Rooftop unit BACnet gateway · BACnet points list

Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The Simplicity LINC is a small gateway mounted in the rooftop unit's control panel. It polls the Simplicity unit controller over Modbus RTU and exposes a fixed set of points on BACnet MS/TP; no configuration is needed. The map has 34 analog inputs, 58 analog values (setpoints, sensor values and settings), 65 binary inputs (outputs, safeties, alarms) and 40 binary values (option and mode enables, comm-value selects, redline/loadshed).

This page lists 197 BACnet objects for the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) — 98 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Johnson Controls’s documentation hosted by Distributor web store (Shopify CDN), not by Johnson Controls itself, so treat it as unofficial.

Manufacturer
Johnson Controls
Model
Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Equipment
Rooftop unit BACnet gateway
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
197 (98 writable)
Transport
BACnet MS/TP
Firmware
ConFig v1.01d
Default device instance
23001
Also known as
Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet
Source document
Simplicity LINC Gateway Application Guide (ConFig v1.01d) · 1031990-UAD-A-0313 · rev. 2013-03 (unofficial copy, hosted by Distributor web store (Shopify CDN))
Download CSV 197 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.

BMS integration notes: Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)

Integration in brief

Set the MAC address (1-99) on DIP switches A0-A7 and the baud on B0-B3 (default 38400); the device instance combines the DE modifier 230 with the MAC (default 23001). The BAS writes the occupied/unoccupied cooling and heating setpoints and can supply space temperature, outdoor temperature, humidity and IAQ values once the matching COMM_ accept BV is set. Read supply air temperature, the active alarm and the alarm buffers.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1OCC_COOL_SPOccupied cooling setpoint, 46-99 °FWrite
AV 50OCC_HEAT_SPOccupied heating setpoint, 45-98 °FWrite
BI 16AIR_PROOF_SWAir proving switch (1 = air flow)Read
AI 4SUP_AIR_TEMPSupply air temperatureRead
AV 6SPACE_TEMPSpace temperature (BAS can write it)Write
AI 15ACTIVE_ALARMActive alarmRead
BI 11MODBUS_ALARMGateway lost Modbus link to the unitRead

Sensors & values from the BMS

AV 6 SPACE_TEMP, AV 7 AMB_TEMP, AV 10 AMB_AIR_HUM, AV 12 RET_AIR_HUM and AV 8 IAQ_VALUE are writable; set BV 108 COMM_ST, BV 101 COMM_OAT, BV 100 COMM_OH, BV 99 COMM_RH or BV 109 COMM_IAQ so the controller accepts the BAS value.

Network setup

Watch out for

Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

197 of 197 shown
Type
Access
Show
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet Points List
DescriptionStates
AImin4SUP_AIR_TEMPSupply Air Temperature°FRead
AI5RET_AIR_TEMPReturn Air Temperature°FRead
AI9OAQ_VALUEOutside Demand Ventilation (OAQ) Value (PPM)ppmRead
AI11AMB_AIR_ENTHOutside Air EnthalpyRead
AI13RET_AIR_ENTHReturn Air EnthalpyRead
AImin15ACTIVE_ALARMActive AlarmRead
AI16NUMBER_COMPSNumber of Compressors AvailableRead
AI17OP_COOL_STPTOperating Cooling Setpoint°FRead
AI31ECO_DAMP_OUTEconomizer Damper Output Status (0- 100%)Read
AI32EXH_DAMP_OUTExhaust Damper Output Status (0- 100%)Read
AI33BLDG_STATICBuilding Static PressureRead
AI34SFAN_VFD_OUTSupply Fan VFD Output Status (0- 100%)Read
AI35DUCT_STATICDuct Static PressureRead
AI36ALARM_1System Alarm #1Read
AI37ALARM_2System Alarm #2Read
AI38ALARM_3System Alarm #3Read
AI39ALARM_4System Alarm #4Read
AI40ALARM_5System Alarm #5Read
AI41E_C1_ACM_HRSElite Compressor #1 Accumulated Run Time (in hours)hRead
AI42E_C2_ACM_HRSElite Compressor #2 Accumulated Run Time (in hours)hRead
AI43E_C3_ACM_HRSElite Compressor #3 Accumulated Run Time (in hours)hRead
AI44E_C4_ACM_HRSElite Compressor #4 Accumulated Run Time (in hours)hRead
AI45I_C1_ACM_HRSIntelli-Comfort Compressor #1 Accumulated Run Time (in hours)hRead
AI46I_C2_ACM_HRSIntelli-Comfort Compressor #2 Accumulated Run Time (in hours)hRead
AI47HGR_VLV_OUTHot Gas Reheat Valve Output Status (0- 100%)Read
AI48NUMBER_HEATNumber of Heat Stages Available (0Read
AI49OP_HEAT_STPTOperating Heating Setpoint°FRead
AI55HW_VLV_OUTHot Water Valve Output Status (0- 100%)Read
AI56CV_VAV_SELECCV VAV Selected (0= Valid CV, 1=Valid VAV, 2= Invalid Value)Read
AI67REVISIONDevice RevisionRead
AI76H1_ACCUM_HRSHeating #1 Accumulated Run Time (in hours)hRead
AI77H2_ACCUM_HRSHeating #2 Accumulated Run Time (in hours)hRead
AI78H3_ACCUM_HRSHeating #3 Accumulated Run Time (in hours)hRead
AI86AIR_MON_INPUTAir Monitor Station InputRead
AVmin1OCC_COOL_SPOccupied Cooling Setpoint; range 46 to 99, default 72°FWrite
AV2UNOC_COOL_SPUn-Occupied Cooling Setpoint; range 46 to 99, default 85°FWrite
AV3SAT_COOL_SPSupply Air Temperature Limit for Cooling Setpoint (degrees; range 40 to 65, default 50°FWrite
AVmin6SPACE_TEMPSpace (Indoor) Air Temperature°FWrite
AV7AMB_TEMPOutside Air Temperature°FWrite
AV8IAQ_VALUEDemand Ventilation (IAQ) Value (PPM); range 0 to 5000ppmWrite
AV10AMB_AIR_HUMOutside Air HumidityWrite
AV12RET_AIR_HUMReturn Air HumidityWrite
AV14ACC_OVER_TMEAccumulated Unoccupied Override Time (in hours)hWrite
AV18DEMVENT_STPTDemand Ventilation Setpoint; range 0 to 5000, default 1000Write
AV19ECON_MIN_POSEconomizer Minimum Position; range 0 to 100, default 20Write
AV20ECO_1ST_STPTEconomizer First Stage Setpoint; range 40 to 65, default 55°FWrite
AV21ECO_2ND_STPTEconomizer Second Stage Setpoint; range 40 to 65, default 50°FWrite
AV22ECON_OAEN_SPEconomizer Outside Air Enthalpy Setpoint; range 10 to 50, default 27Write
AV23ECON_OAT_ENAEconomizer Outside Air Temperature Enable Setpoint; range 40 to 80, default 55°FWrite
AV24COM_V_HI_SPComfort Ventilation Upper Setpoint (degrees F); range 65 to 85, default 80°FWrite
AV25COM_V_LOW_SPComfort Ventilation LowerSetpoint (degrees F); range 60 to 80, default 70°FWrite
AV26TEM_HUM_STPTTemperature Humidity Setpoint (percent Humidity); range 20 to 80, default 50Write
AV27HGR_HUM_STPTHot Gas Reheat Humidity Setpoint (percent Humidity); range 0 to 100, default 50Write
AV28MAX_TH_OFSETMax Temperature Humidity Setpoint Offset; range 0 to 5, default 3Write
AV29TH_OFFSETTemperature Humidity % Humidity that = 1°F; range 1 to 10, default 5Write
AV30MAX_DMV_ECONMaximum Demand Ventillation Economizer Position; range 0 to 100, default 50Write
AVmin50OCC_HEAT_SPOccupied Heating Setpoint; range 45 to 98, default 68°FWrite
AV51UNOC_HEAT_SPUn-Occupied Heating Setpoint; range 45 to 98, default 60°FWrite
AV52SAT_HEAT_SPSupply Air Temperature Limit for Heating Setpoint (degrees; range 100 to 180, default 135°FWrite
AV53SAT_ALM_HEATSupply Air Temperature Alarm Setpoint for Heating; range 0 to 120, default 0Write
AV54OAT_HEAT_L_OOutdoor Air Temperature HeatingLockout Temperature; range 0 to 100, default 75°FWrite
AV57BLDG_SP_STPTBuilding Static Pressure Setpoint; range -0.25 to 0.25, default 0.15Write
AV58DUCT_SP_STPTDuct Static Pressure Setpoint; range 0 to 5, default 1.5Write
AV59DUCT_SD_STPTDuct Static Pressure Shutdown Setpoint; range 0 to 5, default 4.5Write
AV60VAV_OHEAT_SPVAV Occupied Heating Setpoint (degrees F); range 40 to 85, default 68°FWrite
AV61MWU_RAT_STPTMorning Warm-Up and VAV Heating: Return Air Temperature; range 50 to 85, default 70°FWrite
AV62HYD_S1_SA_SPHydronic Heating Stage #1 Supply Air Setpoint (degrees; range 80 to 180, default 120°FWrite
AV63HYD_S2_SA_SPHydronic Heating Stage #2 Supply Air Setpoint (degrees; range 81 to 180, default 150°FWrite
AV64VAV_CL_HI_SPVAV Cooling Supply Air Temperature: Upper Setpoint (degrees; range 41 to 70, default 60°FWrite
AV65VAV_CL_LO_SPVAV Cooling Supply Air Temperature: Lower Setpoint (degrees; range 40 to 69, default 55°FWrite
AV66VAV_SAT_RSETVAV Cooling Supply Air Temperature: Reset Setpoint (Space; range 40 to 85, default 72°FWrite
AV69OP_STPT_DIFOperating Setpoint Differential; range 1 to 5, default 1Write
AV70SAT_ALM_COOLSupply Air Temperature Alarm Setpoint for Cooling; range 0 to 80, default 0Write
AV71SPCE_ALM_TMPSpace Sensor Alarm Temperature (degrees F; range 0 to 25, default 0°FWrite
AV72SPCE_ALM_TIMSpace Sensor Alarm Time (minutes F; range 0 to 120, default 0Write
AV73SP_OFF_RANGESpace Temprature Sensor Offset Range (0-5 degrees); range 0 to 5, default 3Write
AV74OAT_COOL_L_OOutdoor Air Temperature Cooling Lockout Temperature; range 0 to 100, default 45°FWrite
AV75UNOC_OVR_TPUnoccupied Override Time Period; range 0 to 240, default 60Write
AV79OAQ_STPTAir Quality Setpoint Outside; range 0 to 5000, default 1000Write
AV80IO_DVNT_STPTIndoor Outdoor Demand Ventilation Setpoint; range 0 to 2000, default 700Write
AV81POP_HOURSPre-Occupancy Purge Time (hours); range 0 to 23, default 4Write
AV82POP_MINUTESPre-Occupancy Purge Time (minutes); range 0 to 59, default 0Write
AV84ECON_RAEN_SPEconomizer Return Air Enthalpy Setpoint; range 10 to 50, default 27Write
AV85MIN_AMB_TEMP_SPMinimum Outdoor Air Temperature Setpoint (0-100%); range 0 to 100%, default 0Write
AV87ECON_MIN_POS_LPEcon Minimum Position For Low Speed Fan; range 0 to 100, default 25Write
AV88LOW_AMB_ECON_STPTLow Ambient Economizer Temperature Setpoint (0 disables); range 0 to 60, default 0Write
AV89LOW_AMB_ECON_MINLow Ambient Economizer Minimum Position (Percent) (0 disables); range 0 to 99, default 0Write
AV90FAN_SPD_NO_HEAT_COOLFan Speed: No Heating No Cooling; range 0 to 100, default 50Write
AV91FAN_SPD_1ST_COOLFan Speed: 1st Stage Cooling; range 0 to 100, default 70Write
AV92FAN_SPD_1ST_HEATFan Speed: 1st Stage Heating; range 0 to 100, default 100Write
AV93FAN_SPD_ALL_COOLFan Speed: All Stages Cooling; range 0 to 100, default 100Write
AV94FAN_SPD_ALL_HEATFan Speed: All Stages Heating; range 0 to 100, default 100Write
BI4REM_CONT_ENARemote Control EnabledRead
BImin11MODBUS_ALARMModbus Communication AlarmRead
BI14LOW_SUP_VOLTLow Supply VoltageRead0=comps not overridden by LSV, 1=comps overridden
BI15DIRT_FILT_SWDirty Filter Switch StatusRead0=open,1=closed fault
BImin16AIR_PROOF_SWAir Proving Switch StatusRead1=closed, 0=open no air flow
BI17PURGE_SWITCHPurge Switch StatusRead0=open,1=closed
BI18HGR_STATHot Gas Reheat Output StatusRead0=output is OFF, 1=output is ON
BI30EX_FAN_STATExhaust Fan Output StatusRead0=output is OFF, 1=output is ON
BI31ECONO_STATUSEconomizer Output StatusRead0=not Free Cooling, 1= Free Cooling
BI32FRECOOL_STATFree Cooling Mode StatusRead0=comps not overridden by Econo, 1=comps overridden
BI33COM_VENT_STAComfort Ventilation Mode StatusRead1=control is in Comfort Vent mode, 0= it is not
BI40E_IFAN_STATElite Indoor Fan Output StatusRead0=output is OFF, 1=output is ON
BI41E_FAN_OVERElite Fan Overload Switch Input StatusRead1=closed, 0=open fault
BI42E_COMP1_STATElite Compressor #1 Output StatusRead0=output is OFF, 1=output is ON
BI43E_LPS1Elite Low Pressure Switch for Compressor #1 Input StatusRead1=closed, 0=open fault
BI44E_HPS1Elite High Pressure Switch for Compressor #1 Input StatusRead1=closed, 0=open fault
BI45E_C1_OVRLOADElite Compressor #1 Overload Switch Input StatusRead1=closed, 0=open fault
BI46E_COMP2_STATElite Compressor #2 Output StatusRead0=output is OFF, 1=output is ON
BI47E_LPS2Elite Low Pressure Switch for Compressor #2 Input StatusRead1=closed, 0=open fault
BI48E_HPS2Elite High Pressure Switch for Compressor #2 Input StatusRead1=closed, 0=open fault
BI49E_C2_OVRLOADElite Compressor #2 Overload Switch Input StatusRead1=closed, 0=open fault
BI50E_CFAN1_STATElite Condenser Fan #1 Output StatusRead0=output is OFF, 1=output is ON
BI51E_COMP3_STATElite Compressor #3 Output StatusRead0=output is OFF, 1=output is ON
BI52E_LPS3Elite Low Pressure Switch for Compressor #3 Input StatusRead1=closed, 0=open fault
BI53E_HPS3Elite High Pressure Switch for Compressor #3 Input StatusRead1=closed, 0=open fault
BI54E_C3_OVRLOADElite Compressor #3 Overload Switch Input StatusRead1=closed, 0=open fault
BI55E_COMP4_STATElite Compressor #4 Output StatusRead0=output is OFF, 1=output is ON
BI56E_LPS4Elite Low Pressure Switch for Compressor #4 Input StatusRead1=closed, 0=open fault
BI57E_HPS4Elite High Pressure Switch for Compressor #4 Input StatusRead1=closed, 0=open fault
BI58E_C4_OVRLOADElite Compressor #4 Overload Switch Input StatusRead1=closed, 0=open fault
BI59E_CFAN2_STATElite Condenser Fan #2 Output Status Input StatusRead0=output is OFF, 1=output is ON
BI60E_GAS_VLVE1Elite Gas Valve #1 Input StatusRead1=energized, 0=not energized
BI61E_LIMIT_1Elite Limit Switch #1 Input StatusRead1=closed, 0=open fault
BI62E_GAS_VLVE2Elite Gas Valve #2 Input StatusRead1=energized, 0=not energized
BI63E_LIMIT_2Elite Limit Switch #2 Input StatusRead1=closed, 0=open fault
BI64E_GAS_VLVE3Elite Gas Valve #3 Input StatusRead1=energized, 0=not energized
BI65E_LIMIT_3Elite Limit Switch #3 Input StatusRead1=closed, 0=open fault
BI66E_FREEZE_STHot H2O Freeze Thermostat Switch Input StatusRead1=closed, 0=open fault
BI68HEAT_1_STATH1 Heating Output #1 StatusRead0=output is OFF, 1=output is ON
BI69HEAT_2_STATH2 Heating Output #2 StatusRead0=output is OFF, 1=output is ON
BI70HEAT_3_STATH3 Heating Output #3 StatusRead0=output is OFF, 1=output is ON
BI71I_IFAN_STATIntelli-Comfort Indoor Fan Output StatusRead0=output is OFF, 1=output is ON
BI72I_FAN_OVERIntelli-Comfort Fan Overload Switch Input StatusRead0=open,1=closed
BI73I_COMP1_STATIntelli-Comfort Compressor #1 Input StatusRead0=output is OFF, 1=output is ON
BI74I_LPS1Intelli-Comfort Low Pressure Switch for Compressor #1 Input StatusRead1=closed, 0=open fault
BI75I_HPS1Intelli-Comfort High Pressure Switch for Compressor #1 Input StatusRead1=closed, 0=open fault
BI76I_COMP2_STATIntelli-Comfort Compressor #2 Input StatusRead0=output is OFF, 1=output is ON
BI77I_LPS2Intelli-Comfort Low Pressure Switch for Compressor #2 Input StatusRead1=closed, 0=open fault
BI78I_HPS2Intelli-Comfort High Pressure Switch for Compressor #2 Input StatusRead1=closed, 0=open fault
BI79I_CFAN_STATIntelli-Comfort Condenser Fan #1 Input StatusRead0=output is OFF, 1=output is ON
BI80I_GAS_VLVE1Intelli-Comfort Gas Valve #1 Input StatusRead
BI81I_LIMIT_1Intelli-Comfort Limit Switch #1 Input StatusRead
BI82I_FREEZE_1Intelli-Comfort Freeze Thermostat Switch #1 Input StatusRead0=open,1=closed
BI83I_FREEZE_2Intelli-Comfort Freeze Thermostat Switch #2 Input StatusRead0=open,1=closed
BI85ALARM_1_ONAlarm Buffer #1Read0=Alarm has cleared, 1=Alarm is still active
BI86ALARM_2_ONAlarm Buffer #2Read0=Alarm has cleared, 1=Alarm is still active
BI87ALARM_3_ONAlarm Buffer #3Read0=Alarm has cleared, 1=Alarm is still active
BI88ALARM_4_ONAlarm Buffer #4Read0=Alarm has cleared, 1=Alarm is still active
BI89ALARM_5_ONAlarm Buffer #5Read0=Alarm has cleared, 1=Alarm is still active
BI1024_STG_EXP_PRESFour Stage Expansion board PresentRead
BI103VAV_INTELLI_2_PRESVAV Intelli-Comfort 2 Expansion Board PresentRead
BI104FREEZE_STAT_1Freeze Stat # 1Read
BI105FREEZE_STAT_2Freeze Stat # 2Read
BI106FREEZE_STAT_3Freeze Stat # 3Read
BI107FREEZE_STAT_4Freeze Stat # 4Read
BV1OCCUPIED_ENAOccupied Input EnabledWrite
BV2HYDRONC_HEATHydronic Heat EnabledWrite
BV3HH_REVER_VLVHydronic Heat Reverse Actuated Valve InstalledWrite
BV5VAV_OCC_HEATVAV Occupied Heating EnabledWrite
BV6MORN_WARM-UPMorning Warm-Up EnabledWrite
BV7ECONO_INSTEconomizer InstalledWrite
BV8PWR_EX_INSTPower Exhaust InstalledWrite
BV9MOD_EX_INSTModulating Exhaust InstalledWrite
BV10EX_VFD_INSTExhaust VFD InstalledWrite
BV12REDLINERedlineWrite0=clear redline, 1=set redline operation
BV13LOADSHEDLoadshedWrite0=clear loadshed, 1=set loadshed operation
BV19LOW_AMB_OVRDLow Ambient TemperatureWrite0=comps not overridden by LAT, 1=comps overridden
BV20POP_ENABLEDPre-Occupancy Purge EnabledWrite
BV21FAN_ON_W_SENCV-Indoor Fan Operates with Space Sensor Present Option EnabledWrite
BV22SAT_COOLINGSupply Air Temperature Limit for Cooling EnabledWrite
BV23COOLING_ENACooling Mode EnabledWrite
BV24SAT_HEATINGSupply Air Temperature Limit for Heating EnabledWrite
BV25HEATING_ENAHeating Mode EnabledWrite
BV26SEN_FAULT_ENSpace Sensor Fault Override (Construction Mode) EnabledWrite
BV28INTELLI-STRTIntelli-Start EnabledWrite
BV29BP_SENS_INSTBuilding Static Pressure Sensor InstalledWrite
BV34CVM_COOLINGComfort Ventilation Mode for Cooling EnabledWrite
BV35CVM_HEATINGComfort Ventilation Mode for Heating EnabledWrite
BV36ECO_L_TO_SATEconomizer Loading to Control Supply Air Temperature EnabledWrite
BV37OAH_SENSOROutside Air Humidity Sensor EnabledWrite
BV38RAH_SENSORReturn/Inside Air Humidity Sensor EnabledWrite
BV39DEMAND_VENTDemand Ventilation (using Inside Sensor) EnabledWrite
BV67FAN_HEATTurn OFF Continuous Fan when Starting Heat EnabledWrite0=Continuous Fan ON
BV90DF_SW_INSTDirty Filter Switch InstalledWrite
BV93OCC_COMS_ENAOccupied Thermostat or Communication Input EnabledWrite
BV96VAV_UNOCC_HEATVAV Unoccupied Heating EnabledWrite
BV97THERMO_CONTROLThermostat Only Control EnableWrite
BV98DIFF_ENTH_MODEDifferential enthalpy mode enabledWrite
BV99COMM_RHAccept Comm Value for RHWrite
BV100COMM_OHAccept Comm Value for OHWrite
BV101COMM_OATAccept Comm Value for OATWrite
BV108COMM_STAccept Comm Value for Space TemperatureWrite
BV109COMM_IAQAccept Comm Value for Indoor Quality SensorWrite
BV110MIN_AMB_SENMinimum Outdoor Air Sensor EnabledWrite
BV111REM_CONT_BAS_ECONRemote Control Third Party BAS Economizer EnableWrite
Object ID lookup: Johnson Controls Simplicity LINC Gateway point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)

How many BACnet points does the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) have?

This list has 197 BACnet objects: 34 analog inputs, 58 analog values, 65 binary inputs, 40 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet points are writable?

98 of the 197 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet documentation?

Johnson Controls does not publish it on its own website. This list comes from Simplicity LINC Gateway Application Guide (ConFig v1.01d) (1031990-UAD-A-0313), revision 2013-03, a copy hosted by Distributor web store (Shopify CDN) at https://cdn.shopify.com/s/files/1/2139/8037/files/Johnson_Controls_Simplicity_LINC_GATEWAY_ee98fa51-0864-41dc-924a-3e68ee281f71.pdf?788. Ask Johnson Controls or its representative for the current revision.

What are the minimum BACnet points to integrate the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)?

Start with AV 1 OCC_COOL_SP (Occupied cooling setpoint, 46-99 °F); AV 50 OCC_HEAT_SP (Occupied heating setpoint, 45-98 °F); BI 16 AIR_PROOF_SW (Air proving switch (1 = air flow)); AI 4 SUP_AIR_TEMP (Supply air temperature); AV 6 SPACE_TEMP (Space temperature (BAS can write it)); AI 15 ACTIVE_ALARM (Active alarm); BI 11 MODBUS_ALARM (Gateway lost Modbus link to the unit).

Can the BMS supply sensor values to the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)?

AV 6 SPACE_TEMP, AV 7 AMB_TEMP, AV 10 AMB_AIR_HUM, AV 12 RET_AIR_HUM and AV 8 IAQ_VALUE are writable; set BV 108 COMM_ST, BV 101 COMM_OAT, BV 100 COMM_OH, BV 99 COMM_RH or BV 109 COMM_IAQ so the controller accepts the BAS value.

How do I check these points on the real Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Johnson Controls BACnet points lists

Source: Simplicity LINC Gateway Application Guide (ConFig v1.01d) · 1031990-UAD-A-0313 · rev. 2013-03. Object names, instances and units are reproduced as published; descriptions are our own.