Lighting controller (Verasys) · BACnet points list

Johnson Controls Verasys VAC1001 Lighting Controller BACnet points list

Updated 12 November 2026

Short answer

The VAC1001 switches up to nine lighting circuits grouped into zones, from schedules, a light level sensor and override inputs. Through the SBH it exposes 104 objects: unit status, light level and setpoint, per-zone control mode, schedule, override and state, per-circuit command, override, zone select and polarity, and override settings.

This page lists 104 BACnet objects for the Johnson Controls Verasys VAC1001 Lighting Controller — 75 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.

Manufacturer
Johnson Controls
Model
Verasys VAC1001 Lighting Controller
Equipment
Lighting controller (Verasys)
Equipment type
Other equipment
BACnet objects
104 (75 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
VAC1001, Verasys lighting controller
Source document
Verasys BACnet over IP Integration User Guide · LIT-12013287 · rev. 2024-03-11
Download CSV 104 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.

BMS integration notes: Johnson Controls Verasys VAC1001 Lighting Controller

Integration in brief

Integrate through the Verasys Smart Building Hub: enable BACnet routing on the SBH, and the supervisor then sees each system bus device behind the SBH's MS/TP network. Map the enable and occupancy commands, the main setpoints and the status and alarm points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3066Lighting ModeLighting modeWrite
MV 3042Control ModeZone control mode (first zone)Write
MV 3044OverrideZone override (first zone)Write
MV 3084Lighting Circuit 1 CommandLighting circuit 1 commandRead
MV 3085Lighting Circuit 1 OverrideLighting circuit 1 overrideWrite
AV 3012Lighting LevelMeasured light levelRead
AV 3013SetpointLight level setpointWrite
MV 3011Lighting Status BILighting status inputRead
MV 3001Unit StatusUnit statusRead

Network setup

Watch out for

Johnson Controls Verasys VAC1001 Lighting Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

104 of 104 shown
Type
AnalogMulti-state
Access
Show
Johnson Controls Verasys VAC1001 Lighting Controller BACnet Points List
DescriptionStates
MVmin3001Unit StatusRead
MV3002Time ZoneWrite
AV3003AddressWrite
AV3004Device OIDWrite
MV3005LanguageRead
MV3006UnitsWrite
MV3007Baud RateWrite
MV3008Operating Baud RateRead
AV3009Number of Lighting CircuitsWrite
AV3010Number of ZonesWrite
MVmin3011Lighting Status BILight Level StatusRead
AVmin3012Lighting LevelLight LevelRead
AVmin3013SetpointLight Level SetpointWrite
AV3014DifferentialLight Level DifferentialWrite
MVmin3042Control ModeZone 1 Control ModeWrite
MV3043Occ ScheduleN/AWrite
MVmin3044OverrideZone 1 OverrideWrite
MV3045Control ModeZone 1 Control ModeWrite
MV3046Occ ScheduleN/AWrite
MV3047OverrideZone 1 OverrideWrite
MV3048Control ModeZone 1 Control ModeWrite
MVmin3084Lighting Circuit 1 CommandRead
MV3049Occ ScheduleN/AWrite
MVmin3085Lighting Circuit 1 OverrideWrite
MV3050OverrideZone 1 OverrideWrite
MV3086Lighting Circuit 1 Zone SelectWrite
MV3051Control ModeZone 1 Control ModeWrite
MV3087Circuit 1 Command PolarityWrite
MV3052Occ ScheduleN/AWrite
MV3088Lighting Circuit 2 CommandRead
MV3053OverrideZone 1 OverrideWrite
MV3089Lighting Circuit 2 OverrideWrite
MV3054Control ModeZone 1 Control ModeWrite
MV3090Lighting Circuit 2 Zone SelectWrite
MV3055Occ ScheduleN/AWrite
MV3091Circuit 2 Command PolarityWrite
MV3056OverrideZone 1 OverrideWrite
MV3092Lighting Circuit 3 CommandRead
MV3057Control ModeZone 1 Control ModeWrite
MV3093Lighting Circuit 3 OverrideWrite
MV3058Occ ScheduleN/AWrite
MV3094Lighting Circuit 3 Zone SelectWrite
MV3059OverrideZone 1 OverrideWrite
MV3095Circuit 3 Command PolarityWrite
MV3060Control ModeZone 1 Control ModeWrite
MV3096Lighting Circuit 4 CommandRead
MV3061Occ ScheduleN/AWrite
MV3097Lighting Circuit 4 OverrideWrite
MV3062OverrideZone 1 OverrideWrite
MV3098Lighting Circuit 4 Zone SelectWrite
MV3063Control ModeZone 1 Control ModeWrite
MV3099Circuit 4 Command PolarityWrite
MV3064Occ ScheduleN/AWrite
MV3100Lighting Circuit 5 CommandRead
MV3065OverrideZone 1 OverrideWrite
MV3101Lighting Circuit 5 OverrideWrite
MVmin3066Lighting ModeLighting Sensor ModeWrite
MV3102Lighting Circuit 5 Zone SelectWrite
MV3103Circuit 5 Command PolarityWrite
MV3104Lighting Circuit 6 CommandRead
MV3105Lighting Circuit 6 OverrideWrite
MV3106Lighting Circuit 6 Zone SelectWrite
MV3107Circuit 6 Command PolarityWrite
MV3108Lighting Circuit 7 CommandRead
MV3109Lighting Circuit 7 OverrideWrite
MV3110Lighting Circuit 7 Zone SelectWrite
MV3111Circuit 7 Command PolarityWrite
MV3076Zone StateZone 1 CommandRead
MV3112Lighting Circuit 8 CommandRead
MV3077Zone StateZone 1 CommandRead
MV3113Lighting Circuit 8 OverrideWrite
MV3078Zone StateZone 1 CommandRead
MV3114Lighting Circuit 8 Zone SelectWrite
MV3079Zone StateZone 1 CommandRead
MV3115Circuit 8 Command PolarityWrite
MV3080Zone StateZone 1 CommandRead
MV3116Lighting Circuit 9 CommandRead
MV3081Zone StateZone 1 CommandRead
MV3117Lighting Circuit 9 OverrideWrite
MV3082Zone StateZone 1 CommandRead
MV3118Lighting Circuit 9 Zone SelectWrite
MV3083Zone StateZone 1 CommandRead
MV3119Circuit 9 Command PolarityWrite
AV3015Zone 1 Override DurationWrite
MV3120Zone 1 Override is MomentaryWrite
MV3121Zone 1 Override InputRead
AV3016Zone 1 Override DurationWrite
MV3122Zone 1 Override is MomentaryWrite
MV3123Zone 1 Override InputRead
AV3017Zone 1 Override DurationWrite
MV3124Zone 1 Override is MomentaryWrite
MV3125Zone 1 Override InputRead
AV3018Zone 1 Override DurationWrite
MV3126Zone 1 Override is MomentaryWrite
MV3127Zone 1 Override InputRead
AV3019Zone 1 Override DurationWrite
MV3128Zone 1 Override is MomentaryWrite
MV3129Zone 1 Override InputRead
AV3020Zone 1 Override DurationWrite
MV3130Zone 1 Override is MomentaryWrite
MV3131Zone 1 Override InputRead
AV3021Zone 1 Override DurationWrite
MV3132Zone 1 Override is MomentaryWrite
MV3133Zone 1 Override InputRead
Object ID lookup: Johnson Controls Verasys VAC1001 Lighting Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Verasys VAC1001 Lighting Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Johnson Controls Verasys VAC1001 Lighting Controller

How many BACnet points does the Johnson Controls Verasys VAC1001 Lighting Controller have?

This list has 104 BACnet objects: 14 analog values, 90 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Johnson Controls Verasys VAC1001 Lighting Controller BACnet points are writable?

75 of the 104 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Johnson Controls Verasys VAC1001 Lighting Controller BACnet documentation?

The source is Verasys BACnet over IP Integration User Guide (LIT-12013287), revision 2024-03-11, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/maps/bQUUXbLn_sJI5F5XzKax0Q/attachments/ETDjFYqCzPvla4mPr0wdlw-bQUUXbLn_sJI5F5XzKax0Q/content.

What are the minimum BACnet points to integrate the Johnson Controls Verasys VAC1001 Lighting Controller?

Start with MV 3066 Lighting Mode (Lighting mode); MV 3042 Control Mode (Zone control mode (first zone)); MV 3044 Override (Zone override (first zone)); MV 3084 Lighting Circuit 1 Command (Lighting circuit 1 command); MV 3085 Lighting Circuit 1 Override (Lighting circuit 1 override); AV 3012 Lighting Level (Measured light level); AV 3013 Setpoint (Light level setpoint); MV 3011 Lighting Status BI (Lighting status input); MV 3001 Unit Status (Unit status).

How do I check these points on the real Verasys VAC1001 Lighting Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Johnson Controls BACnet points lists

Source: Verasys BACnet over IP Integration User Guide · LIT-12013287 · rev. 2024-03-11. Object names, instances and units are reproduced as published; descriptions are our own.