- TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Rooftop unit controller (room thermostat, conventional or heat-pump RTUs) · BACnet points list
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP) BACnet points list
Updated 28 October 2026
The TEC3630 and TEC3631 are field-selectable BACnet MS/TP or N2 networked thermostats for single- or two-stage rooftop units and heat pumps with an optional economizer. The point table covers modes, occupied/unoccupied/standby setpoints, network overrides for outdoor air and zone humidity, stage and fan outputs, the economizer command and loop tuning, plus the internal schedule. The TEC3631 has an onboard occupancy sensor.
This page lists 101 BACnet objects for the Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP) — 73 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
- Equipment
- Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 101 (73 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1
- Also known as
- TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat
BMS integration notes: Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Put the TEC on the MS/TP trunk with a unique address and instance, set OCC-CONFIG to External and command NET-OCC from the BAS. Write the occupied setpoints, control mode and fan mode, and read the operational zone temperature, unit status, stage outputs and the critical event MV.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 29501 | Unit Enable (UNITEN-MODE) | Shutdown or enable the unit | Write |
| MV 29500 | Control Mode (SYSTEM-MODE) | Auto, cooling or heating | Write |
| MV 29519 | Supervisory Occupancy (NET-OCC) | BAS occupancy: occupied, unoccupied, standby | Write |
| MV 29520 | Occupancy Configuration Source (OCC-CONFIG) | Must be External for NET-OCC to take effect | Write |
| MV 29524 | Fan Mode (FAN-MODE) | Fan mode: on, auto or smart | Write |
| AV 29502 | Occupied Cooling Setpoint (CLGOCC-SP) | Occupied cooling setpoint, °F | Write |
| AV 29503 | Occupied Heating Setpoint (HTGOCC-SP) | Occupied heating setpoint, °F | Write |
| MV 29700 | Unit Status (UNIT-S) | Detailed unit status | Read |
| AV 29701 | Operational Space Temperature (EFF-ZNT) | Zone temperature used for control | Read |
| MV 30000 | MV Critical Active Event | Active critical faults | Read |
Enable & remote start
Set Occupancy Configuration Source (OCC-CONFIG, MV 29520) to External, then command Supervisor Occupancy (NET-OCC, MV 29519) occupied, unoccupied or standby. With OCC-CONFIG = Schedule the internal schedule writes LOCAL-OCC instead. Unit Enable (MV 29501) shuts the unit down or enables it, and Control Mode (MV 29500) picks auto, cooling or heating. A manual override at the display, an occupancy input or the motion sensor can still change the effective occupancy.
Sensors & values from the BMS
The BAS can supply outdoor air temperature (NET-OAT, AV 29513), outdoor air humidity (NET-OAH, AV 29514), zone humidity (NET-ZNH, AV 29516) and supply air temperature (NET-SAT, AV 29515). The guide gives no timeout for these values.
Network setup
- Out of the box the thermostat runs BACnet MS/TP; N2 is chosen with FC Comm Mode in the Network Setup menu (the unit reboots).
- BACnet Instance ID: 1 to 4,194,302, default 1. MS/TP address: 4 to 127, default 4.
- MS/TP baud rate default is Auto; fixed choices are 1200, 9600, 19200, 38400 and 76800.
- Character encoding defaults to ISO 10646 (UCS-2) for Metasys; a third-party BAS may need a different setting.
Watch out for
- The guide says AV and MV objects are written without a priority (Metasys Change Default); the last such write received is the one executed.
- The passcode cannot be changed from the BAS, only at the display or through the Mobile Access Portal.
- LOCK-LVL (MV 29531) can hide the menu or most display functions; State 0 gives full access.
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 29700 | Unit Status (UNIT-S) | Detailed unit status | Read | 1=System Fault, 2=Airflow Fault, 3=Open Window, 4=Control Off, 5=Unreliable Temperature, 6=Dehumidification, 7=Idle, 8=Cooling, 9=Heating, 10=Cooling Unavailable, 11=Heating Unavailable, 12=Cooling Unavailable due to Changeover, 13=Cooling Unavailable due to OA Temp, 14=Cooling Unavailable due to Control Mode, 15=Heating Unavailable due to Changeover, 16=Heating Unavailable due to OA Temp, 17=Heating Unavailable due to Control Mode, 18=Load Shed Active | |
| AVmin | 29701 | Operational Space Temperature (EFF-ZNT) | Zone temperature used for control | Read | ||
| AV | 29704 | Eff Outdoor Air Temperature (EFF-OAT) | Outdoor air temperature used for control | Read | ||
| AV | 29705 | Active Setpoint (EFF-SETPOINT) | Active setpoint | Read | ||
| AV | 29706 | CV Operating Cooling Setpoint (EFFCLG-SP) | Active cooling setpoint | Read | ||
| AV | 29707 | CV Operating Heating Setpoint (EFFHTG-SP) | Active heating setpoint | Read | ||
| MV | 29708 | Occupancy Status (EFF-OCC) | Effective occupancy status | Read | 1=Occupied, 2=Temp Occupancy, 3=Unoccupied, 4=Standby, 5=Occupied-Override, 6=Unoccupied-Override | |
| MV | 29709 | Occupancy Input Source (OCCSOURCE-S) | What set the current occupancy | Read | 1=Occupancy B1, 2=Temp Occ B1, 3=Temp Occ, 4=Occ Override, 5=Local Schedule, 6=BAS Schedule, 7=Occupancy Sensor | |
| AV | 86905 | Econ Command (OAD-O) | Economizer damper output | Write | ||
| AV | 29714 | Cool Cmd (CLGPID-%) | Cooling/dehumidification loop output | % | Read | |
| BO | 86911 | Cool Stage 1 (Y1-C) | Cooling stage 1 output | Write | Inactive/Active | |
| BO | 86910 | Cool Stage 2 (Y2-C) | Cooling stage 2 output | Write | Inactive/Active | |
| AV | 29717 | Heat Cmd (HTGPID-%) | Heating loop output | % | Read | |
| BO | 86912 | Heat Stg 1 (W1OB-C) | Heating stage 1 output (or O/B valve) | Write | Inactive/Active | |
| BO | 86908 | Heat Stg 2 (W2SUP-C) | Heating stage 2 output | Write | Inactive/Active | |
| MV | 29518 | Manual Occupancy Override (OCCOVRD-MODE) | Manual occupancy override from the display | Write | 1=No Override, 2=Occupied, 3=Unoccupied | |
| MVmin | 29519 | Supervisory Occupancy (NET-OCC) | Occupancy command from the BAS (OCC-CONFIG = External) | Write | 1=Occupied, 2=Unoccupied, 3=Standby, 4=Not Set | |
| MVmin | 29520 | Occupancy Configuration Source (OCC-CONFIG) | Occupancy source: internal schedule or external (BAS) | Write | 1=Schedule, 2=External | |
| AV | 29522 | Passcode (PASSCODE) | Display passcode (cannot be changed from the BAS) | Read | ||
| MVmin | 29524 | Fan Mode (FAN-MODE) | Fan mode (single- or variable-speed fan) | Write | 1=On, 2=Auto, 3=Smart | |
| MV | 29525 | Fan Override (FANOVRD-MODE) | Fan override from the display | Write | 1=On, 2=Auto, 3=Quiet | |
| MV | 29527 | Aux Mode (AUX-MODE) | Auxiliary output function | Write | 1=Not Used, 2=Occupied NO, 3=Occupied NC, 4=Occupied Fan NO, 5=Occupied Fan NC, 6=On, 7=Off | |
| MV | 29528 | Temperature Units (TEMP-UNITS) | Display units: IP or SI | Write | 1=IP, 2=SI | |
| AV | 29529 | Max Setpoint Offset (MAXSP-OFFSET) | Largest warmer/cooler offset allowed | °F | Write | |
| BI | 30827 | B1 Sensor (BI1-S) | Binary input 1 state | Read | Inactive/Active | |
| BI | 30828 | B2 Sensor (BI2-S) | Binary input 2 state | Read | Inactive/Active | |
| BO | 86909 | BO2 Command (FAN-C) | Fan output | Write | Inactive/Active | |
| MV | 29728 | Load Shed Active (LOADSHED-EN) | Load shed active | Write | 0=No, 1=Yes | |
| AV | 29725 | Load Shed Rate limit (LOADSHEDRL) | Load shed setpoint rate limit | °F | Write | |
| AV | 29726 | Load Shed Adjust (LOADSHED-ADJ) | Load shed setpoint adjustment | °F | Write | |
| MV | 29712 | Fan Speed Status (FANSPD-S) | Supply fan status | Read | 1=Off, 2=On, 3=Low, 4=Medium, 5=High | |
| MV | 6 | Local Occupancy (LOCAL-OCC) | Occupancy from the internal schedule | Read | 1=Occupied, 2=Unoccupied, 3=Standby, 4=Not Set | |
| MVmin | 29500 | Control Mode (SYSTEM-MODE) | Unit control mode: auto, cooling or heating | Write | 1=Auto, 2=Cooling, 3=Heating | |
| MVmin | 29501 | Unit Enable (UNITEN-MODE) | Unit shutdown or enable | Write | 1=Shutdown, 2=Enable | |
| AV | 29567 | Common Setpoint (COMMON-SP) | Single common setpoint (common setpoint mode) | °F | Read | |
| AVmin | 29502 | Occupied Cooling Setpoint (CLGOCC-SP) | Occupied cooling setpoint | °F | Write | |
| AVmin | 29503 | Occupied Heating Setpoint (HTGOCC-SP) | Occupied heating setpoint | °F | Write | |
| AV | 29504 | Unoccupied Cooling Setpoint (CLGUNOCC-SP) | Unoccupied cooling setpoint | °F | Write | |
| AV | 29505 | Unoccupied Heating Setpoint (HTGUNOCC-SP) | Unoccupied heating setpoint | °F | Write | |
| AV | 29506 | Standby Cooling Setpoint (CLGSTBY-SP) | Standby cooling setpoint | °F | Write | |
| AV | 29507 | Standby Heating Setpoint (HTGSTBY-SP) | Standby heating setpoint | °F | Write | |
| AV | 29508 | Setpoint Offset (WC-ADJ) | Warmer/cooler offset added to the setpoint | Write | ||
| MV | 29509 | Hold/Run (HOLDRUN-MD) | Hold or run the schedule | Write | 1=Hold, 2=Run | |
| MV | 29517 | Reset PID Tuning (TUNING-RESET) | Reset the PID auto-tuning | Write | 1=No, 2=Yes | |
| AV | 29513 | Network Override Outdoor Air Temperature (NET-OAT) | Outdoor air temperature written by the BAS | °F | Write | |
| AV | 29514 | Network Override Outdoor Air Humidity (NET-OAH) | Outdoor air humidity written by the BAS | %RH | Write | |
| AV | 29516 | Network Override Zone Humidity (NET-ZNH) | Zone humidity written by the BAS | %RH | Write | |
| AV | 29515 | Network Override Supply Air Temperature (NET-SAT) | Supply air temperature written by the BAS | °F | Write | |
| AV | 29723 | Supplemental % Command SUPHTPID-%) | Supplemental heat loop output | % | Write | |
| AV | 29713 | Economizer PID CMD (OADPID-%) | Economizer loop output | % | Write | |
| AV | 29727 | Temporary Occupancy Duration (TEMPOCC-LEN) | Temporary occupancy duration | min | Write | |
| AV | 29534 | Unoccupied Off Delay (UNOCC-OFF-DELAY) | Delay before unoccupied off | min | Write | |
| MV | 29563 | Occ Setpoint Select (OCCSP-SEL) | Setpoint adjust method: offset or min/max | Write | 0=Setpoint Offset, 1=Min and Max Setpoint | |
| MV | 29566 | Heat Cool Setpoint Mode (HTGCLGSP-MODE) | Common or individual heat/cool setpoints | Write | 0=Common Setpoint, 1=Individual Setpoint | |
| AV | 29560 | Max Heating Setpoint (MAXHTG-SP) | Highest heating setpoint allowed | Write | ||
| AV | 29559 | Min Heating Setpoint (MINHTG-SP) | Lowest heating setpoint allowed | °F | Write | |
| AV | 29562 | Max Cooling Setpoint (MAXCLG-SP) | Highest cooling setpoint allowed | °F | Write | |
| AV | 29561 | Min Cooling Setpoint (MINCLG-SP) | Lowest cooling setpoint allowed | Write | ||
| AV | 29565 | Max Setpoint (MAX-SP) | Highest common setpoint allowed | °F | Write | |
| AV | 29564 | Min Setpoint (MIN-SP) | Lowest common setpoint allowed | °F | Write | |
| BO | 86913 | Aux On/Off Command (AUX-C) | Auxiliary output | Write | Inactive/Active | |
| MV | 29533 | Temp Control Setup (TEMPCTRL-SETUP) | Temperature control tuning method | Write | 0=Automatic PID Tuning, 1=Deadband Override, 2=Manual PID Tuning, 3=On/Off Control (units without economizer damper) | |
| MV | 29558 | Temp Control Setup 2 (TEMPCTRL-SETUP2) | Tuning method (units with economizer damper) | Write | 0=Automatic PID Tuning, 1=Deadband Override, 2=Manual PID Tuning | |
| AV | 29557 | Auto Economizer Tuning (AUTO-ECON-EN) | Economizer auto-tuning enable | Write | 0=Disable, 1=Enable | |
| AV | 29556 | Deadband (DEADBAND) | Control deadband | delta °F | Write | |
| AV | 29535 | Heat Prop band (HTG-PROP-BAND) | Heating loop proportional band | delta °F | Write | |
| AV | 29536 | Heat Integral Time (HTG-INT-TIME) | Heating loop integral time | s | Write | |
| AV | 29537 | Heat Process Range (HTG-PROC-RANGE) | Heating loop process range | delta °F | Write | |
| AV | 29538 | Heat Saturation Time (HTG-SAT-TIME) | Heating loop saturation time | s | Write | |
| AV | 29539 | Heat Time Constant (HTG-TIME-CONST) | Heating loop time constant | s | Write | |
| AV | 29540 | Heat Process Dead Time (HTG-DEAD-TIME) | Heating loop process dead time | s | Write | |
| AV | 29541 | Heat Period (HTG-PERIOD) | Heating loop period | s | Write | |
| AV | 29542 | Cool Prop Band (CLG-PROP-BAND) | Cooling loop proportional band | delta °F | Write | |
| AV | 29543 | Cool Integral Time (CLG-INT-TIME) | Cooling loop integral time | s | Write | |
| AV | 29544 | Cool Process Range (CLG-PROC-RANGE) | Cooling loop process range | delta °F | Write | |
| AV | 29545 | Cool Saturation Time (CLG-SAT-TIME) | Cooling loop saturation time | s | Write | |
| AV | 29546 | Cool Time Constant (CLG-TIME-CONST) | Cooling loop time constant | s | Write | |
| AV | 29547 | Cool Process Dead Time (CLG-DEAD-TIME) | Cooling loop process dead time | s | Write | |
| AV | 29548 | Cool Period (CLG-PERIOD) | Cooling loop period | s | Write | |
| AV | 29549 | Econ Prop Band (ECON-PROP-BAND) | Economizer loop proportional band | delta °F | Write | |
| AV | 29550 | Econ Integral Time (ECON-INT-TIME) | Economizer loop integral time | s | Write | |
| AV | 29551 | Econ Process Range (ECON-PROC-RANGE) | Economizer loop process range | delta °F | Write | |
| AV | 29552 | Econ Saturation Time (ECON-SAT-TIME) | Economizer loop saturation time | s | Write | |
| AV | 29553 | Econ Time Constant (ECON-TIME-CONST) | Economizer loop time constant | s | Write | |
| AV | 29554 | Econ Process Dead Time (ECON-DEAD-TIME) | Economizer loop process dead time | s | Write | |
| AV | 29555 | Econ Period (ECON-PERIOD) | Economizer loop period | s | Write | |
| MV | 29531 | LOCK-LVL | Display user lockout level | Write | 0=State 0, 1=State 1, 2=State 2 | |
| SCH | 10133 | Schedule | Internal occupancy schedule | Write | ||
| CAL | 10019 | Calendar | Holiday calendar for the schedule | Write | ||
| MVmin | 30000 | MV Critical Active Event | Active critical faults (bit list) | Read | ||
| NC | 10 | Critical Active Event NTF | Notification class for critical active events | Read | ||
| MV | 29999 | MV Critical Inactive Event | Critical faults returned to normal | Read | ||
| NC | 11 | Critical Inactive Event NTF | Notification class for critical inactive events | Read | ||
| MV | 29998 | MV Service Priority Active Event | Active service-priority faults | Read | ||
| NC | 12 | Service Priority Active Event NTF | Notification class for service-priority events | Read | ||
| MV | 29997 | MV Service Priority Inactive Event | Service-priority faults returned to normal | Read | ||
| NC | 13 | Service Priority Inactive Event NTF | Notification class for service-priority events | Read | ||
| MV | 29996 | MV Service Active Event | Active service faults | Read | ||
| NC | 14 | Service Active Event NTF | Notification class for service events | Read | ||
| MV | 29995 | MV Service Inactive Event | Service faults returned to normal | Read | ||
| NC | 15 | Service Inactive Event NTF | Notification class for service events | Read |
No points match these filters.
Integration notes
- The guide's BACnet table has no access column; access here is inferred from the N2 point type printed in the same row (AO/BO/MO writable, AI/BI/MI read-only). The network override points and the Schedule and Calendar objects (no N2 type) are marked writable.
- Multistate state numbers are copied from the guide's enum lists.
- The six MV event objects (MV 29995-30000) and their notification classes (10-15) come from the guide's separate multi-state event table, which applies to all three TEC36xx families on BACnet MS/TP.
- Temp Control Setup (MV 29533) applies to units without an economizer damper and Temp Control Setup 2 (MV 29558) to units with one.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
How many BACnet points does the Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP) have?
This list has 101 BACnet objects: 57 analog values, 2 binary inputs, 6 binary outputs, 1 calendar, 6 notification classs, 1 schedule, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP) BACnet points are writable?
73 of the 101 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP) BACnet documentation?
The source is TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers Technical Bulletin (LIT-12011956), revision 2018-07, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/of4XABY6Cun_CHQyMfnYOw/content.
What are the minimum BACnet points to integrate the Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)?
Start with MV 29501 Unit Enable (UNITEN-MODE) (Shutdown or enable the unit); MV 29500 Control Mode (SYSTEM-MODE) (Auto, cooling or heating); MV 29519 Supervisory Occupancy (NET-OCC) (BAS occupancy: occupied, unoccupied, standby); MV 29520 Occupancy Configuration Source (OCC-CONFIG) (Must be External for NET-OCC to take effect); MV 29524 Fan Mode (FAN-MODE) (Fan mode: on, auto or smart); AV 29502 Occupied Cooling Setpoint (CLGOCC-SP) (Occupied cooling setpoint, °F); AV 29503 Occupied Heating Setpoint (HTGOCC-SP) (Occupied heating setpoint, °F); MV 29700 Unit Status (UNIT-S) (Detailed unit status); AV 29701 Operational Space Temperature (EFF-ZNT) (Zone temperature used for control); MV 30000 MV Critical Active Event (Active critical faults).
How do I enable BMS control of the Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)?
Set Occupancy Configuration Source (OCC-CONFIG, MV 29520) to External, then command Supervisor Occupancy (NET-OCC, MV 29519) occupied, unoccupied or standby. With OCC-CONFIG = Schedule the internal schedule writes LOCAL-OCC instead. Unit Enable (MV 29501) shuts the unit down or enables it, and Control Mode (MV 29500) picks auto, cooling or heating. A manual override at the display, an occupancy input or the motion sensor can still change the effective occupancy.
Can the BMS supply sensor values to the Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)?
The BAS can supply outdoor air temperature (NET-OAT, AV 29513), outdoor air humidity (NET-OAH, AV 29514), zone humidity (NET-ZNH, AV 29516) and supply air temperature (NET-SAT, AV 29515). The guide gives no timeout for these values.
How do I check these points on the real TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil
Source: TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked and Wireless Thermostat Controllers Technical Bulletin · LIT-12011956 · rev. 2018-07. Object names, instances and units are reproduced as published; descriptions are our own.