  4. TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)

VAV zone controller (room thermostat for TEC zoning) · BACnet points list

Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The TEC2647Z-3 is the zone controller of the Johnson Controls TEC zoning system for constant volume, pressure-dependent rooftop units. It modulates the zone damper, can drive analog or on/off reheat, and sends weighted heating and cooling demand to its rooftop controller over BACnet MS/TP. A supervisory controller can monitor it, schedule each zone, or take full control, depending on Cfg Network Handle.

This page lists 51 BACnet objects for the Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.

Manufacturer
Johnson Controls
Model
TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Equipment
VAV zone controller (room thermostat for TEC zoning)
Equipment type
VAV boxes & fan coils
BACnet objects
51 (32 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
72aaa (aaa = MS/TP address)
Also known as
TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller
Source document
TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications Technical Bulletin (TEC2647Z-3, TEC2647Z-3+PIR, TEC2664Z-3) · LIT-12011682 · rev. 2011-05-13
Download CSV 51 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.

BMS integration notes: Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)

Integration in brief

Give each zone controller and rooftop controller a unique MS/TP address, add them to the supervisory controller, then choose the network handle. With Default Zone Handle the supervisor only monitors; with 2 it can schedule each zone through GUI Occupancy (MV 9); with 3 it takes full control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 9GUI OccupancyOccupancy command (needs network handle 2 or 3)Write
MV 7Cfg Network Handle1 monitor only, 2 zone occupancy, 3 full releaseWrite
AV 11GUI Occupied Heat SptOccupied heating setpoint, °FWrite
AV 12GUI Occupied Cool SptOccupied cooling setpoint, °FWrite
MV 11GUI Effective OccupancyOccupancy in effectRead
AV 21GUI Room TemperatureZone temperature, °FWrite
AI 1GUI Damper PositionZone damper position, %Read
AV 19GUI PI Heat Weighted DemandHeating demand sent to the rooftop, %Read
AV 20GUI PI Cool Weighted DemandCooling demand sent to the rooftop, %Read

Enable & remote start

Cfg Network Handle (MV 7) sets how much control the supervisory controller has: 1 = Default Zone Handle (monitor only, zones follow the rooftop schedule), 2 = Default Minus Occupancy (each zone can be scheduled through GUI Occupancy, MV 9), 3 = Full Release (the supervisor takes full control). The handle can only be written from the supervisory controller, not the zone menu.

Sensors & values from the BMS

To feed room temperature from the BMS, set GUI Room Temp Override (BV 10) to Override and write GUI Room Temperature (AV 21). GUI Outdoor Temperature (AV 22) is writable.

Network setup

Watch out for

Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

51 of 51 shown
Type
Multi-state
Access
Show
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1GUI Damper PositionZone damper position%Read
AV1Cfg Zone MACZone controller MS/TP addressRead
AV2Cfg RTC MACMS/TP address of the rooftop controller it followsRead
AV3Cfg AO2 OA Lock SptOutdoor temperature lockout for AO 2 reheat°FWrite
AV4Cfg BO5 OA Lock SptOutdoor temperature lockout for BO 5 reheat°FWrite
AV5Cfg Damper Min PosDamper minimum position%Write
AV6Cfg Damper Max PosDamper maximum position%Write
AV7Cfg Damper Max Heat PosDamper maximum position in heating%Write
AV8Cfg Heating Spt LimitHighest heating setpoint allowed°FWrite
AV9Cfg Cooling Spt LimitLowest cooling setpoint allowed°FWrite
AV10Cfg DeadbandMinimum heat/cool setpoint deadband°FWrite
AVmin11GUI Occupied Heat SptOccupied heating setpoint°FWrite
AVmin12GUI Occupied Cool SptOccupied cooling setpoint°FWrite
AV13GUI Unoccupied Heat SptUnoccupied heating setpoint°FWrite
AV14GUI Unoccupied Cool SptUnoccupied cooling setpoint°FWrite
AV15GUI Standby Heat SptStandby heating setpoint°FWrite
AV16GUI Standby Cool SptStandby cooling setpoint°FWrite
AV17GUI AO2 StatusAO 2 reheat output%Read
AV18GUI UI3 StatusUI 3 input value°FRead
AVmin19GUI PI Heat Weighted DemandWeighted heating demand sent to the rooftop%Read
AVmin20GUI PI Cool Weighted DemandWeighted cooling demand sent to the rooftop%Read
AVmin21GUI Room TemperatureRoom temperature (writable with override)°FWrite
AV22GUI Outdoor TemperatureOutdoor temperature°FWrite
AV23Cfg Device InstanceBACnet device instanceRead
AV24GUI P1 Heat DemandZone heating loop demand%Read
AV25GUI P1 Cool DemandZone cooling loop demand%Read
BI1GUI BI1 StatusBinary input 1 statusRead0=Inactive (Contact Open), 1=Active (Contact Closed)
BI2GUI BI2 StatusBinary input 2 statusRead0=Inactive, 1=Active
BV1Cfg Temperature ScaleTemperature scaleWrite0=°C, 1=°F
BV2Cfg Menu ScrollDisplay menu scrollWrite0=No Scroll, 1=Scroll Active
BV3Cfg Motion Detector FunctionMotion detector functionWrite0=Disabled, 1=Enabled
BV4Cfg AO2 RA/DAAO 2 direct or reverse actingWrite0=Direct Acting (DA), 1=Reverse Acting (RA)
BV5Cfg BO5 Time BaseBO 5 cycle time baseWrite0=15 Minutes, 1=10 Seconds
BV6Cfg BO5 ConfigurationBO 5 normally open or closedWrite0=Normally Open (N.O.), 1=Normally Closed (N.C.)
BV7GUI BO5 StatusBO 5 reheat output statusRead0=Off, 1=On
BV8Sta AO2 Lock StatusAO 2 outdoor lockout activeRead0=Inactive, 1=Active
BV9Sta BO5 Lock StatusBO 5 outdoor lockout activeRead0=Inactive, 1=Active
BV10GUI Room Temp OverrideRoom temperature override enableWrite0=Normal, 1=Override
BV11Sta RTC Smart RecoverySmart recovery active at the rooftopWrite0=Off, 1=On
BV12Cfg Setpoint TypeSetpoint changes permanent or temporaryRead0=Permanent, 1=Temporary
MV1Cfg Zone BaudMS/TP baud rateRead1=9600, 2=19200, 3=38400, 4=76800, 5=Auto
MV2Cfg Reheat ConfigurationReheat typeWrite1=None, 2=Analog Duct Reheat Only, 3=On/Off Duct Reheat Only, 4=On/Off Peripheral Reheat Only, 5=Analog Duct Reheat and On/Off Peripheral Reheat
MV3Cfg BI1 ConfigurationBinary input 1 functionWrite1=None, 2=Motion N.O., 3=Motion N.C.
MV4Cfg PI Heat WeightWeight of this zone in heating demandWrite1=0%, 2=25%, 3=50%, 4=75%, 5=100%
MV5Cfg PI Cool WeightWeight of this zone in cooling demandWrite1=0%, 2=25%, 3=50%, 4=75%, 5=100%
MV6Cfg Temporary Occupancy TimeTemporary occupancy durationRead1=0 Hours, 2=1 Hour, 3=2 Hours, 4=3 Hours, 5=4 Hours, 6=5 Hours, 7=6 Hours, 8=7 Hours, 9=8 Hours, 10=9 Hours, 11=10 Hours, 12=11 Hours, 13=12 Hours
MVmin7Cfg Network HandleHow much control the supervisory controller takesWrite1=Default Zone Handle (Supervisory Controller Monitors the Zoning System), 2=Default Minus Occupancy (Allows Each Zone to be Scheduled Independently), 3=Full Release (Supervisory Controller Assumes Complete Control of the Zoning System)
MV8GUI Zone Keypad LockoutZone keypad lockout levelWrite1=No Lockout, 2=Level 1, 3=Level 2, 4=Level 3
MVmin9GUI OccupancyOccupancy commandWrite1=Local Occupancy, 2=Occupied, 3=Unoccupied
MV10Sta RTC Zone SequencingRooftop sequence (cool or heat) seen by the zoneWrite1=Cool, 2=Heat
MVmin11GUI Effective OccupancyEffective occupancyRead1=Occupied, 2=Unoccupied, 3=Temporary Occupied, 4=Standby
Object ID lookup: Johnson Controls TEC2647Z-3 Zone Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)

How many BACnet points does the Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP) have?

This list has 51 BACnet objects: 1 analog input, 25 analog values, 2 binary inputs, 12 binary values, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP) BACnet points are writable?

32 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP) BACnet documentation?

The source is TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications Technical Bulletin (TEC2647Z-3, TEC2647Z-3+PIR, TEC2664Z-3) (LIT-12011682), revision 2011-05-13, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/y0yBSZRkp~9t9PGRQ94OSw/content.

What are the minimum BACnet points to integrate the Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)?

Start with MV 9 GUI Occupancy (Occupancy command (needs network handle 2 or 3)); MV 7 Cfg Network Handle (1 monitor only, 2 zone occupancy, 3 full release); AV 11 GUI Occupied Heat Spt (Occupied heating setpoint, °F); AV 12 GUI Occupied Cool Spt (Occupied cooling setpoint, °F); MV 11 GUI Effective Occupancy (Occupancy in effect); AV 21 GUI Room Temperature (Zone temperature, °F); AI 1 GUI Damper Position (Zone damper position, %); AV 19 GUI PI Heat Weighted Demand (Heating demand sent to the rooftop, %); AV 20 GUI PI Cool Weighted Demand (Cooling demand sent to the rooftop, %).

How do I enable BMS control of the Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)?

Cfg Network Handle (MV 7) sets how much control the supervisory controller has: 1 = Default Zone Handle (monitor only, zones follow the rooftop schedule), 2 = Default Minus Occupancy (each zone can be scheduled through GUI Occupancy, MV 9), 3 = Full Release (the supervisor takes full control). The handle can only be written from the supervisory controller, not the zone menu.

Can the BMS supply sensor values to the Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)?

To feed room temperature from the BMS, set GUI Room Temp Override (BV 10) to Override and write GUI Room Temperature (AV 21). GUI Outdoor Temperature (AV 22) is writable.

How do I check these points on the real TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Johnson Controls BACnet points lists

Source: TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications Technical Bulletin (TEC2647Z-3, TEC2647Z-3+PIR, TEC2664Z-3) · LIT-12011682 · rev. 2011-05-13. Object names, instances and units are reproduced as published; descriptions are our own.