ||
| AI | 10027 | OUXX_Heat exchange high 2 temperature | °C/°F | Read | ||
| AI | 10028 | OUXX_Heat exchange high 3 temperature | °C/°F | Read | ||
| AI | 10029 | OUXX_Heat exchange high 4 temperature | °C/°F | Read | ||
| AI | 10030 | OUXX_Unit temperature | °C/°F | Read | ||
| AI | 10031 | OUXX_Discharge pipe 1 temperature | °C/°F | Read | ||
| AI | 10032 | OUXX_Discharge pipe 2 temperature | °C/°F | Read | ||
| AI | 10033 | OUXX_Crankcase temperature 1 | °C/°F | Read | ||
| AI | 10034 | OUXX_Crankcase temperature 2 | °C/°F | Read | ||
| AI | 10035 | OUXX_Compressor current 1 | A | Read | ||
| AI | 10036 | OUXX_Compressor current 2 | A | Read | ||
| AI | 10037 | OUXX_High pressure | MPa | Read | ||
| AI | 10038 | OUXX_Low pressure | MPa | Read | ||
| BImin | 25 | IUXX_Communication Status_S | Read | 0=No Error, 1=Error | ||
| BImin | 26 | IUXX_On/Off_S | Read | 0=Off, 1=On | ||
| BOmin | 25 | IUXX_On/Off_C | Command | 0=Off, 1=On | ||
| MI | 25 | IUXX_Operation Mode_S | Read | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | ||
| MOmin | 25 | IUXX_Operation Mode_C | Command | 1=Heat, 2=Cool, 3=Fan, 4=Dry, 5=Auto | ||
| AImin | 25 | IUXX_Temperature Setpoint_S | °C/°F | Read | ||
| AOmin | 25 | IUXX_Temperature Setpoint_C | Only when the Dual-Setpoint function is disabled | °C/°F | Command | |
| MI | 26 | IUXX_FanSpeed_S | Read | 1=Low, 2=Medium, 3=High, 4=Powerful | ||
| MOmin | 26 | IUXX_FanSpeed_C | Command | 1=Low, 2=Medium, 3=High, 4=Powerful | ||
| BI | 27 | IUXX_Remote Lock_S | Read | 0=Unlock, 1=Lock | ||
| BO | 26 | IUXX_Remote Lock_C | Command | 0=Unlock, 1=Lock | ||
| MI | 27 | IUXX_Louver / Vane Position_S | Read | 1=Swing, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4 | ||
| MO | 27 | IUXX_Louver / Vane Position_C | Command | 1=Swing, 2=Pos1, 3=Pos2, 4=Pos3, 5=Pos4 | ||
| AImin | 26 | IUXX_Room Temperature_S | °C/°F | Read | ||
| BI | 28 | IUXX_Filter Sign_S | Read | 0=Off, 1=On | ||
| AImin | 27 | IUXX_Unit Error code_S | 0 = no error, 1-255 = error code | Read | ||
| BI | 29 | IUXX_Compressor_S | Read | 0=Off, 1=On | ||
| BO | 27 | IUXX_Filter Sign Reset_C | Command | 0=No reset, 1=Reset | ||
| BO | 28 | IUXX_RC Error Reset_C | Command | 0=No reset, 1=Reset | ||
| BI | 30 | IUXX_Thermo On/Off_S | Read | 0=Off, 1=On | ||
| AI | 28 | IUXX_Expansion valve opening pulse_S | Expansion valve opening, 0-999 pulses | Read | ||
| AI | 29 | IUXX_Decision frequency_S | Hz | Read | ||
| AI | 30 | IUXX_Demand frequency_S | Hz | Read | ||
| AI | 31 | IUXX_Heat Exchange low 1 temperature_S | °C/°F | Read | ||
| AI | 32 | IUXX_Heat Exchange low 2 temperature_S | °C/°F | Read | ||
| AI | 33 | IUXX_Heat Exchange low 3 temperature_S | °C/°F | Read | ||
| AI | 34 | IUXX_Consumption Yesterday_S | Wh/kWh | Read | ||
| AI | 35 | IUXX_Consumption Today_S | Wh/kWh | Read | ||
| AI | 36 | IUXX_Consumption Total_S | Wh/kWh | Read | ||
| AI | 37 | IUXX_Consumption Yesterday Heat_S | Wh/kWh | Read | ||
| AI | 38 | IUXX_Consumption Today Heat_S | Wh/kWh | Read | ||
| AI | 39 | IUXX_Consumption Total Heat_S | Wh/kWh | Read | ||
| AI | 40 | IUXX_Consumption Yesterday Cool_S | Wh/kWh | Read | ||
| AI | 41 | IUXX_Consumption Today Cool_S | Wh/kWh | Read | ||
| AI | 42 | IUXX_Consumption Today Cool_S | Printed with the same name as AI 41 (offset 17) | Wh/kWh | Read | |
| AO | 26 | IUXX_Dualsetpoint Cool Temperature_C | Only when the Dual-Setpoint function is enabled | °C/°F | Command | |
| AO | 27 | IUXX_Dualsetpoint Heat Temperature_C | Only when the Dual-Setpoint function is enabled | °C/°F | Command | |
| AO | 28 | IUXX_Dualsetpoint Auto Temperature_C | Only when the Dual-Setpoint function is enabled | °C/°F | Command |
No points match these filters.
Object ID lookup: Intesis IN776MHI***O000 point IDs by name
BI15000Gateway Communication StatusBO15000On/Off (all units)MO15000Mode (all units)AO15000Temperature Setpoint (all units)MO15001FanSpeed (all units)BO15001Remote LockAO15001Dualsetpoint Cool Temperature (all units)AO15002Dualsetpoint Heat Temperature (all units)AO15003Dualsetpoint Auto Temperature (all units)AI10020OUXX_Compressor 1 FrequencyAI10021OUXX_Compressor 2 FrequencyAI10022OUXX_Heat Exchange low 1 temperatureAI10023OUXX_Heat Exchange low 2 temperatureAI10024OUXX_Heat Exchange low 3 temperatureAI10025OUXX_Heat Exchange low 4 temperatureAI10026OUXX_Heat exchange high 1 temperatureAI10027OUXX_Heat exchange high 2 temperatureAI10028OUXX_Heat exchange high 3 temperatureAI10029OUXX_Heat exchange high 4 temperatureAI10030OUXX_Unit temperatureAI10031OUXX_Discharge pipe 1 temperatureAI10032OUXX_Discharge pipe 2 temperatureAI10033OUXX_Crankcase temperature 1AI10034OUXX_Crankcase temperature 2AI10035OUXX_Compressor current 1AI10036OUXX_Compressor current 2AI10037OUXX_High pressureAI10038OUXX_Low pressureBI25IUXX_Communication Status_SBI26IUXX_On/Off_SBO25IUXX_On/Off_CMI25IUXX_Operation Mode_SMO25IUXX_Operation Mode_CAI25IUXX_Temperature Setpoint_SAO25IUXX_Temperature Setpoint_CMI26IUXX_FanSpeed_SMO26IUXX_FanSpeed_CBI27IUXX_Remote Lock_SBO26IUXX_Remote Lock_CMI27IUXX_Louver / Vane Position_SMO27IUXX_Louver / Vane Position_CAI26IUXX_Room Temperature_SBI28IUXX_Filter Sign_SAI27IUXX_Unit Error code_SBI29IUXX_Compressor_SBO27IUXX_Filter Sign Reset_CBO28IUXX_RC Error Reset_CBI30IUXX_Thermo On/Off_SAI28IUXX_Expansion valve opening pulse_SAI29IUXX_Decision frequency_SAI30IUXX_Demand frequency_SAI31IUXX_Heat Exchange low 1 temperature_SAI32IUXX_Heat Exchange low 2 temperature_SAI33IUXX_Heat Exchange low 3 temperature_SAI34IUXX_Consumption Yesterday_SAI35IUXX_Consumption Today_SAI36IUXX_Consumption Total_SAI37IUXX_Consumption Yesterday Heat_SAI38IUXX_Consumption Today Heat_SAI39IUXX_Consumption Total Heat_SAI40IUXX_Consumption Yesterday Cool_SAI41IUXX_Consumption Today Cool_SAI42IUXX_Consumption Today Cool_SAO26IUXX_Dualsetpoint Cool Temperature_CAO27IUXX_Dualsetpoint Heat Temperature_CAO28IUXX_Dualsetpoint Auto Temperature_C
Integration notes
- Points are listed for the global objects (15000 + n), outdoor unit 1 (OU block = (OU x 20) + 10000, OU 1-12) and indoor unit 1 (IU block = IU x 25, IU 1-128). Names keep the printed XX placeholder; footnote digits after names are removed.
- The manual has no access column: _C and the all-units command objects are taken as commandable, _S objects as read-only.
- With the Dual-Setpoint function enabled, the single setpoint commands are replaced by the three Dualsetpoint objects; the Temperature Setpoint_S then reports accordingly.
- AI offsets 16 and 17 are both printed as "IUXX_Consumption Today Cool_S" (the other consumption groups end with a Total object); both are listed as printed.
- The filename of the manual says in776air although the title is IN776MHI.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)
How many BACnet points does the Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet) have?
This list has 66 BACnet objects: 37 analog inputs, 8 analog outputs, 7 binary inputs, 6 binary outputs, 3 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet) BACnet points are writable?
19 of the 66 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet) BACnet documentation?
The source is 700 Series Air Gateway - IN776MHI***O000, Mitsubishi Heavy Industries VRF systems, User Manual (section 7.3 Integration into BACnet systems), revision Version 1.2.18 (2025-12-09), published free by Intesis at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in776airxxxo000.pdf.
What are the minimum BACnet points to integrate the Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)?
Start with BO 25 IUXX_On/Off_C (Start/stop indoor unit); MO 25 IUXX_Operation Mode_C (Mode command); AO 25 IUXX_Temperature Setpoint_C (Setpoint command); MO 26 IUXX_FanSpeed_C (Fan speed command); BI 26 IUXX_On/Off_S (Run status); AI 25 IUXX_Temperature Setpoint_S (Setpoint in use); AI 26 IUXX_Room Temperature_S (Room temperature); BI 25 IUXX_Communication Status_S (Unit offline alarm); AI 27 IUXX_Unit Error code_S (Fault code (0 = no error)); BI 15000 Gateway Communication Status (Gateway communication error).
How do I enable BMS control of the Intesis IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)?
No enable point is documented; remote controllers can be locked per unit with IUXX_Remote Lock_C or globally with Remote Lock.
How do I check these points on the real IN776MHI***O000 (700 Series Air gateway, Mitsubishi Heavy Industries VRF to BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Intesis BACnet points lists
- Air-to-water heat pump BACnet gateway
Intesis IN485DAI001A000 (Daikin Altherma 3 gateway, BACnet MS/TP)
Daikin Altherma 3 air-to-water heat pumps, connected on the P1/P2 user-interface bus.
Also known as: IN485DAI001A000, Daikin Altherma 3 BACnet, Altherma BACnet MS/TP, Daikin air-to-water heat pump BACnet, Daikin P1P2 BACnet gateway, Intesis Altherma - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485DAI001I000 (Daikin residential gateway, BACnet MS/TP)
Daikin residential split indoor units with an S21 connector.
Also known as: IN485DAI001I000, Daikin BACnet MS/TP gateway, Daikin split BACnet, Daikin S21 BACnet, Intesis Daikin MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485DAI001R000 (Daikin Sky and VRV gateway, BACnet MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485DAI001R000, INBACDAI001R100 (legacy code), INMBSDAI001R000, Daikin VRV BACnet MS/TP, Daikin Sky BACnet gateway, Daikin P1P2 BACnet, Intesis Daikin VRV MS/TP - Air conditioner BACnet gateway (1 indoor unit)
Intesis IN485FGL001I000 (Fujitsu gateway)
Fujitsu residential and VRF indoor units, connected with the supplied AC cable.
Also known as: Fujitsu BACnet gateway, Fujitsu VRF BACnet, Fujitsu Airstage BACnet, Fujitsu BACnet MS/TP, Fujitsu BACnet points list, Intesis Fujitsu - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485HIT001R000 (Hitachi commercial and VRF gateway, BACnet MS/TP)
Hitachi commercial and VRF indoor units on the AB wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485HIT001R000, INMBSHIT001R000 (legacy code), Hitachi BACnet MS/TP gateway, Hitachi VRF BACnet, Hitachi Set Free BACnet, Intesis Hitachi MS/TP - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis IN485MHI001R000 (Mitsubishi Heavy Industries gateway, BACnet MS/TP)
Mitsubishi Heavy Industries residential and VRF indoor units on the X-Y wired remote-controller bus (one unit or a group that acts as one).
Also known as: IN485MHI001R000, INBACMHI001R100 (legacy code), MHI BACnet MS/TP gateway, Mitsubishi Heavy BACnet, MHI VRF BACnet, Intesis MHI MS/TP - Air-to-water heat pump BACnet gateway
Intesis IN485MIT001A000 (Mitsubishi Electric Ecodan gateway, BACnet MS/TP)
Mitsubishi Electric Ecodan air-to-water units, connected to the CN105 socket of the Ecodan controller board.
Also known as: IN485MIT001A000, Mitsubishi Ecodan BACnet, Ecodan BACnet MS/TP, Mitsubishi air-to-water heat pump BACnet, Ecodan CN105 BACnet, Intesis Ecodan - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485MIT001I000 (Mitsubishi Electric gateway, BACnet MS/TP)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (or CN92) connector.
Also known as: IN485MIT001I000, Mitsubishi Electric BACnet MS/TP gateway, Mr. Slim BACnet, City Multi BACnet gateway, Mitsubishi CN105 BACnet, Intesis Mitsubishi MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485PAN001I000 (Panasonic Etherea/RAC gateway, BACnet MS/TP)
Panasonic Etherea and other residential (RAC) split indoor units with a CN-CNT connector.
Also known as: IN485PAN001I000, Panasonic Etherea BACnet, Panasonic RAC BACnet MS/TP, Panasonic CN-CNT BACnet, Panasonic split BACnet gateway, Intesis Panasonic MS/TP - Split air conditioner BACnet gateway (1 indoor unit)
Intesis IN485SAM001R000 (Samsung NASA gateway, BACnet MS/TP)
Samsung NASA-protocol indoor units, connected on the F3/F4 remote-controller bus (one unit or a group acting as one).
Also known as: IN485SAM001R000, Samsung NASA BACnet gateway, Samsung F3/F4 BACnet, Samsung BACnet MS/TP, Samsung WindFree BACnet, Intesis Samsung MS/TP - VRF BACnet gateway (multiple indoor units, H-Link)
Intesis IN770AIR***O000 for Hitachi and Hisense VRF (700 Series Air Gateway)
Hitachi and Hisense VRF systems on the H-Link (TB2) bus.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Hitachi, IN770 Hisense, Hitachi H-Link BACnet gateway, Hisense VRF BACnet gateway, Intesis 700 Series Hitachi - VRF BACnet gateway (multiple indoor units, Midea)
Intesis IN770AIR***O000 for Midea commercial and VRF (700 Series Air Gateway)
Midea commercial and VRF air conditioning systems.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Midea, Midea VRF BACnet gateway, Midea commercial BACnet IP, Intesis 700 Series Midea - VRF BACnet gateway (City Multi groups via centralized controller)
Intesis IN770AIR***O000 for Mitsubishi Electric City Multi (700 Series Air Gateway)
Mitsubishi Electric City Multi systems reached through one or two centralized controllers, up to 50 groups each.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Mitsubishi Electric, City Multi BACnet gateway, Mitsubishi AE-200 BACnet gateway, Intesis 700 Series City Multi - VRF BACnet gateway (multiple indoor units, P-Link/S-Link)
Intesis IN770AIR***O000 for Panasonic P-Link/S-Link (700 Series Air Gateway)
Panasonic VRF, PAC and GHP systems with a U1U2 P-Link/S-Link connection.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Panasonic, Panasonic U1U2 BACnet gateway, Panasonic P-Link BACnet, Panasonic ECOi BACnet, Intesis 700 Series Panasonic - VRF BACnet gateway (up to 64 indoor units, Samsung NASA)
Intesis IN770AIR***O000 for Samsung NASA VRF (700 Series Air Gateway)
Samsung NASA VRF systems: indoor units, AHU, ERV, hot-water and chiller units, up to 64 per gateway.
Also known as: IN770AIRXXSO000, IN770AIR00SO000, IN770AIR00MO000, IN770 Samsung, Samsung NASA BACnet gateway, Samsung DVM BACnet, Intesis 700 Series Samsung - VRF BACnet gateway (Fujitsu, multi-unit)
Intesis IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)
Fujitsu VRF systems (outdoor units 0-11, indoor units 1-64) integrated through the Intesis 700 Series Air gateway IN775FGL***O000.
Also known as: IN775FGL, IN775FGLO000, IN775FGL***O000, 700 Series Air Fujitsu, Intesis Fujitsu VRF BACnet gateway, HMS Intesis Fujitsu VRF, Fujitsu Airstage VRF BACnet - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACDAI001I000 (Daikin domestic gateway)
Daikin residential (domestic) split indoor units with an S21 connector.
Also known as: Daikin BACnet gateway, Daikin residential BACnet, Daikin split BACnet, DK-AC-BAC-1, Daikin S21 BACnet, Intesis Daikin - VRF / split air conditioner BACnet gateway (1 indoor unit or group)
Intesis INBACDAI001R000 (Daikin Sky and VRV gateway, BACnet IP and MS/TP)
Daikin Sky Air and VRV indoor units, connected on the P1P2 wired remote-controller bus.
Also known as: INBACDAI001R000, DK-RC-BAC-1 (legacy code), Daikin VRV BACnet IP gateway, Daikin Sky Air BACnet, Daikin P1P2 BACnet IP, Intesis Daikin SKY VRV - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACHIT001R000 (Hitachi VRF gateway)
Hitachi commercial and VRF indoor units, connected through the wired remote-controller (A/B) bus.
Also known as: Hitachi BACnet gateway, Hitachi VRF BACnet, Hitachi BACnet points list, Intesis Hitachi BACnet IP MS/TP, IN485HIT001R000 - VRF BACnet gateway (up to 16 or 64 indoor units)
Intesis INBACHIT016O000 / INBACHIT064O000 (Hitachi VRF H-Link BACnet server)
Hitachi VRF systems on the H-Link (TB2) bus: up to 16 (INBACHIT016O000) or 64 (INBACHIT064O000) indoor units.
Also known as: Hitachi VRF BACnet gateway, Hitachi H-Link BACnet, Hitachi BACnet points list, HI-AC-BAC-16, HI-AC-BAC-64, INBACHIT016O000, Intesis BACnet Server Hitachi VRF - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMHI001R000 (Mitsubishi Heavy Industries gateway)
Mitsubishi Heavy Industries RAC, FD, KX6 and KXR6 (VRF) series indoor units, via the X-Y remote-controller bus.
Also known as: Mitsubishi Heavy BACnet gateway, MHI BACnet, Mitsubishi Heavy Industries BACnet points list, MH-RC-BAC-1, MHI KX6 KXR6 VRF BACnet, IN485MHI001R000 - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMID001I100 (Midea VRF gateway)
Midea commercial and VRF indoor units (V4, V6 on XYE; V8 on D1D2).
Also known as: Midea BACnet gateway, Midea VRF BACnet, Midea BACnet points list, Midea BACnet MS/TP, Intesis Midea - VRF BACnet gateway (up to 4 indoor units)
Intesis INBACMID004I000 (Midea commercial and VRF BACnet server, up to 4 units)
Midea commercial and VRF systems on the XYE bus, up to 4 indoor units.
Also known as: INBACMID004I000, MD-AC-BAC-4 (legacy code), Midea VRF BACnet gateway, Midea XYE BACnet, Midea commercial BACnet IP, Intesis Midea 4 units - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACMIT001I000 (Mitsubishi Electric gateway)
Mitsubishi Electric residential, Mr. Slim and City Multi indoor units with a CN105 (CN92 on some) connector.
Also known as: Mitsubishi Electric BACnet gateway, Mitsubishi Electric Mr. Slim BACnet, City Multi BACnet (single unit), ME-AC-BAC-1, Mitsubishi CN105 BACnet, Intesis Mitsubishi Electric - Split air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001I000 (Panasonic Etherea/RAC gateway, BACnet IP and MS/TP)
Panasonic Etherea and RAC (domestic) split indoor units with a CN-CNT connector.
Also known as: INBACPAN001I000, PA-AC-BAC-1 (legacy code), Panasonic Etherea BACnet IP, Panasonic RAC BACnet, Panasonic CN-CNT BACnet, Intesis Panasonic domestic - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACPAN001R100 (Panasonic ECOi/PACi gateway)
Panasonic ECOi (VRF) and PACi indoor units, via the R1/R2 remote-controller bus.
Also known as: Panasonic BACnet gateway, Panasonic VRF BACnet, Panasonic ECOi BACnet, Panasonic PACi BACnet, Panasonic BACnet points list, PA-RC2-BAC-1L - VRF BACnet gateway (up to 16, 64 or 128 indoor units)
Intesis INBACPAN016O000 / 064O000 / 128O000 (Panasonic VRF P-Link BACnet server)
Panasonic VRF (ECOi and similar) systems on one or two P-Link lines, up to 128 indoor units depending on model.
Also known as: Panasonic VRF BACnet gateway, Panasonic P-Link BACnet, Panasonic BACnet points list, PA-AC-BAC-16, PA-AC-BAC-64, PA-AC-BAC-128, INBACPAN016O000, INBACPAN128O000, Intesis BACnet Server Panasonic VRF - VRF BACnet gateway (up to 4, 8, 16 or 64 indoor units)
Intesis INBACSAM004O000 / 008O000 / 016O000 / 064O000 (Samsung NASA BACnet server)
Samsung air conditioners and heat pumps on the NASA R1/R2 bus, from 4 to 64 indoor units depending on model.
Also known as: Samsung BACnet gateway, Samsung NASA BACnet, Samsung DVM BACnet, Samsung BACnet points list, INBACSAM016O000, Intesis BACnet Server Samsung NASA - Air conditioner BACnet gateway (1 indoor unit)
Intesis INBACTOS001R100 (Toshiba gateway)
Toshiba Digital and VRF line indoor units, via the A/B remote-controller bus.
Also known as: Toshiba BACnet gateway, Toshiba VRF BACnet, Toshiba BACnet points list, TO-RC-BAC-1L, Toshiba VRF BACnet MS/TP - VRF BACnet IP gateway (up to 8 or 64 indoor units)
Intesis IntesisBox HI-AC-BAC-8 / HI-AC-BAC-64 (Hitachi HC-A8MB / HC-A64MB adaptor)
Hitachi air conditioning and VRF indoor units on H-Link, reached through a Hitachi HC-A8MB or HC-A64MB communication adaptor.
Also known as: HI-AC-BAC-8, IntesisBox BACnet/IP Hitachi AC, HC-A64MB BACnet, HC-A8MB BACnet, Hitachi HC-A64MB BACnet gateway - VRF BACnet IP gateway (up to 64 or 128 indoor units)
Intesis IntesisBox PA-AC-BAC-64 / PA-AC-BAC-128 (Panasonic CZ-CFUNC2 adaptor)
Panasonic commercial air conditioning indoor units reached through a Panasonic CZ-CFUNC2 communication adaptor (two links, up to 64 indoor units each).
Also known as: IntesisBox BACnet/IP Panasonic AC, CZ-CFUNC2 BACnet, Panasonic CZ-CFUNC2 BACnet gateway
Source: 700 Series Air Gateway - IN776MHI***O000, Mitsubishi Heavy Industries VRF systems, User Manual (section 7.3 Integration into BACnet systems) · rev. Version 1.2.18 (2025-12-09). Object names, instances and units are reproduced as published; descriptions are our own.