- VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
Fan-powered VAV terminal unit controller · BACnet points list
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan) BACnet points list
Updated 4 November 2026
Application 1717-8 (On/Off Series Fan) is one of the ten preloaded applications in the Johnson Controls VAV1717 controller, which has a built-in damper actuator and velocity pressure sensor and runs on BACnet MS/TP. It controls a series fan-powered VAV box with a single-speed fan. Points cover occupancy and unit enable, temperature and airflow setpoints, zone sensors, airflow in L/s, CFM and CMH, damper output, the fan command and the loop and state diagnostics.
This page lists 87 BACnet objects for the Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan) — 39 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
- Equipment
- Fan-powered VAV terminal unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 87 (39 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
Set the MS/TP address on the DIP switches, load the 1717-8 application, then enable the unit with UNITEN-MODE, drive occupancy through OCC-SCHEDULE and write the occupied setpoints. Read zone temperature, effective occupancy, airflow and damper output plus the fan command.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 77 | UNITEN-MODE | Unit enable: Shutdown or Enable | Write |
| MV 59 | OCC-SCHEDULE | Occupancy from the BAS schedule | Write |
| AV 3474 | CLGOCC-SP | Occupied cooling setpoint, °C | Write |
| AV 3475 | HTGOCC-SP | Occupied heating setpoint, °C | Write |
| MV 3290 | EFF-OCC | Occupancy in effect | Read |
| AV 278004 | ZN-T | Zone temperature, °C | Read |
| AV 3515 | SA-F | Supply airflow, L/s | Read |
| AO 2131 | DPR-O | Damper output, % | Read |
| BO 2045 | SF-C | Box fan on/off output | Read |
Enable & remote start
UNITEN-MODE (Shutdown or Enable, default Enable) turns the box on or off. Occupancy comes from OCC-SCHEDULE (Occupied, Unoccupied, Standby or Not Set) written by the supervisory schedule; OCC-OVERRIDE overrides it, and EFF-OCC shows the result. SYSTEM-MODE (default Auto) can force cool only, heat only, fan only, water flush or purge.
Sensors & values from the BMS
SA-T (writable, default 13 °C) is the supply air temperature used for automatic warmup: warmup starts when SA-T and ZN-T are reliable and SA-T exceeds ZN-T plus WCT-DIFF; otherwise the BAS can command warmup with WC-C. With ZONE SETPOINT SOURCE set to Remote, the box uses BAS ZN-SP instead of the sensor setpoint.
Network setup
- BACnet MS/TP (default) as a B-ASC; the controller can also be set to N2. Valid MS/TP addresses are 4 to 127, set on the address DIP switches before power-up.
- Select one of the ten preloaded applications for the box type; the point list and BACnet IDs depend on the application.
- Commission airflow with SA-AREA (box area) and SA-KFACTOR (pickup gain); AUTOCAL-STATE shows autocalibration.
Watch out for
- Several BACnet IDs (ZN-T and the zone sensor points among them) differ between applications, so a template from one application does not fit another.
- CLGOCC-MINFLOW, CLG-MAXFLOW, SA-AREA, SA-KFACTOR and the time settings are commissioning values; don't write them cyclically.
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1094 | DA-VP | Discharge air velocity pressure | Pa | Read | |
| AI | 277984 | ZN-CO2 | Netsensor zone CO2 | ppm | Read | |
| AI | 278062 | ZN-H | Netsensor zone humidity | %RH | Read | |
| AV | 1103 | ZN-SP-NS | Netsensor zone setpoint | °C | Read | |
| AI | 277987 | ZN-SP-TE730 | TE730 zone setpoint | °C | Read | |
| AI | 1106 | ZN-T-NS | Netsensor zone temperature | °C | Read | |
| AI | 277993 | ZN-T-TE730 | TE730 zone temperature | °C | Read | |
| BV | 1105 | ZN-TOCC-NS | Netsensor zone temporary occupancy; default Inactive | Read | Inactive, Active | |
| BI | 277990 | ZN-TOCC-TE730 | TE730 zone temporary occupancy; default Inactive | Read | Inactive, Active | |
| AOmin | 2131 | DPR-O | Supply air damper output | % | Read | |
| MV | 2086 | OCC-MODE | Occupancy status display | Read | ||
| BOmin | 2045 | SF-C | Supply fan command | Read | ||
| MV | 3341 | FAN-OUTSTATE | Fan output state | Read | Off, On, Hold | |
| MV | 3385 | SAD-OUTSTATE | Supply air damper output state | Read | Bypass, Hold, Control Flow Unreliable, Control Flow Reliable | |
| AV | 4410 | SAFLOW-ABSEFFORT | Supply airflow absolute effort | % | Read | |
| AV | 4409 | SAFLOW-ABSERROR | Supply airflow absolute error | L/s | Read | |
| AV | 4411 | SAFLOW-ERROR | Supply airflow error | L/s | Read | |
| AV | 4412 | SAFLOW-EWMA | Supply airflow exponentially weighted moving average | % | Read | |
| AV | 3384 | SAFLOW-SP | Supply airflow setpoint; default 0.0 L/s | L/s | Write | |
| AV | 5715 | SPMAXPOS | Supply air damper maximum position; default 80% | % | Write | |
| AV | 4246 | CLG-ABSEFFORT | Cooling absolute effort | % | Read | |
| AV | 4245 | CLG-ABSERROR | Cooling absolute error | °C | Read | |
| AV | 4247 | CLG-ERROR | Cooling error | °C | Read | |
| AV | 4248 | CLG-EWMA | Cooling exponentially weighted moving average | % | Read | |
| AV | 3615 | CLG-O | Cooling output | % | Read | |
| MV | 3387 | SAFLOW-OUTSTATE | Supply airflow output state | Read | Min, Max, Hold, Control, Heating, Warmup, Failsoft | |
| MV | 278061 | MIN FLOW RESET TYPE | Minimum flow reset type; default None | Write | None, CO2 | |
| AV | 3266 | CLDWN-MINFLOW | Cooldown minimum flow; default 100 L/s | L/s | Write | |
| AV | 3267 | CLG-MINFLOW | Cooling minimum flow | L/s | Read | |
| AV | 3272 | CLGUNOCC-MINFLOW | Unoccupied cooling minimum flow; default 0 L/s | L/s | Write | |
| AV | 3268 | HTG-MINFLOW | Heating minimum flow | L/s | Read | |
| AV | 3273 | HTGUNOCC-MINFLOW | Unoccupied heating minimum flow; default 100 L/s | L/s | Write | |
| AV | 3270 | MINFLOWCO2-PB | CO2 minimum flow proportional band; default 400 ppm | ppm | Write | |
| AV | 3271 | MINFLOWCO2-SP | CO2 minimum flow setpoint; default 700 ppm | ppm | Write | |
| AV | 3269 | OCC-LEVEL | Occupancy level; default 0 | Write | ||
| AV | 3274 | WU-MINFLOW | Warmup minimum flow; default 100 L/s | L/s | Write | |
| MVmin | 3290 | EFF-OCC | Effective occupancy; default Occupied | Read | Occupied, Unoccupied, Bypass, Standby | |
| AV | 3289 | OCCMODE-BYPASSTIME | Occupancy mode bypass time; default 3600 s | s | Write | |
| AV | 5871 | PRESS-REQ | Zone pressure request | Read | ||
| AV | 3386 | SAD-ST | Supply air damper stroke time; default 60 s | s | Write | |
| AVmin | 3515 | SA-F | Supply air flow | L/s | Read | |
| AV | 5869 | CLG-REQ | Zone cooling request | Read | ||
| AV | 5870 | HTG-REQ | Zone heating request | Read | ||
| MV | 3468 | WC-S | Warmup cooldown status; default Normal | Read | Normal, Warmup, Cooldown, Coast | |
| AV | 3469 | WCT-DIFF | Warmup cooldown temperature differential; default 8°C | °C | Write | |
| AVmin | 3474 | CLGOCC-SP | Occupied cooling setpoint; default 23°C | °C | Write | |
| AV | 3476 | CLGSTBY-SP | Standby cooling setpoint; default 25°C | °C | Write | |
| AV | 3478 | CLGUNOCC-SP | Unoccupied cooling setpoint; default 28°C | °C | Write | |
| AV | 3472 | EFFCLG-SP | Effective cooling setpoint | °C | Read | |
| AV | 3473 | EFFHTG-SP | Effective heating setpoint | °C | Read | |
| AVmin | 3475 | HTGOCC-SP | Occupied heating setpoint; default 21°C | °C | Write | |
| AV | 3477 | HTGSTBY-SP | Standby heating setpoint; default 19°C | °C | Write | |
| AV | 3479 | HTGUNOCC-SP | Unoccupied heating setpoint; default 16°C | °C | Write | |
| MV | 3091 | AUTOCAL-STATE | Autocalibration state | Read | Uncalibrated, Waiting to Calibrate, Waiting for Damper, Autocalibrate, Normal | |
| AV | 3108 | CLG-MAXFLOW | Cooling maximum flow; default 500 L/s | L/s | Write | |
| AV | 3109 | CLGOCC-MINFLOW | Occupied cooling minimum flow; default 100 L/s | L/s | Write | |
| AV | 3110 | HTGOCC-MINFLOW | Occupied heating minimum flow; default 100 L/s | L/s | Write | |
| AV | 3111 | SA-AREA | Supply air box area; default 0.032 m² | m² | Write | |
| AV | 3112 | SA-KFACTOR | Supply air pickup gain; default 2 | Write | ||
| MV | 3466 | ZNT-STATE | Zone temperature state; default Satisfied | Read | Satisfied, Supp Htg, Supp Htg + Box Htg, Box Htg + Supp Htg, Prmy Clg, Temperature Unreliable | |
| MV | 3343 | FAN-STATE | Fan state | Read | Off, On | |
| AV | 3342 | HTG-PURGETIME | Heating purge time; default 120 s | s | Write | |
| BV | 3391 | PFRESTART-EN | Power fail restart enable; default TRUE | Write | ||
| AV | 3392 | PFRESTART-TIME | Power fail restart time; default 60 s | s | Write | |
| MV | 3393 | UNITEN-STATE | Unit enable state | Read | Shutdown, Enable | |
| AV | 3450 | UNOCC-SATTIME | Unoccupied saturation time; default 300 s | s | Write | |
| MV | 3452 | UNOCC-STATE | Unoccupied state | Read | Satisfied, Prmy Clg, Supp Htg, Box Htg, Box Htg + Supp Htg, Temperature Unreliable, Unocc Ctrl Not Req'd | |
| MV | 3471 | WC-STATE | Warmup cooldown state | Read | Normal, Warmup Satisfied, Warmup Unreliable, Cooldown, Cooldown Unreliable, Prmy Htg, Prmy Htg + Supp Htg, Prmy Htg + Supp Htg + Box Htg, Prmy Htg + Box Htg, Prmy Htg + Box Htg + Supp Htg, Coast | |
| BV | 4 | AUTOCAL-C | Autocalibration command; default FALSE | Read | ||
| AV | 277997 | BAS-ZN-SP | BAS zone setpoint; default 25°C | °C | Write | |
| MV | 58 | OCC-OVERRIDE | Occupancy override; default Not Set | Write | Occupied, Unoccupied, Bypass, Standby, Not Set | |
| MVmin | 59 | OCC-SCHEDULE | Occupancy schedule; default Not Set | Write | Occupied, Unoccupied, Standby, Not Set | |
| AV | 75 | SA-T | Supply air temperature; default 13°C | °C | Write | |
| MV | 76 | SYSTEM-MODE | System mode; default Auto | Write | Cool Only, Heat Only, Fan Only, Water Flush, Purge, Auto | |
| BV | 769 | TUNING-RESET | PID tuning reset; default FALSE | Write | ||
| MVmin | 77 | UNITEN-MODE | Unit enable mode; default Enable | Write | Shutdown, Enable | |
| MV | 80 | WC-C | Warmup cooldown command; default Normal | Write | Normal, Warmup, Cooldown, Coast | |
| MV | 277996 | ZONE SETPOINT SOURCE | Zone setpoint source; default Local | Write | Local, Remote | |
| AV | 25270 | CLG-REQ SRC | Cooling request source | Read | ||
| AV | 278000 | EFFECTIVE-ZN-SP | Effective zone setpoint | °C | Read | |
| AV | 25269 | PRESS-REQ SRC | Zone pressure request source | Read | ||
| AV | 278002 | SA-F-CFM | Supply airflow in cubic feet per minute | CFM | Read | |
| AV | 278003 | SA-F-CMH | Supply airflow in cubic meters per hour | CMH | Read | |
| AV | 278001 | SA-F-L/S | Supply airflow in liters per second | L/s | Read | |
| AVmin | 278004 | ZN-T | Zone temperature | °C | Read | |
| AV | 278005 | ZN-T OFFSET (NS) | Zone temperature offset for Netsensor; default 0 | Δ°C | Write | |
| AV | 278006 | ZN-T OFFSET (TE730) | Zone temperature offset for TE730; default 0 | Δ°C | Write |
No points match these filters.
Object ID lookup: Johnson Controls VAV1717 App 1717-8 On/Off Series Fan point IDs by name
AI1094DA-VPAI277984ZN-CO2AI278062ZN-HAV1103ZN-SP-NSAI277987ZN-SP-TE730AI1106ZN-T-NSAI277993ZN-T-TE730BV1105ZN-TOCC-NSBI277990ZN-TOCC-TE730AO2131DPR-OMV2086OCC-MODEBO2045SF-CMV3341FAN-OUTSTATEMV3385SAD-OUTSTATEAV4410SAFLOW-ABSEFFORTAV4409SAFLOW-ABSERRORAV4411SAFLOW-ERRORAV4412SAFLOW-EWMAAV3384SAFLOW-SPAV5715SPMAXPOSAV4246CLG-ABSEFFORTAV4245CLG-ABSERRORAV4247CLG-ERRORAV4248CLG-EWMAAV3615CLG-OMV3387SAFLOW-OUTSTATEMV278061MIN FLOW RESET TYPEAV3266CLDWN-MINFLOWAV3267CLG-MINFLOWAV3272CLGUNOCC-MINFLOWAV3268HTG-MINFLOWAV3273HTGUNOCC-MINFLOWAV3270MINFLOWCO2-PBAV3271MINFLOWCO2-SPAV3269OCC-LEVELAV3274WU-MINFLOWMV3290EFF-OCCAV3289OCCMODE-BYPASSTIMEAV5871PRESS-REQAV3386SAD-STAV3515SA-FAV5869CLG-REQAV5870HTG-REQMV3468WC-SAV3469WCT-DIFFAV3474CLGOCC-SPAV3476CLGSTBY-SPAV3478CLGUNOCC-SPAV3472EFFCLG-SPAV3473EFFHTG-SPAV3475HTGOCC-SPAV3477HTGSTBY-SPAV3479HTGUNOCC-SPMV3091AUTOCAL-STATEAV3108CLG-MAXFLOWAV3109CLGOCC-MINFLOWAV3110HTGOCC-MINFLOWAV3111SA-AREAAV3112SA-KFACTORMV3466ZNT-STATEMV3343FAN-STATEAV3342HTG-PURGETIMEBV3391PFRESTART-ENAV3392PFRESTART-TIMEMV3393UNITEN-STATEAV3450UNOCC-SATTIMEMV3452UNOCC-STATEMV3471WC-STATEBV4AUTOCAL-CAV277997BAS-ZN-SPMV58OCC-OVERRIDEMV59OCC-SCHEDULEAV75SA-TMV76SYSTEM-MODEBV769TUNING-RESETMV77UNITEN-MODEMV80WC-CMV277996ZONE SETPOINT SOURCEAV25270CLG-REQ SRCAV278000EFFECTIVE-ZN-SPAV25269PRESS-REQ SRCAV278002SA-F-CFMAV278003SA-F-CMHAV278001SA-F-L/SAV278004ZN-TAV278005ZN-T OFFSET (NS)AV278006ZN-T OFFSET (TE730)
Integration notes
- Objects from Table 27 on pages 32-34 of the VAV1717 and VAV1732 Application Note (LIT-12013794). Access, units, defaults and state text come from Table 19 (All BACnet points).
- Some BACnet IDs (for example ZN-T and the zone sensor points) are specific to this application and differ in other VAV1717 applications.
- Units are metric as printed (°C, L/s, Pa); SA-F-CFM and SA-F-CMH give airflow in CFM and m³/h.
- The MAP Gateway table in the same note shows some commands (heating stage and fan commands, DPR-O, AUTOCAL-C) as writable, but the BACnet point table lists them as read-only; access here follows the BACnet table.
- Multistate state text is listed in the order printed; the table gives no state numbers.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
How many BACnet points does the Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan) have?
This list has 87 BACnet objects: 6 analog inputs, 1 analog output, 55 analog values, 1 binary input, 1 binary output, 4 binary values, 19 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan) BACnet points are writable?
39 of the 87 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan) BACnet documentation?
The source is VAV1717 and VAV1732 VAV Controllers Application Note (LIT-12013794), revision 2021-08-09, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/1A9bXr239BVM1oXYaNZBSA/content.
What are the minimum BACnet points to integrate the Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)?
Start with MV 77 UNITEN-MODE (Unit enable: Shutdown or Enable); MV 59 OCC-SCHEDULE (Occupancy from the BAS schedule); AV 3474 CLGOCC-SP (Occupied cooling setpoint, °C); AV 3475 HTGOCC-SP (Occupied heating setpoint, °C); MV 3290 EFF-OCC (Occupancy in effect); AV 278004 ZN-T (Zone temperature, °C); AV 3515 SA-F (Supply airflow, L/s); AO 2131 DPR-O (Damper output, %); BO 2045 SF-C (Box fan on/off output).
How do I enable BMS control of the Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)?
UNITEN-MODE (Shutdown or Enable, default Enable) turns the box on or off. Occupancy comes from OCC-SCHEDULE (Occupied, Unoccupied, Standby or Not Set) written by the supervisory schedule; OCC-OVERRIDE overrides it, and EFF-OCC shows the result. SYSTEM-MODE (default Auto) can force cool only, heat only, fan only, water flush or purge.
Can the BMS supply sensor values to the Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)?
SA-T (writable, default 13 °C) is the supply air temperature used for automatic warmup: warmup starts when SA-T and ZN-T are reliable and SA-T exceeds ZN-T plus WCT-DIFF; otherwise the BAS can command warmup with WC-C. With ZONE SETPOINT SOURCE set to Remote, the box uses BAS ZN-SP instead of the sensor setpoint.
How do I check these points on the real VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: VAV1717 and VAV1732 VAV Controllers Application Note · LIT-12013794 · rev. 2021-08-09. Object names, instances and units are reproduced as published; descriptions are our own.