- Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Rooftop unit BACnet gateway · BACnet points list
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet points list
Updated 12 November 2026Unofficial source
The Simplicity LINC is a small gateway mounted in the rooftop unit's control panel. It polls the Simplicity unit controller over Modbus RTU and exposes a fixed set of points on BACnet MS/TP; no configuration is needed. The map has 34 analog inputs, 58 analog values (setpoints, sensor values and settings), 65 binary inputs (outputs, safeties, alarms) and 40 binary values (option and mode enables, comm-value selects, redline/loadshed).
This page lists 197 BACnet objects for the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) — 98 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Johnson Controls’s documentation hosted by Distributor web store (Shopify CDN), not by Johnson Controls itself, so treat it as unofficial.
- Manufacturer
- Johnson Controls
- Model
- Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
- Equipment
- Rooftop unit BACnet gateway
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 197 (98 writable)
- Transport
- BACnet MS/TP
- Firmware
- ConFig v1.01d
- Default device instance
- 23001
- Also known as
- Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet
- Source document
- Simplicity LINC Gateway Application Guide (ConFig v1.01d) · 1031990-UAD-A-0313 · rev. 2013-03 (unofficial copy, hosted by Distributor web store (Shopify CDN))
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Set the MAC address (1-99) on DIP switches A0-A7 and the baud on B0-B3 (default 38400); the device instance combines the DE modifier 230 with the MAC (default 23001). The BAS writes the occupied/unoccupied cooling and heating setpoints and can supply space temperature, outdoor temperature, humidity and IAQ values once the matching COMM_ accept BV is set. Read supply air temperature, the active alarm and the alarm buffers.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 1 | OCC_COOL_SP | Occupied cooling setpoint, 46-99 °F | Write |
| AV 50 | OCC_HEAT_SP | Occupied heating setpoint, 45-98 °F | Write |
| BI 16 | AIR_PROOF_SW | Air proving switch (1 = air flow) | Read |
| AI 4 | SUP_AIR_TEMP | Supply air temperature | Read |
| AV 6 | SPACE_TEMP | Space temperature (BAS can write it) | Write |
| AI 15 | ACTIVE_ALARM | Active alarm | Read |
| BI 11 | MODBUS_ALARM | Gateway lost Modbus link to the unit | Read |
Sensors & values from the BMS
AV 6 SPACE_TEMP, AV 7 AMB_TEMP, AV 10 AMB_AIR_HUM, AV 12 RET_AIR_HUM and AV 8 IAQ_VALUE are writable; set BV 108 COMM_ST, BV 101 COMM_OAT, BV 100 COMM_OH, BV 99 COMM_RH or BV 109 COMM_IAQ so the controller accepts the BAS value.
Network setup
- MAC address 1-99 on DIP switches A0-A7 (default 1); baud on B0-B3 (default 38400).
- Device instance = DE modifier 230 combined with the MAC address (default 23001); default unit name YORK_RTU.
- The Simplicity board must stay at Modbus address 1 to talk to the gateway.
Watch out for
- The Simplicity flash memory is rated for 1,000,000 writes; do not write settings more than about once every 10 minutes on average.
- New data can take up to two minutes to show.
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 4 | SUP_AIR_TEMP | Supply Air Temperature | °F | Read | |
| AI | 5 | RET_AIR_TEMP | Return Air Temperature | °F | Read | |
| AI | 9 | OAQ_VALUE | Outside Demand Ventilation (OAQ) Value (PPM) | ppm | Read | |
| AI | 11 | AMB_AIR_ENTH | Outside Air Enthalpy | Read | ||
| AI | 13 | RET_AIR_ENTH | Return Air Enthalpy | Read | ||
| AImin | 15 | ACTIVE_ALARM | Active Alarm | Read | ||
| AI | 16 | NUMBER_COMPS | Number of Compressors Available | Read | ||
| AI | 17 | OP_COOL_STPT | Operating Cooling Setpoint | °F | Read | |
| AI | 31 | ECO_DAMP_OUT | Economizer Damper Output Status (0- 100%) | Read | ||
| AI | 32 | EXH_DAMP_OUT | Exhaust Damper Output Status (0- 100%) | Read | ||
| AI | 33 | BLDG_STATIC | Building Static Pressure | Read | ||
| AI | 34 | SFAN_VFD_OUT | Supply Fan VFD Output Status (0- 100%) | Read | ||
| AI | 35 | DUCT_STATIC | Duct Static Pressure | Read | ||
| AI | 36 | ALARM_1 | System Alarm #1 | Read | ||
| AI | 37 | ALARM_2 | System Alarm #2 | Read | ||
| AI | 38 | ALARM_3 | System Alarm #3 | Read | ||
| AI | 39 | ALARM_4 | System Alarm #4 | Read | ||
| AI | 40 | ALARM_5 | System Alarm #5 | Read | ||
| AI | 41 | E_C1_ACM_HRS | Elite Compressor #1 Accumulated Run Time (in hours) | h | Read | |
| AI | 42 | E_C2_ACM_HRS | Elite Compressor #2 Accumulated Run Time (in hours) | h | Read | |
| AI | 43 | E_C3_ACM_HRS | Elite Compressor #3 Accumulated Run Time (in hours) | h | Read | |
| AI | 44 | E_C4_ACM_HRS | Elite Compressor #4 Accumulated Run Time (in hours) | h | Read | |
| AI | 45 | I_C1_ACM_HRS | Intelli-Comfort Compressor #1 Accumulated Run Time (in hours) | h | Read | |
| AI | 46 | I_C2_ACM_HRS | Intelli-Comfort Compressor #2 Accumulated Run Time (in hours) | h | Read | |
| AI | 47 | HGR_VLV_OUT | Hot Gas Reheat Valve Output Status (0- 100%) | Read | ||
| AI | 48 | NUMBER_HEAT | Number of Heat Stages Available (0 | Read | ||
| AI | 49 | OP_HEAT_STPT | Operating Heating Setpoint | °F | Read | |
| AI | 55 | HW_VLV_OUT | Hot Water Valve Output Status (0- 100%) | Read | ||
| AI | 56 | CV_VAV_SELEC | CV VAV Selected (0= Valid CV, 1=Valid VAV, 2= Invalid Value) | Read | ||
| AI | 67 | REVISION | Device Revision | Read | ||
| AI | 76 | H1_ACCUM_HRS | Heating #1 Accumulated Run Time (in hours) | h | Read | |
| AI | 77 | H2_ACCUM_HRS | Heating #2 Accumulated Run Time (in hours) | h | Read | |
| AI | 78 | H3_ACCUM_HRS | Heating #3 Accumulated Run Time (in hours) | h | Read | |
| AI | 86 | AIR_MON_INPUT | Air Monitor Station Input | Read | ||
| AVmin | 1 | OCC_COOL_SP | Occupied Cooling Setpoint; range 46 to 99, default 72 | °F | Write | |
| AV | 2 | UNOC_COOL_SP | Un-Occupied Cooling Setpoint; range 46 to 99, default 85 | °F | Write | |
| AV | 3 | SAT_COOL_SP | Supply Air Temperature Limit for Cooling Setpoint (degrees; range 40 to 65, default 50 | °F | Write | |
| AVmin | 6 | SPACE_TEMP | Space (Indoor) Air Temperature | °F | Write | |
| AV | 7 | AMB_TEMP | Outside Air Temperature | °F | Write | |
| AV | 8 | IAQ_VALUE | Demand Ventilation (IAQ) Value (PPM); range 0 to 5000 | ppm | Write | |
| AV | 10 | AMB_AIR_HUM | Outside Air Humidity | Write | ||
| AV | 12 | RET_AIR_HUM | Return Air Humidity | Write | ||
| AV | 14 | ACC_OVER_TME | Accumulated Unoccupied Override Time (in hours) | h | Write | |
| AV | 18 | DEMVENT_STPT | Demand Ventilation Setpoint; range 0 to 5000, default 1000 | Write | ||
| AV | 19 | ECON_MIN_POS | Economizer Minimum Position; range 0 to 100, default 20 | Write | ||
| AV | 20 | ECO_1ST_STPT | Economizer First Stage Setpoint; range 40 to 65, default 55 | °F | Write | |
| AV | 21 | ECO_2ND_STPT | Economizer Second Stage Setpoint; range 40 to 65, default 50 | °F | Write | |
| AV | 22 | ECON_OAEN_SP | Economizer Outside Air Enthalpy Setpoint; range 10 to 50, default 27 | Write | ||
| AV | 23 | ECON_OAT_ENA | Economizer Outside Air Temperature Enable Setpoint; range 40 to 80, default 55 | °F | Write | |
| AV | 24 | COM_V_HI_SP | Comfort Ventilation Upper Setpoint (degrees F); range 65 to 85, default 80 | °F | Write | |
| AV | 25 | COM_V_LOW_SP | Comfort Ventilation LowerSetpoint (degrees F); range 60 to 80, default 70 | °F | Write | |
| AV | 26 | TEM_HUM_STPT | Temperature Humidity Setpoint (percent Humidity); range 20 to 80, default 50 | Write | ||
| AV | 27 | HGR_HUM_STPT | Hot Gas Reheat Humidity Setpoint (percent Humidity); range 0 to 100, default 50 | Write | ||
| AV | 28 | MAX_TH_OFSET | Max Temperature Humidity Setpoint Offset; range 0 to 5, default 3 | Write | ||
| AV | 29 | TH_OFFSET | Temperature Humidity % Humidity that = 1°F; range 1 to 10, default 5 | Write | ||
| AV | 30 | MAX_DMV_ECON | Maximum Demand Ventillation Economizer Position; range 0 to 100, default 50 | Write | ||
| AVmin | 50 | OCC_HEAT_SP | Occupied Heating Setpoint; range 45 to 98, default 68 | °F | Write | |
| AV | 51 | UNOC_HEAT_SP | Un-Occupied Heating Setpoint; range 45 to 98, default 60 | °F | Write | |
| AV | 52 | SAT_HEAT_SP | Supply Air Temperature Limit for Heating Setpoint (degrees; range 100 to 180, default 135 | °F | Write | |
| AV | 53 | SAT_ALM_HEAT | Supply Air Temperature Alarm Setpoint for Heating; range 0 to 120, default 0 | Write | ||
| AV | 54 | OAT_HEAT_L_O | Outdoor Air Temperature HeatingLockout Temperature; range 0 to 100, default 75 | °F | Write | |
| AV | 57 | BLDG_SP_STPT | Building Static Pressure Setpoint; range -0.25 to 0.25, default 0.15 | Write | ||
| AV | 58 | DUCT_SP_STPT | Duct Static Pressure Setpoint; range 0 to 5, default 1.5 | Write | ||
| AV | 59 | DUCT_SD_STPT | Duct Static Pressure Shutdown Setpoint; range 0 to 5, default 4.5 | Write | ||
| AV | 60 | VAV_OHEAT_SP | VAV Occupied Heating Setpoint (degrees F); range 40 to 85, default 68 | °F | Write | |
| AV | 61 | MWU_RAT_STPT | Morning Warm-Up and VAV Heating: Return Air Temperature; range 50 to 85, default 70 | °F | Write | |
| AV | 62 | HYD_S1_SA_SP | Hydronic Heating Stage #1 Supply Air Setpoint (degrees; range 80 to 180, default 120 | °F | Write | |
| AV | 63 | HYD_S2_SA_SP | Hydronic Heating Stage #2 Supply Air Setpoint (degrees; range 81 to 180, default 150 | °F | Write | |
| AV | 64 | VAV_CL_HI_SP | VAV Cooling Supply Air Temperature: Upper Setpoint (degrees; range 41 to 70, default 60 | °F | Write | |
| AV | 65 | VAV_CL_LO_SP | VAV Cooling Supply Air Temperature: Lower Setpoint (degrees; range 40 to 69, default 55 | °F | Write | |
| AV | 66 | VAV_SAT_RSET | VAV Cooling Supply Air Temperature: Reset Setpoint (Space; range 40 to 85, default 72 | °F | Write | |
| AV | 69 | OP_STPT_DIF | Operating Setpoint Differential; range 1 to 5, default 1 | Write | ||
| AV | 70 | SAT_ALM_COOL | Supply Air Temperature Alarm Setpoint for Cooling; range 0 to 80, default 0 | Write | ||
| AV | 71 | SPCE_ALM_TMP | Space Sensor Alarm Temperature (degrees F; range 0 to 25, default 0 | °F | Write | |
| AV | 72 | SPCE_ALM_TIM | Space Sensor Alarm Time (minutes F; range 0 to 120, default 0 | Write | ||
| AV | 73 | SP_OFF_RANGE | Space Temprature Sensor Offset Range (0-5 degrees); range 0 to 5, default 3 | Write | ||
| AV | 74 | OAT_COOL_L_O | Outdoor Air Temperature Cooling Lockout Temperature; range 0 to 100, default 45 | °F | Write | |
| AV | 75 | UNOC_OVR_TP | Unoccupied Override Time Period; range 0 to 240, default 60 | Write | ||
| AV | 79 | OAQ_STPT | Air Quality Setpoint Outside; range 0 to 5000, default 1000 | Write | ||
| AV | 80 | IO_DVNT_STPT | Indoor Outdoor Demand Ventilation Setpoint; range 0 to 2000, default 700 | Write | ||
| AV | 81 | POP_HOURS | Pre-Occupancy Purge Time (hours); range 0 to 23, default 4 | Write | ||
| AV | 82 | POP_MINUTES | Pre-Occupancy Purge Time (minutes); range 0 to 59, default 0 | Write | ||
| AV | 84 | ECON_RAEN_SP | Economizer Return Air Enthalpy Setpoint; range 10 to 50, default 27 | Write | ||
| AV | 85 | MIN_AMB_TEMP_SP | Minimum Outdoor Air Temperature Setpoint (0-100%); range 0 to 100%, default 0 | Write | ||
| AV | 87 | ECON_MIN_POS_LP | Econ Minimum Position For Low Speed Fan; range 0 to 100, default 25 | Write | ||
| AV | 88 | LOW_AMB_ECON_STPT | Low Ambient Economizer Temperature Setpoint (0 disables); range 0 to 60, default 0 | Write | ||
| AV | 89 | LOW_AMB_ECON_MIN | Low Ambient Economizer Minimum Position (Percent) (0 disables); range 0 to 99, default 0 | Write | ||
| AV | 90 | FAN_SPD_NO_HEAT_COOL | Fan Speed: No Heating No Cooling; range 0 to 100, default 50 | Write | ||
| AV | 91 | FAN_SPD_1ST_COOL | Fan Speed: 1st Stage Cooling; range 0 to 100, default 70 | Write | ||
| AV | 92 | FAN_SPD_1ST_HEAT | Fan Speed: 1st Stage Heating; range 0 to 100, default 100 | Write | ||
| AV | 93 | FAN_SPD_ALL_COOL | Fan Speed: All Stages Cooling; range 0 to 100, default 100 | Write | ||
| AV | 94 | FAN_SPD_ALL_HEAT | Fan Speed: All Stages Heating; range 0 to 100, default 100 | Write | ||
| BI | 4 | REM_CONT_ENA | Remote Control Enabled | Read | ||
| BImin | 11 | MODBUS_ALARM | Modbus Communication Alarm | Read | ||
| BI | 14 | LOW_SUP_VOLT | Low Supply Voltage | Read | 0=comps not overridden by LSV, 1=comps overridden | |
| BI | 15 | DIRT_FILT_SW | Dirty Filter Switch Status | Read | 0=open,1=closed fault | |
| BImin | 16 | AIR_PROOF_SW | Air Proving Switch Status | Read | 1=closed, 0=open no air flow | |
| BI | 17 | PURGE_SWITCH | Purge Switch Status | Read | 0=open,1=closed | |
| BI | 18 | HGR_STAT | Hot Gas Reheat Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 30 | EX_FAN_STAT | Exhaust Fan Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 31 | ECONO_STATUS | Economizer Output Status | Read | 0=not Free Cooling, 1= Free Cooling | |
| BI | 32 | FRECOOL_STAT | Free Cooling Mode Status | Read | 0=comps not overridden by Econo, 1=comps overridden | |
| BI | 33 | COM_VENT_STA | Comfort Ventilation Mode Status | Read | 1=control is in Comfort Vent mode, 0= it is not | |
| BI | 40 | E_IFAN_STAT | Elite Indoor Fan Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 41 | E_FAN_OVER | Elite Fan Overload Switch Input Status | Read | 1=closed, 0=open fault | |
| BI | 42 | E_COMP1_STAT | Elite Compressor #1 Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 43 | E_LPS1 | Elite Low Pressure Switch for Compressor #1 Input Status | Read | 1=closed, 0=open fault | |
| BI | 44 | E_HPS1 | Elite High Pressure Switch for Compressor #1 Input Status | Read | 1=closed, 0=open fault | |
| BI | 45 | E_C1_OVRLOAD | Elite Compressor #1 Overload Switch Input Status | Read | 1=closed, 0=open fault | |
| BI | 46 | E_COMP2_STAT | Elite Compressor #2 Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 47 | E_LPS2 | Elite Low Pressure Switch for Compressor #2 Input Status | Read | 1=closed, 0=open fault | |
| BI | 48 | E_HPS2 | Elite High Pressure Switch for Compressor #2 Input Status | Read | 1=closed, 0=open fault | |
| BI | 49 | E_C2_OVRLOAD | Elite Compressor #2 Overload Switch Input Status | Read | 1=closed, 0=open fault | |
| BI | 50 | E_CFAN1_STAT | Elite Condenser Fan #1 Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 51 | E_COMP3_STAT | Elite Compressor #3 Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 52 | E_LPS3 | Elite Low Pressure Switch for Compressor #3 Input Status | Read | 1=closed, 0=open fault | |
| BI | 53 | E_HPS3 | Elite High Pressure Switch for Compressor #3 Input Status | Read | 1=closed, 0=open fault | |
| BI | 54 | E_C3_OVRLOAD | Elite Compressor #3 Overload Switch Input Status | Read | 1=closed, 0=open fault | |
| BI | 55 | E_COMP4_STAT | Elite Compressor #4 Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 56 | E_LPS4 | Elite Low Pressure Switch for Compressor #4 Input Status | Read | 1=closed, 0=open fault | |
| BI | 57 | E_HPS4 | Elite High Pressure Switch for Compressor #4 Input Status | Read | 1=closed, 0=open fault | |
| BI | 58 | E_C4_OVRLOAD | Elite Compressor #4 Overload Switch Input Status | Read | 1=closed, 0=open fault | |
| BI | 59 | E_CFAN2_STAT | Elite Condenser Fan #2 Output Status Input Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 60 | E_GAS_VLVE1 | Elite Gas Valve #1 Input Status | Read | 1=energized, 0=not energized | |
| BI | 61 | E_LIMIT_1 | Elite Limit Switch #1 Input Status | Read | 1=closed, 0=open fault | |
| BI | 62 | E_GAS_VLVE2 | Elite Gas Valve #2 Input Status | Read | 1=energized, 0=not energized | |
| BI | 63 | E_LIMIT_2 | Elite Limit Switch #2 Input Status | Read | 1=closed, 0=open fault | |
| BI | 64 | E_GAS_VLVE3 | Elite Gas Valve #3 Input Status | Read | 1=energized, 0=not energized | |
| BI | 65 | E_LIMIT_3 | Elite Limit Switch #3 Input Status | Read | 1=closed, 0=open fault | |
| BI | 66 | E_FREEZE_ST | Hot H2O Freeze Thermostat Switch Input Status | Read | 1=closed, 0=open fault | |
| BI | 68 | HEAT_1_STAT | H1 Heating Output #1 Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 69 | HEAT_2_STAT | H2 Heating Output #2 Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 70 | HEAT_3_STAT | H3 Heating Output #3 Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 71 | I_IFAN_STAT | Intelli-Comfort Indoor Fan Output Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 72 | I_FAN_OVER | Intelli-Comfort Fan Overload Switch Input Status | Read | 0=open,1=closed | |
| BI | 73 | I_COMP1_STAT | Intelli-Comfort Compressor #1 Input Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 74 | I_LPS1 | Intelli-Comfort Low Pressure Switch for Compressor #1 Input Status | Read | 1=closed, 0=open fault | |
| BI | 75 | I_HPS1 | Intelli-Comfort High Pressure Switch for Compressor #1 Input Status | Read | 1=closed, 0=open fault | |
| BI | 76 | I_COMP2_STAT | Intelli-Comfort Compressor #2 Input Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 77 | I_LPS2 | Intelli-Comfort Low Pressure Switch for Compressor #2 Input Status | Read | 1=closed, 0=open fault | |
| BI | 78 | I_HPS2 | Intelli-Comfort High Pressure Switch for Compressor #2 Input Status | Read | 1=closed, 0=open fault | |
| BI | 79 | I_CFAN_STAT | Intelli-Comfort Condenser Fan #1 Input Status | Read | 0=output is OFF, 1=output is ON | |
| BI | 80 | I_GAS_VLVE1 | Intelli-Comfort Gas Valve #1 Input Status | Read | ||
| BI | 81 | I_LIMIT_1 | Intelli-Comfort Limit Switch #1 Input Status | Read | ||
| BI | 82 | I_FREEZE_1 | Intelli-Comfort Freeze Thermostat Switch #1 Input Status | Read | 0=open,1=closed | |
| BI | 83 | I_FREEZE_2 | Intelli-Comfort Freeze Thermostat Switch #2 Input Status | Read | 0=open,1=closed | |
| BI | 85 | ALARM_1_ON | Alarm Buffer #1 | Read | 0=Alarm has cleared, 1=Alarm is still active | |
| BI | 86 | ALARM_2_ON | Alarm Buffer #2 | Read | 0=Alarm has cleared, 1=Alarm is still active | |
| BI | 87 | ALARM_3_ON | Alarm Buffer #3 | Read | 0=Alarm has cleared, 1=Alarm is still active | |
| BI | 88 | ALARM_4_ON | Alarm Buffer #4 | Read | 0=Alarm has cleared, 1=Alarm is still active | |
| BI | 89 | ALARM_5_ON | Alarm Buffer #5 | Read | 0=Alarm has cleared, 1=Alarm is still active | |
| BI | 102 | 4_STG_EXP_PRES | Four Stage Expansion board Present | Read | ||
| BI | 103 | VAV_INTELLI_2_PRES | VAV Intelli-Comfort 2 Expansion Board Present | Read | ||
| BI | 104 | FREEZE_STAT_1 | Freeze Stat # 1 | Read | ||
| BI | 105 | FREEZE_STAT_2 | Freeze Stat # 2 | Read | ||
| BI | 106 | FREEZE_STAT_3 | Freeze Stat # 3 | Read | ||
| BI | 107 | FREEZE_STAT_4 | Freeze Stat # 4 | Read | ||
| BV | 1 | OCCUPIED_ENA | Occupied Input Enabled | Write | ||
| BV | 2 | HYDRONC_HEAT | Hydronic Heat Enabled | Write | ||
| BV | 3 | HH_REVER_VLV | Hydronic Heat Reverse Actuated Valve Installed | Write | ||
| BV | 5 | VAV_OCC_HEAT | VAV Occupied Heating Enabled | Write | ||
| BV | 6 | MORN_WARM-UP | Morning Warm-Up Enabled | Write | ||
| BV | 7 | ECONO_INST | Economizer Installed | Write | ||
| BV | 8 | PWR_EX_INST | Power Exhaust Installed | Write | ||
| BV | 9 | MOD_EX_INST | Modulating Exhaust Installed | Write | ||
| BV | 10 | EX_VFD_INST | Exhaust VFD Installed | Write | ||
| BV | 12 | REDLINE | Redline | Write | 0=clear redline, 1=set redline operation | |
| BV | 13 | LOADSHED | Loadshed | Write | 0=clear loadshed, 1=set loadshed operation | |
| BV | 19 | LOW_AMB_OVRD | Low Ambient Temperature | Write | 0=comps not overridden by LAT, 1=comps overridden | |
| BV | 20 | POP_ENABLED | Pre-Occupancy Purge Enabled | Write | ||
| BV | 21 | FAN_ON_W_SEN | CV-Indoor Fan Operates with Space Sensor Present Option Enabled | Write | ||
| BV | 22 | SAT_COOLING | Supply Air Temperature Limit for Cooling Enabled | Write | ||
| BV | 23 | COOLING_ENA | Cooling Mode Enabled | Write | ||
| BV | 24 | SAT_HEATING | Supply Air Temperature Limit for Heating Enabled | Write | ||
| BV | 25 | HEATING_ENA | Heating Mode Enabled | Write | ||
| BV | 26 | SEN_FAULT_EN | Space Sensor Fault Override (Construction Mode) Enabled | Write | ||
| BV | 28 | INTELLI-STRT | Intelli-Start Enabled | Write | ||
| BV | 29 | BP_SENS_INST | Building Static Pressure Sensor Installed | Write | ||
| BV | 34 | CVM_COOLING | Comfort Ventilation Mode for Cooling Enabled | Write | ||
| BV | 35 | CVM_HEATING | Comfort Ventilation Mode for Heating Enabled | Write | ||
| BV | 36 | ECO_L_TO_SAT | Economizer Loading to Control Supply Air Temperature Enabled | Write | ||
| BV | 37 | OAH_SENSOR | Outside Air Humidity Sensor Enabled | Write | ||
| BV | 38 | RAH_SENSOR | Return/Inside Air Humidity Sensor Enabled | Write | ||
| BV | 39 | DEMAND_VENT | Demand Ventilation (using Inside Sensor) Enabled | Write | ||
| BV | 67 | FAN_HEAT | Turn OFF Continuous Fan when Starting Heat Enabled | Write | 0=Continuous Fan ON | |
| BV | 90 | DF_SW_INST | Dirty Filter Switch Installed | Write | ||
| BV | 93 | OCC_COMS_ENA | Occupied Thermostat or Communication Input Enabled | Write | ||
| BV | 96 | VAV_UNOCC_HEAT | VAV Unoccupied Heating Enabled | Write | ||
| BV | 97 | THERMO_CONTROL | Thermostat Only Control Enable | Write | ||
| BV | 98 | DIFF_ENTH_MODE | Differential enthalpy mode enabled | Write | ||
| BV | 99 | COMM_RH | Accept Comm Value for RH | Write | ||
| BV | 100 | COMM_OH | Accept Comm Value for OH | Write | ||
| BV | 101 | COMM_OAT | Accept Comm Value for OAT | Write | ||
| BV | 108 | COMM_ST | Accept Comm Value for Space Temperature | Write | ||
| BV | 109 | COMM_IAQ | Accept Comm Value for Indoor Quality Sensor | Write | ||
| BV | 110 | MIN_AMB_SEN | Minimum Outdoor Air Sensor Enabled | Write | ||
| BV | 111 | REM_CONT_BAS_ECON | Remote Control Third Party BAS Economizer Enable | Write |
No points match these filters.
Object ID lookup: Johnson Controls Simplicity LINC Gateway point IDs by name
AI4SUP_AIR_TEMPAI5RET_AIR_TEMPAI9OAQ_VALUEAI11AMB_AIR_ENTHAI13RET_AIR_ENTHAI15ACTIVE_ALARMAI16NUMBER_COMPSAI17OP_COOL_STPTAI31ECO_DAMP_OUTAI32EXH_DAMP_OUTAI33BLDG_STATICAI34SFAN_VFD_OUTAI35DUCT_STATICAI36ALARM_1AI37ALARM_2AI38ALARM_3AI39ALARM_4AI40ALARM_5AI41E_C1_ACM_HRSAI42E_C2_ACM_HRSAI43E_C3_ACM_HRSAI44E_C4_ACM_HRSAI45I_C1_ACM_HRSAI46I_C2_ACM_HRSAI47HGR_VLV_OUTAI48NUMBER_HEATAI49OP_HEAT_STPTAI55HW_VLV_OUTAI56CV_VAV_SELECAI67REVISIONAI76H1_ACCUM_HRSAI77H2_ACCUM_HRSAI78H3_ACCUM_HRSAI86AIR_MON_INPUTAV1OCC_COOL_SPAV2UNOC_COOL_SPAV3SAT_COOL_SPAV6SPACE_TEMPAV7AMB_TEMPAV8IAQ_VALUEAV10AMB_AIR_HUMAV12RET_AIR_HUMAV14ACC_OVER_TMEAV18DEMVENT_STPTAV19ECON_MIN_POSAV20ECO_1ST_STPTAV21ECO_2ND_STPTAV22ECON_OAEN_SPAV23ECON_OAT_ENAAV24COM_V_HI_SPAV25COM_V_LOW_SPAV26TEM_HUM_STPTAV27HGR_HUM_STPTAV28MAX_TH_OFSETAV29TH_OFFSETAV30MAX_DMV_ECONAV50OCC_HEAT_SPAV51UNOC_HEAT_SPAV52SAT_HEAT_SPAV53SAT_ALM_HEATAV54OAT_HEAT_L_OAV57BLDG_SP_STPTAV58DUCT_SP_STPTAV59DUCT_SD_STPTAV60VAV_OHEAT_SPAV61MWU_RAT_STPTAV62HYD_S1_SA_SPAV63HYD_S2_SA_SPAV64VAV_CL_HI_SPAV65VAV_CL_LO_SPAV66VAV_SAT_RSETAV69OP_STPT_DIFAV70SAT_ALM_COOLAV71SPCE_ALM_TMPAV72SPCE_ALM_TIMAV73SP_OFF_RANGEAV74OAT_COOL_L_OAV75UNOC_OVR_TPAV79OAQ_STPTAV80IO_DVNT_STPTAV81POP_HOURSAV82POP_MINUTESAV84ECON_RAEN_SPAV85MIN_AMB_TEMP_SPAV87ECON_MIN_POS_LPAV88LOW_AMB_ECON_STPTAV89LOW_AMB_ECON_MINAV90FAN_SPD_NO_HEAT_COOLAV91FAN_SPD_1ST_COOLAV92FAN_SPD_1ST_HEATAV93FAN_SPD_ALL_COOLAV94FAN_SPD_ALL_HEATBI4REM_CONT_ENABI11MODBUS_ALARMBI14LOW_SUP_VOLTBI15DIRT_FILT_SWBI16AIR_PROOF_SWBI17PURGE_SWITCHBI18HGR_STATBI30EX_FAN_STATBI31ECONO_STATUSBI32FRECOOL_STATBI33COM_VENT_STABI40E_IFAN_STATBI41E_FAN_OVERBI42E_COMP1_STATBI43E_LPS1BI44E_HPS1BI45E_C1_OVRLOADBI46E_COMP2_STATBI47E_LPS2BI48E_HPS2BI49E_C2_OVRLOADBI50E_CFAN1_STATBI51E_COMP3_STATBI52E_LPS3BI53E_HPS3BI54E_C3_OVRLOADBI55E_COMP4_STATBI56E_LPS4BI57E_HPS4BI58E_C4_OVRLOADBI59E_CFAN2_STATBI60E_GAS_VLVE1BI61E_LIMIT_1BI62E_GAS_VLVE2BI63E_LIMIT_2BI64E_GAS_VLVE3BI65E_LIMIT_3BI66E_FREEZE_STBI68HEAT_1_STATBI69HEAT_2_STATBI70HEAT_3_STATBI71I_IFAN_STATBI72I_FAN_OVERBI73I_COMP1_STATBI74I_LPS1BI75I_HPS1BI76I_COMP2_STATBI77I_LPS2BI78I_HPS2BI79I_CFAN_STATBI80I_GAS_VLVE1BI81I_LIMIT_1BI82I_FREEZE_1BI83I_FREEZE_2BI85ALARM_1_ONBI86ALARM_2_ONBI87ALARM_3_ONBI88ALARM_4_ONBI89ALARM_5_ONBI1024_STG_EXP_PRESBI103VAV_INTELLI_2_PRESBI104FREEZE_STAT_1BI105FREEZE_STAT_2BI106FREEZE_STAT_3BI107FREEZE_STAT_4BV1OCCUPIED_ENABV2HYDRONC_HEATBV3HH_REVER_VLVBV5VAV_OCC_HEATBV6MORN_WARM-UPBV7ECONO_INSTBV8PWR_EX_INSTBV9MOD_EX_INSTBV10EX_VFD_INSTBV12REDLINEBV13LOADSHEDBV19LOW_AMB_OVRDBV20POP_ENABLEDBV21FAN_ON_W_SENBV22SAT_COOLINGBV23COOLING_ENABV24SAT_HEATINGBV25HEATING_ENABV26SEN_FAULT_ENBV28INTELLI-STRTBV29BP_SENS_INSTBV34CVM_COOLINGBV35CVM_HEATINGBV36ECO_L_TO_SATBV37OAH_SENSORBV38RAH_SENSORBV39DEMAND_VENTBV67FAN_HEATBV90DF_SW_INSTBV93OCC_COMS_ENABV96VAV_UNOCC_HEATBV97THERMO_CONTROLBV98DIFF_ENTH_MODEBV99COMM_RHBV100COMM_OHBV101COMM_OATBV108COMM_STBV109COMM_IAQBV110MIN_AMB_SENBV111REM_CONT_BAS_ECON
Integration notes
- Access is from the Read/Write column. The table prefixes each object type with (2) or (5); the guide does not explain the prefix.
- Elite (E_) and Intelli-Comfort (I_) points only report on units with those controller generations; expansion board points need the board.
- Printed descriptors with a stray space after an underscore (e.g. E_FAN_ OVER) are shown without the space.
- The guide prints the list twice (description order and object order); both tables agree, 197 objects.
- Source: Simplicity LINC Gateway application guide 1031990-UAD-A-0313, Tables 2 and 3.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
How many BACnet points does the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) have?
This list has 197 BACnet objects: 34 analog inputs, 58 analog values, 65 binary inputs, 40 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet points are writable?
98 of the 197 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops) BACnet documentation?
Johnson Controls does not publish it on its own website. This list comes from Simplicity LINC Gateway Application Guide (ConFig v1.01d) (1031990-UAD-A-0313), revision 2013-03, a copy hosted by Distributor web store (Shopify CDN) at https://cdn.shopify.com/s/files/1/2139/8037/files/Johnson_Controls_Simplicity_LINC_GATEWAY_ee98fa51-0864-41dc-924a-3e68ee281f71.pdf?788. Ask Johnson Controls or its representative for the current revision.
What are the minimum BACnet points to integrate the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)?
Start with AV 1 OCC_COOL_SP (Occupied cooling setpoint, 46-99 °F); AV 50 OCC_HEAT_SP (Occupied heating setpoint, 45-98 °F); BI 16 AIR_PROOF_SW (Air proving switch (1 = air flow)); AI 4 SUP_AIR_TEMP (Supply air temperature); AV 6 SPACE_TEMP (Space temperature (BAS can write it)); AI 15 ACTIVE_ALARM (Active alarm); BI 11 MODBUS_ALARM (Gateway lost Modbus link to the unit).
Can the BMS supply sensor values to the Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)?
AV 6 SPACE_TEMP, AV 7 AMB_TEMP, AV 10 AMB_AIR_HUM, AV 12 RET_AIR_HUM and AV 8 IAQ_VALUE are writable; set BV 108 COMM_ST, BV 101 COMM_OAT, BV 100 COMM_OH, BV 99 COMM_RH or BV 109 COMM_IAQ so the controller accepts the BAS value.
How do I check these points on the real Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: Simplicity LINC Gateway Application Guide (ConFig v1.01d) · 1031990-UAD-A-0313 · rev. 2013-03. Object names, instances and units are reproduced as published; descriptions are our own.