 "manufacturer": "Intesis",
 "manufacturer_slug": "intesis",
 "model": "IN775FGL***O000 (700 Series Air gateway, Fujitsu VRF to BACnet)",
 "model_slug": "in775fgl-o000-fujitsu-vrf",
 "aliases": [
  "IN775FGL",
  "IN775FGLO000",
  "IN775FGL***O000",
  "700 Series Air Fujitsu",
  "Intesis Fujitsu VRF BACnet gateway",
  "HMS Intesis Fujitsu VRF",
  "Fujitsu Airstage VRF BACnet"
 ],
 "equipment_type": "VRF BACnet gateway (Fujitsu, multi-unit)",
 "applies_to": "Fujitsu VRF systems (outdoor units 0-11, indoor units 1-64) integrated through the Intesis 700 Series Air gateway IN775FGL***O000.",
 "summary": "The IN775FGL***O000 is a multi-protocol Intesis 700 Series gateway that reads a Fujitsu VRF network and serves it as BACnet IP or BACnet MS/TP objects (the same map for both). It has gateway/batch objects, a block per outdoor unit and a block per indoor unit; instance numbers come from fixed formulas on the unit number.",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "Points are listed for the global/batch objects, outdoor unit 0 (OU block = (OU x 25) + 10000, OU 0-11) and indoor unit 1 (IU block = U x 100, U 1-64). Names keep the printed XX placeholder.",
  "The manual has no access column: _C (command) objects are taken as commandable, _S (status) objects as read-only.",
  "Batch_SetTemp_C is printed as object type \"1-Analog Input\". The manual's own type codes use 0 = Analog Input and 1 = Analog Output (every other _C setpoint is printed \"1-Analog Output\"), and it is a command, so AO 0 is used here.",
  "IUXX_FanSpeed_C/_S are printed twice with different state lists (7 speeds and 5 speeds) at the same instance; the 7-speed list is shown and the 5-speed list is in the description. Check which applies to your indoor units.",
  "Only the objects for units configured in the gateway exist; use IUXX_Exists_S to check."
 ],
 "source": {
  "title": "700 Series Air Gateway - IN775FGL***O000, Fujitsu VRF systems, User Manual (section 7.3 Integration into BACnet systems)",
  "doc_number": null,
  "revision_date": "Version 1.0.15 (2025-12-09)",
  "url": "https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user_manual_in775fglxxxo000.pdf"
 },
 "integration": {
  "summary": "Connect the gateway to the Fujitsu VRF bus, scan and configure the units in Intesis MAPS, then map each indoor unit's _C/_S objects from its block (U x 100). Use the Batch_ objects for all-unit commands.",
  "minimum_points": [
   {
    "ref": "BO 100",
    "name": "IUXX_Operation_C",
    "why": "Start/stop indoor unit"
   },
   {
    "ref": "MO 100",
    "name": "IUXX_OperationMode_C",
    "why": "Mode command"
   },
   {
    "ref": "AO 100",
    "name": "IUXX_SetTemp_C",
    "why": "Setpoint command"
   },
   {
    "ref": "MO 101",
    "name": "IUXX_FanSpeed_C",
    "why": "Fan speed command"
   },
   {
    "ref": "BI 101",
    "name": "IUXX_Operation_S",
    "why": "Run status"
   },
   {
    "ref": "AI 100",
    "name": "IUXX_SetTemp_S",
    "why": "Setpoint in use"
   },
   {
    "ref": "AI 101",
    "name": "IUXX_SpaceTemp_S",
    "why": "Room temperature"
   },
   {
    "ref": "BI 105",
    "name": "IUXX_Error_S",
    "why": "Unit alarm"
   },
   {
    "ref": "MI 105",
    "name": "IUXX_ErrorCode_S",
    "why": "Fault code (1 = no error)"
   },
   {
    "ref": "BI 1",
    "name": "Gateway_Error_S",
    "why": "Gateway fault"
   }
  ],
  "enable": "No enable point is documented; remote-controller use can be restricted with IUXX_RC_Prohibit_C.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet IP or BACnet MS/TP is selected in Intesis MAPS; the object map is the same for both.",
   "Out of the box DHCP is tried; with no DHCP server the gateway falls back to 192.168.100.246."
  ],
  "gotchas": [
   "Instances are formula-based: indoor unit n uses n x 100 + offset, outdoor unit n uses n x 25 + 10000 + offset.",
   "Batch_ commands act on all units at once."
  ]
 },
 "points": [
  {
   "type": "BO",
   "instance": 0,
   "name": "Gateway_ES_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=Not used, 1=Energy saving"
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "Gateway_ES_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Not used, 1=Energy saving"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Gateway_Error_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Abnormal"
  },
  {
   "type": "MI",
   "instance": 0,
   "name": "Gateway_ErrorCode_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=No error, 2=Hardware Comm. Error, 3=No Config Error"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Batch_Operation_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MO",
   "instance": 0,
   "name": "Batch_OperationMode_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "Batch_Fanspeed_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med_Low, 7=Med_High"
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "Batch_SetTemp_C",
   "description": "",
   "units": "°C/°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "MO",
   "instance": 2,
   "name": "Batch_RC_Prohibition_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=Disabled, 1=No disabled"
  },
  {
   "type": "MO",
   "instance": 10000,
   "name": "OUXX_CapacitySave_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "1=Not set, 2=100%, 3=90%, 4=80%, 5=70%, 6=60%, 7=50%, 8=40%"
  },
  {
   "type": "MI",
   "instance": 10000,
   "name": "OUXX_CapacitySave_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Not set, 2=100%, 3=90%, 4=80%, 5=70%, 6=60%, 7=50%, 8=40%"
  },
  {
   "type": "BO",
   "instance": 10000,
   "name": "OUXX_ForcedOff_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=Reset, 1=Set"
  },
  {
   "type": "BI",
   "instance": 10000,
   "name": "OUXX_ForcedOff_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Reset, 1=Set"
  },
  {
   "type": "MO",
   "instance": 10001,
   "name": "OUXX_LowNoiseOp_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "1=Stop, 2=Lev1_Quiet, 3=Lev1_Ability, 4=Lev2_Quiet, 5=Lev2_Ability, 6=Lev3_Quiet, 7=Lev3_Ability"
  },
  {
   "type": "MI",
   "instance": 10001,
   "name": "OUXX_LowNoiseOp_S",
   "description": "Values per the AC manual (1-16)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 10001,
   "name": "OUXX_Error_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Fault"
  },
  {
   "type": "MI",
   "instance": 10002,
   "name": "OUXX_ErrorCode_S",
   "description": "1 = no error, other values = error code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "IUXX_Exists_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Not Exist, 1=Exist"
  },
  {
   "type": "BO",
   "instance": 100,
   "name": "IUXX_Operation_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 101,
   "name": "IUXX_Operation_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MO",
   "instance": 100,
   "name": "IUXX_OperationMode_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto"
  },
  {
   "type": "MI",
   "instance": 100,
   "name": "IUXX_OperationMode_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Cool, 2=Heat, 3=Fan, 4=Dry, 5=Auto"
  },
  {
   "type": "MO",
   "instance": 101,
   "name": "IUXX_FanSpeed_C",
   "description": "Second printed state set: 1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet",
   "units": "",
   "access": "C",
   "states": "1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med_Low, 7=Med_High"
  },
  {
   "type": "MI",
   "instance": 101,
   "name": "IUXX_FanSpeed_S",
   "description": "Second printed state set: 1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet",
   "units": "",
   "access": "R",
   "states": "1=Low, 2=High, 3=Med, 4=Auto, 5=Quiet, 6=Med_Low, 7=Med_High"
  },
  {
   "type": "MO",
   "instance": 102,
   "name": "IUXX_AirFlowDirVT_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Swing"
  },
  {
   "type": "MI",
   "instance": 102,
   "name": "IUXX_AirFlowDirVT_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Swing"
  },
  {
   "type": "MO",
   "instance": 103,
   "name": "IUXX_AirFlowDirHZ_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Pos5, 6=Swing"
  },
  {
   "type": "MI",
   "instance": 103,
   "name": "IUXX_AirFlowDirHZ_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=Pos1, 2=Pos2, 3=Pos3, 4=Pos4, 5=Pos5, 6=Swing"
  },
  {
   "type": "AO",
   "instance": 100,
   "name": "IUXX_SetTemp_C",
   "description": "",
   "units": "°C/°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "IUXX_SetTemp_S",
   "description": "",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "IUXX_SpaceTemp_S",
   "description": "",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MO",
   "instance": 104,
   "name": "IUXX_RC_Prohibit_C",
   "description": "Values per the AC manual (1-65)",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 104,
   "name": "IUXX_RC_Prohibit_S",
   "description": "Values per the AC manual (1-65)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 101,
   "name": "IUXX_ThermostatOFF_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=Reset, 1=Set"
  },
  {
   "type": "BI",
   "instance": 102,
   "name": "IUXX_ThermostatOFF_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Reset, 1=Set"
  },
  {
   "type": "BO",
   "instance": 102,
   "name": "IUXX_Reset_Filter_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=No Reset, 1=Reset"
  },
  {
   "type": "BI",
   "instance": 103,
   "name": "IUXX_FilterSign_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=No Sign, 1=Sign"
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "IUXX_Emergency_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Stop"
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "IUXX_Error_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Fault"
  },
  {
   "type": "MI",
   "instance": 105,
   "name": "IUXX_ErrorCode_S",
   "description": "1 = no error, other values = error code",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 103,
   "name": "IUXX_TempLimValid_C",
   "description": "",
   "units": "",
   "access": "C",
   "states": "0=Invalid, 1=Valid"
  },
  {
   "type": "BI",
   "instance": 106,
   "name": "IUXX_TempLimValid_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "0=Invalid, 1=Valid"
  },
  {
   "type": "AO",
   "instance": 101,
   "name": "IUXX_AutoTempLoLim_C",
   "description": "",
   "units": "°C/°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "IUXX_AutoTempLoLim_S",
   "description": "",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 102,
   "name": "IUXX_AutoTempHiLim_C",
   "description": "",
   "units": "°C/°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "IUXX_AutoTempHiLim_S",
   "description": "",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 103,
   "name": "IUXX_CoolTempLoLim_C",
   "description": "",
   "units": "°C/°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "IUXX_CoolTempLoLim_S",
   "description": "",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 104,
   "name": "IUXX_CoolTempHiLim_C",
   "description": "",
   "units": "°C/°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "IUXX_CoolTempHiLim_S",
   "description": "",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 105,
   "name": "IUXX_HeatTempLoLim_C",
   "description": "",
   "units": "°C/°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "IUXX_HeatTempLoLim_S",
   "description": "",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 106,
   "name": "IUXX_HeatTempHiLim_C",
   "description": "",
   "units": "°C/°F",
   "access": "C",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "IUXX_HeatTempHiLim_S",
   "description": "",
   "units": "°C/°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "MI",
   "instance": 106,
   "name": "IUXX_Managed_Mode_S",
   "description": "",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Master, 3=Slave, 4=External"
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "IUXX_Consumption Yesterday",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "IUXX_Consumption Today",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 110,
   "name": "IUXX_Consumption Total",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "IUXX_Consumption Yesterday Heat",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "IUXX_Consumption Today Heat",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 113,
   "name": "IUXX_Consumption Total Heat",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 114,
   "name": "IUXX_Consumption Yesterday Cool",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 115,
   "name": "IUXX_Consumption Today Cool",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 116,
   "name": "IUXX_Consumption Total Cool",
   "description": "",
   "units": "Wh/kWh",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/intesis/in775fgl-o000-fujitsu-vrf",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}