- Home
- BACnet points lists
- Johnson Controls
- Verasys VAC1000 Constant Volume Controller
Rooftop / constant volume unit controller (Verasys) · BACnet points list
Johnson Controls Verasys VAC1000 Constant Volume Controller BACnet points list
Updated 12 November 2026
The VAC1000 runs a constant volume rooftop or air handler. Through the SBH it exposes 129 objects, close to the VAC3000 list but with several MV instances shifted by one and Unit Enable, Emergency Mode and System Mode added: unit status, inputs, occupancy, zone temperature and setpoints, outputs, economizer settings, FDD alarms, lockouts and fan runtime.
This page lists 129 BACnet objects for the Johnson Controls Verasys VAC1000 Constant Volume Controller — 72 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- Verasys VAC1000 Constant Volume Controller
- Equipment
- Rooftop / constant volume unit controller (Verasys)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 129 (72 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- VAC1000, Verasys VAC1000, Verasys constant volume controller
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls Verasys VAC1000 Constant Volume Controller
Integrate through the Verasys Smart Building Hub: enable BACnet routing on the SBH, and the supervisor then sees each system bus device behind the SBH's MS/TP network. Map the enable and occupancy commands, the main setpoints and the status and alarm points.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 29548 | Unit Enable | Unit enable | Write |
| MV 29550 | System Mode | System mode | Write |
| MV 29547 | Occupancy Override | Occupancy override | Write |
| AV 29522 | Temperature Setpoint | Temperature setpoint | Write |
| AV 29508 | Zone Temperature | Zone temperature | Read |
| MV 29511 | Zone Occupancy | Zone occupancy | Read |
| MV 29500 | Unit Status | Unit status | Read |
| MV 29506 | Supply Fan Status BI | Supply fan status input | Read |
| MV 29509 | Service Alarm | Service alarm | Read |
| MV 29537 | Econ Fault Active | Economizer fault active | Read |
Network setup
- Devices on the Verasys system bus are reached through the Smart Building Hub (SBH, LC-SBH200/300) BACnet routing feature; the SBH needs a wired Ethernet connection (its Wi-Fi client does not route BACnet IP).
- In SBH Settings > BACnet Settings: MS/TP device object identifier (default 1), MAC (default 117) and MS/TP network number (default 64,999); set Routing Mode to Enabled, UDP port (default 47808) and IP network number (default 1,001).
- If the SBH and the supervisor are on different IP subnets, set up BBMD entries on both (SBH Settings > BBMD).
- SBH schedules become visible to the supervisor; only Occupied/Unoccupied and On/Off schedules are supported.
Watch out for
- The SBH routes BACnet IP only over Ethernet, not Wi-Fi.
- Give every system bus device a unique device object identifier on the BACnet network.
Johnson Controls Verasys VAC1000 Constant Volume Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 29500 | Unit Status | Read | |||
| MV | 29501 | Time Zone | Write | |||
| MV | 29502 | Language | Write | |||
| MV | 29503 | Units | Write | |||
| MV | 29504 | FCB Baud Rate | Baud Rate | Write | ||
| MV | 29505 | Operating Baud Rate | Read | |||
| MVmin | 29506 | Supply Fan Status BI | Read | |||
| MV | 29507 | Purge BI | Read | |||
| MV | 29508 | Filter Status BI | Read | |||
| MVmin | 29509 | Service Alarm | Read | |||
| MV | 29510 | Low Temperature Limit Fault BI | Read | |||
| MVmin | 29511 | Zone Occupancy | Read | |||
| MV | 29512 | Occupancy Sensor BI | Read | |||
| MV | 29513 | Temporary Occupancy | N/A | Write | ||
| MV | 29514 | Supply Fan BO | Read | |||
| MV | 29515 | Cooling Stage 1 BO | Read | |||
| MV | 29516 | Cooling Stage 2 BO | Read | |||
| MV | 29517 | Cooling Stage 3 BO | Read | |||
| MV | 29518 | Cooling Stage 4 BO | Read | |||
| MV | 29519 | Heating Stage 1 BO | Read | |||
| MV | 29520 | Heating Stage 2 BO | Read | |||
| MV | 29521 | Heating Stage 3 BO | Read | |||
| MV | 29522 | Heating Stage 4 BO | Read | |||
| MV | 29523 | Compressor Stage 1 BO | Read | |||
| MV | 29524 | Compressor Stage 2 BO | Read | |||
| MV | 29525 | Reversing Valve BO | Read | |||
| MV | 29526 | Reversing Valve Polarity | Write | |||
| MV | 29527 | Hot Gas Bypass Valve BO | Read | |||
| MV | 29528 | Supp Heating Stage 1 BO | Read | |||
| MV | 29529 | Supp Heating Stage 2 BO | Read | |||
| MV | 29530 | Humidifier BO | Read | |||
| MV | 29531 | OAT Cooling Lockout Enabled | Write | |||
| MV | 29532 | OAT Heating Lockout Enabled | Write | |||
| MV | 29533 | Rotate Cooling Stage | Write | |||
| MV | 29534 | Rotate Enable | Write | |||
| MV | 29535 | Rotate Heating Stage | Write | |||
| MV | 29536 | Load Shed Active | Read | |||
| MVmin | 29537 | Econ Fault Active | Read | |||
| MV | 29538 | Air Temperature Sensor Fault | Read | |||
| MV | 29539 | Econ Operational Fault | Read | |||
| MV | 29540 | Econ Not Operational Fault | Read | |||
| MV | 29541 | Econ Excessive Outside Air | Read | |||
| MV | 29542 | Damper Modulation Fault | Read | |||
| MV | 29543 | Cooling Ineffective Alarm | Read | |||
| MV | 29544 | Heating Ineffective Alarm | Read | |||
| MV | 29545 | Fan Runtime Alarm | Read | |||
| MV | 29546 | Fan Runtime Reset | Write | |||
| MVmin | 29547 | Occupancy Override | Write | |||
| MVmin | 29548 | Unit Enable | Write | |||
| MV | 29549 | Emergency Mode | Write | |||
| MVmin | 29550 | System Mode | Write | |||
| AV | 29500 | Device Address | Address | Write | ||
| AV | 29501 | Device Object ID | Write | |||
| AV | 29502 | Mixed Air Damper Position AI | Read | |||
| AV | 29503 | Outdoor Air Temperature Sensor AI | Read | |||
| AV | 29504 | Operational Outdoor Air Temperature | Read | |||
| AV | 29505 | Supply Air Temperature AI | Read | |||
| AV | 29506 | Mixed Air Temperature AI | Read | |||
| AV | 29507 | Return Air Temperature AI | Read | |||
| AVmin | 29508 | Zone Temperature | Read | |||
| AV | 29509 | Setpoint Adjust | Read | |||
| AV | 29510 | Zone Humidity | Read | |||
| AV | 29511 | Zone Humidity AI | Read | |||
| AV | 29512 | Zone Quality | Read | |||
| AV | 29513 | Return CO2 Sensor AI | Read | |||
| AV | 29514 | Supply Fan Speed AO | Read | |||
| AV | 29515 | Mixed Air Damper AO | Read | |||
| AV | 29516 | Minimum OA Damper AO | Read | |||
| AV | 29517 | Cooling % Command | Read | |||
| AV | 29518 | Heating % Command | Read | |||
| AV | 29519 | Heat Pump % Command | Read | |||
| AV | 29520 | Humidification AO | Read | |||
| AV | 29521 | Warm/Cool Adjust Range | Write | |||
| AVmin | 29522 | Temperature Setpoint | Write | |||
| AV | 29523 | Deadband | Write | |||
| AV | 29524 | Effective Cooling Setpoint | Read | |||
| AV | 29525 | Unocc Cooling Setpoint | Write | |||
| AV | 29526 | Standby Cooling Setpoint | Write | |||
| AV | 29527 | Effective Heating Setpoint | Read | |||
| AV | 29528 | Standby Heating Setpoint | Write | |||
| AV | 29529 | Unocc Heating Setpoint | Write | |||
| AV | 29530 | Temp Occupancy Time | Write | |||
| AV | 29531 | Fan Only Speed | Write | |||
| AV | 29532 | Min Fan Speed | Write | |||
| AV | 29533 | Max Fan Speed | Write | |||
| AV | 29534 | Clg Stage 1 Speed | Write | |||
| AV | 29535 | Clg Stage 2 Speed | Write | |||
| AV | 29536 | Clg Stage 3 Speed | Write | |||
| AV | 29537 | Clg Stage 4 Speed | Write | |||
| AV | 29538 | Htg Stage 1 Speed | Write | |||
| AV | 29539 | Htg Stage 2 Speed | Write | |||
| AV | 29540 | Htg Stage 3 Speed | Write | |||
| AV | 29541 | Htg Stage 4 Speed | Write | |||
| AV | 29542 | Minimum OA Percent | Write | |||
| AV | 29543 | Economizer Switchover Setpoint | Write | |||
| AV | 29544 | Low Limit Temperature Setpoint | Write | |||
| AV | 29545 | Supply Air Low Limit Setpoint | Write | |||
| AV | 29546 | CO2 Reset A | Write | |||
| AV | 29547 | CO2 Reset B | Write | |||
| AV | 29548 | Min Pos High Setpoint | Write | |||
| AV | 29549 | Failsoft Cooling Value | Write | |||
| AV | 29550 | Failsoft Heating Value | Write | |||
| AV | 29551 | OA Cooling Lockout Setpoint | Write | |||
| AV | 29552 | OA Heating Lockout Setpoint | Write | |||
| AV | 29553 | Supply Air Setpoint Cooling Min | Write | |||
| AV | 29554 | Supply Air Setpoint Heating Max | Write | |||
| AV | 29555 | Cooling Min On Time | Write | |||
| AV | 29556 | Cooling Min Off Time | Write | |||
| AV | 29557 | Interstage On Delay Time | Write | |||
| AV | 29558 | Interstage Off Delay Time | Write | |||
| AV | 29559 | Heating Min On Time | Write | |||
| AV | 29560 | Heating Min Off Time | Write | |||
| AV | 29561 | Low OA Lockout Setpoint | Write | |||
| AV | 29562 | Compressor Min On Time | Write | |||
| AV | 29563 | Compressor Min Off Time | Write | |||
| AV | 29564 | Supp Min On Time | Write | |||
| AV | 29565 | Supp Min Off Time | Write | |||
| AV | 29566 | Humidity Setpoint | Write | |||
| AV | 29567 | Dehumidification Setpoint | Write | |||
| AV | 29568 | Load Shed Adjust | Write | |||
| AV | 29569 | Load Shed Rate Limit | Write | |||
| AV | 29570 | Damper Pos Error | Write | |||
| AV | 29571 | Damper Min Pos Fault Tolerance | Write | |||
| AV | 29572 | Econ Fault Delay | Write | |||
| AV | 29573 | Heat Cool Alarm Differential | Write | |||
| AV | 29574 | Heat Cool Alarm Delay | Write | |||
| AV | 29575 | Fan Runtime | Read | |||
| AV | 29576 | SF Alarm Delay | Write | |||
| AV | 29577 | Fan Runtime Limit | Write |
No points match these filters.
Object ID lookup: Johnson Controls Verasys VAC1000 Constant Volume Controller point IDs by name
MV29500Unit StatusMV29501Time ZoneMV29502LanguageMV29503UnitsMV29504FCB Baud RateMV29505Operating Baud RateMV29506Supply Fan Status BIMV29507Purge BIMV29508Filter Status BIMV29509Service AlarmMV29510Low Temperature Limit Fault BIMV29511Zone OccupancyMV29512Occupancy Sensor BIMV29513Temporary OccupancyMV29514Supply Fan BOMV29515Cooling Stage 1 BOMV29516Cooling Stage 2 BOMV29517Cooling Stage 3 BOMV29518Cooling Stage 4 BOMV29519Heating Stage 1 BOMV29520Heating Stage 2 BOMV29521Heating Stage 3 BOMV29522Heating Stage 4 BOMV29523Compressor Stage 1 BOMV29524Compressor Stage 2 BOMV29525Reversing Valve BOMV29526Reversing Valve PolarityMV29527Hot Gas Bypass Valve BOMV29528Supp Heating Stage 1 BOMV29529Supp Heating Stage 2 BOMV29530Humidifier BOMV29531OAT Cooling Lockout EnabledMV29532OAT Heating Lockout EnabledMV29533Rotate Cooling StageMV29534Rotate EnableMV29535Rotate Heating StageMV29536Load Shed ActiveMV29537Econ Fault ActiveMV29538Air Temperature Sensor FaultMV29539Econ Operational FaultMV29540Econ Not Operational FaultMV29541Econ Excessive Outside AirMV29542Damper Modulation FaultMV29543Cooling Ineffective AlarmMV29544Heating Ineffective AlarmMV29545Fan Runtime AlarmMV29546Fan Runtime ResetMV29547Occupancy OverrideMV29548Unit EnableMV29549Emergency ModeMV29550System ModeAV29500Device AddressAV29501Device Object IDAV29502Mixed Air Damper Position AIAV29503Outdoor Air Temperature Sensor AIAV29504Operational Outdoor Air TemperatureAV29505Supply Air Temperature AIAV29506Mixed Air Temperature AIAV29507Return Air Temperature AIAV29508Zone TemperatureAV29509Setpoint AdjustAV29510Zone HumidityAV29511Zone Humidity AIAV29512Zone QualityAV29513Return CO2 Sensor AIAV29514Supply Fan Speed AOAV29515Mixed Air Damper AOAV29516Minimum OA Damper AOAV29517Cooling % CommandAV29518Heating % CommandAV29519Heat Pump % CommandAV29520Humidification AOAV29521Warm/Cool Adjust RangeAV29522Temperature SetpointAV29523DeadbandAV29524Effective Cooling SetpointAV29525Unocc Cooling SetpointAV29526Standby Cooling SetpointAV29527Effective Heating SetpointAV29528Standby Heating SetpointAV29529Unocc Heating SetpointAV29530Temp Occupancy TimeAV29531Fan Only SpeedAV29532Min Fan SpeedAV29533Max Fan SpeedAV29534Clg Stage 1 SpeedAV29535Clg Stage 2 SpeedAV29536Clg Stage 3 SpeedAV29537Clg Stage 4 SpeedAV29538Htg Stage 1 SpeedAV29539Htg Stage 2 SpeedAV29540Htg Stage 3 SpeedAV29541Htg Stage 4 SpeedAV29542Minimum OA PercentAV29543Economizer Switchover SetpointAV29544Low Limit Temperature SetpointAV29545Supply Air Low Limit SetpointAV29546CO2 Reset AAV29547CO2 Reset BAV29548Min Pos High SetpointAV29549Failsoft Cooling ValueAV29550Failsoft Heating ValueAV29551OA Cooling Lockout SetpointAV29552OA Heating Lockout SetpointAV29553Supply Air Setpoint Cooling MinAV29554Supply Air Setpoint Heating MaxAV29555Cooling Min On TimeAV29556Cooling Min Off TimeAV29557Interstage On Delay TimeAV29558Interstage Off Delay TimeAV29559Heating Min On TimeAV29560Heating Min Off TimeAV29561Low OA Lockout SetpointAV29562Compressor Min On TimeAV29563Compressor Min Off TimeAV29564Supp Min On TimeAV29565Supp Min Off TimeAV29566Humidity SetpointAV29567Dehumidification SetpointAV29568Load Shed AdjustAV29569Load Shed Rate LimitAV29570Damper Pos ErrorAV29571Damper Min Pos Fault ToleranceAV29572Econ Fault DelayAV29573Heat Cool Alarm DifferentialAV29574Heat Cool Alarm DelayAV29575Fan RuntimeAV29576SF Alarm DelayAV29577Fan Runtime Limit
Integration notes
- Object names are the short Verasys names as printed. The guide gives no units or state texts; multistate state texts come from the device.
- Access is from the Writable column (TRUE = writable).
- Differs from the VAC3000 table: MV 29525-29547 are shifted by one instance and MV 29548-29550 (Unit Enable, Emergency Mode, System Mode) are added.
- Source: LIT-12013287 Table 10 'BACnet attributes' (129 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Verasys VAC1000 Constant Volume Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls Verasys VAC1000 Constant Volume Controller
How many BACnet points does the Johnson Controls Verasys VAC1000 Constant Volume Controller have?
This list has 129 BACnet objects: 78 analog values, 51 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls Verasys VAC1000 Constant Volume Controller BACnet points are writable?
72 of the 129 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls Verasys VAC1000 Constant Volume Controller BACnet documentation?
The source is Verasys BACnet over IP Integration User Guide (LIT-12013287), revision 2024-03-11, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/maps/bQUUXbLn_sJI5F5XzKax0Q/attachments/ETDjFYqCzPvla4mPr0wdlw-bQUUXbLn_sJI5F5XzKax0Q/content.
What are the minimum BACnet points to integrate the Johnson Controls Verasys VAC1000 Constant Volume Controller?
Start with MV 29548 Unit Enable (Unit enable); MV 29550 System Mode (System mode); MV 29547 Occupancy Override (Occupancy override); AV 29522 Temperature Setpoint (Temperature setpoint); AV 29508 Zone Temperature (Zone temperature); MV 29511 Zone Occupancy (Zone occupancy); MV 29500 Unit Status (Unit status); MV 29506 Supply Fan Status BI (Supply fan status input); MV 29509 Service Alarm (Service alarm); MV 29537 Econ Fault Active (Economizer fault active).
How do I check these points on the real Verasys VAC1000 Constant Volume Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Refrigerated display case controller
Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)
PENN / Johnson Controls MR5 Series (MR534) panel-mount controllers for refrigerated display cases, with the ADPT-MR5-RS485 adapter for BACnet MS/TP or Verasys.
Also known as: MR5, MR534, MR534AFDV, MR534AFDN, PENN MR5, ADPT-MR5-RS485, LIT-12013019, JCI refrigeration case controller - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Room pressure controller (isolation room)
Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-1655 room pressure controllers for isolation rooms, labs and cleanrooms, with optional anteroom and flow inputs.
Also known as: FMS-1655, FMS1655, Triatek FMS-1655, Triatek room pressure controller, JCI room pressure controller, LIT-12013120 - Room pressure controller (critical environment)
Johnson Controls Triatek FMS-2000C Critical Environment Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000C critical environment controllers for isolation rooms, labs and cleanrooms (successor of the FMS-1655).
Also known as: FMS-2000C, FMS2000C, FMS-2000, Triatek FMS-2000C, LIT-12013504, JCI critical environment controller - Room pressure monitor (critical environment)
Johnson Controls Triatek FMS-2000M Critical Environment Monitor (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000M critical environment monitors with one to four differential pressure sensors (models FMS2M-Bx1x to Bx4x).
Also known as: FMS-2000M, FMS2000M, Triatek FMS-2000M, FMS2M, FMS2M-Bx1x, FMS2M-Bx2x, FMS2M-Bx3x, FMS2M-Bx4x, LIT-12013580 - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Bypass damper controller (Verasys zoning)
Johnson Controls Verasys BYP200 Bypass Controller
Verasys BYP200 bypass damper controllers that hold duct static pressure in a zoning system.
Also known as: BYP200, Verasys bypass controller - General purpose I/O controller (Verasys)
Johnson Controls Verasys generic IO controller
Verasys generic IO controllers with digital and analog inputs, outputs, NetSensors and energy meters on the system bus.
Also known as: Verasys generic IO, Verasys IO controller, Verasys GIO - Rooftop unit controller (Smart Equipment)
Johnson Controls Verasys SSE system bus (Smart Equipment rooftop board)
Rooftop units with the Simplicity SE / Smart Equipment (SSE) control board connected to a Verasys system bus.
Also known as: SSE, Simplicity SE, Verasys SSE - Lighting controller (Verasys)
Johnson Controls Verasys VAC1001 Lighting Controller
Verasys VAC1001 lighting controllers with up to 9 lighting circuits grouped into zones.
Also known as: VAC1001, Verasys lighting controller - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC3000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC3000 Constant Volume Controller.
Also known as: VAC3000, Verasys VAC3000, Verasys constant volume controller, Verasys CV controller - VAV / zone damper controller (Verasys)
Johnson Controls Verasys Zone Equipment Controller (ZEC)
Verasys Zone Equipment Controllers serving zone dampers and VAV boxes in a Verasys zoning system.
Also known as: ZEC, Verasys ZEC, Zone Equipment Controller - Rooftop unit controller (Verasys zoning)
Johnson Controls Verasys Zoning RTU (rooftop unit on the Verasys system bus)
Rooftop units integrated as the air source of a Verasys zoning system.
Also known as: Verasys Zoning RTU, Verasys RTU, Verasys zoning rooftop - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771 - Zoning system coordinator
Johnson Controls VZC100 Verasys Zone Coordinator
Verasys VZC100 zone coordinators that run a zoned rooftop system (zone voting, duct pressure and discharge air resets).
Also known as: VZC100, Verasys Zone Coordinator
Source: Verasys BACnet over IP Integration User Guide · LIT-12013287 · rev. 2024-03-11. Object names, instances and units are reproduced as published; descriptions are our own.