- T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Fan coil unit controller (room thermostat) · BACnet points list
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP) BACnet points list
Updated 4 November 2026
The T8800 is a compact touch screen fan coil thermostat with BACnet MS/TP. Its 18 objects cover the three fan speed relays, the valve outputs, room temperature, setpoint, power, mode, fan speed, occupancy and an error code. VLV-2 exists only on the TF20 and VLV-M only on the TB21.
This page lists 18 BACnet objects for the Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
- Equipment
- Fan coil unit controller (room thermostat)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 18 (13 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- T8800, T8800-TF20, T8800-TB20, T8800-TB21
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Set the MAC address at the thermostat, discover it on the BACnet MS/TP trunk, then command POWER, ORP-MODE, FAN-S and ZN-SP. Read EFF-ZNT, OCC-S and ERROR.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1101 | POWER | Fan coil on/off command | Command |
| MV 1301 | ORP-MODE | Mode: Cooling, Heating or Ventilation | Write |
| MV 1302 | FAN-S | Fan speed: Auto, Low, Med or High | Write |
| AV 1202 | ZN-SP | Setpoint, 5-35 °C | Write |
| MV 1303 | OCC-S | Occupancy; BAS can override at priority 8 | Command |
| AV 1201 | EFF-ZNT | Room temperature, °C | Read |
| MV 1304 | ERROR | Error status: OK, E1, E2, HI, LO | Read |
Enable & remote start
POWER (BV 1101) turns the fan coil on or off. LC-PWR-PRI (MV 1305) decides whether the touch button writes power at priority 16 (Normal) or priority 8 (High, held for 6 hours), which matters if the BAS also commands POWER.
Sensors & values from the BMS
RZN-T (AI 1008) reads a wired remote sensor; the guide lists no BAS-written temperature object.
Network setup
- MS/TP MAC address 4 to 128; the factory value 128 is not valid for a master, so set the MAC before connecting.
- Baud rate default is Auto; fixed choices are 1200, 9600, 19200, 38400 and 76800.
- Enter the setting menu with the fan coil off by holding the fan and up keys for 5 seconds; MAC is setting 1 and baud rate setting 10.
- No on-board end-of-line termination; fit terminators on the first and last devices.
Watch out for
- With LC-PWR-PRI = High a local power press holds priority 8 for 6 hours and can mask a lower-priority BAS command.
- OCC-S follows the occupancy contact when no remote sensor is fitted; a BAS write at priority 8 overrides it.
- CLG-ONLY on TB20/TB21: a remote change to heating is reverted to cooling by the thermostat.
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 1001 | FAN-H | High fan speed output | Command | Off/On | |
| BO | 1002 | FAN-M | Medium fan speed output | Command | Off/On | |
| BO | 1003 | FAN-L | Low fan speed output | Command | Off/On | |
| BO | 1004 | VLV-1 | Valve output; cooling valve on TF20, cool/heat valve on TB20 | Command | Off/On | |
| BO | 1005 | VLV-2 | Heating valve output; T8800-TF20 only | Command | Off/On | |
| AO | 1006 | VLV-M | Modulating valve output, 0-100 %; T8800-TB21 only | % | Command | |
| AI | 1007 | ZN-T | Room temperature, internal sensor; 0 to 55 °C | °C | Read | |
| AI | 1008 | RZN-T | Room temperature, remote sensor; 0 to 55 °C | °C | Read | |
| BI | 1009 | HW-OCC | Occupancy contact; shares the input with RZN-T | Read | Unoccupied/Occupied | |
| BVmin | 1101 | POWER | Fan coil power on/off | Command | Off/On | |
| BV | 1102 | CLG-ONLY | Cooling and ventilation only; TB20 and TB21 | Write | Disable/Enable | |
| AVmin | 1201 | EFF-ZNT | Current room temperature; 0 to 55 °C | °C | Read | |
| AVmin | 1202 | ZN-SP | Setpoint; 5 to 35 °C | °C | Write | |
| MVmin | 1301 | ORP-MODE | Running mode; local or remote | Write | Cooling, Heating, Ventilation | |
| MVmin | 1302 | FAN-S | Fan speed | Write | Auto, Low, Med, High | |
| MVmin | 1303 | OCC-S | Occupancy status; BAS can override at priority 8 | Command | Unoccupied/Occupied | |
| MVmin | 1304 | ERROR | Error status | Read | OK, E1, E2, HI, LO | |
| MV | 1305 | LC-PWR-PRI | Priority used for local power commands | Write | Normal, High |
No points match these filters.
Object ID lookup: Johnson Controls T8800 Fan Coil Thermostat point IDs by name
Integration notes
- Objects from Table 3 on pages 4-5 of Technical Bulletin Rev 1.0; descriptions from section 3.2.
- The table has no access column. Access is inferred: inputs, EFF-ZNT and ERROR read-only; outputs, POWER and OCC-S (the guide says OCC-S can be overridden at priority 8) commandable; the other values writable.
- Multistate state text is listed in the order printed; the table gives no state numbers.
- The device object (DEV-1) is not listed as a point.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
How many BACnet points does the Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP) have?
This list has 18 BACnet objects: 2 analog inputs, 1 analog output, 2 analog values, 1 binary input, 5 binary outputs, 2 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP) BACnet points are writable?
13 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP) BACnet documentation?
The source is T8800 series BACnet MS/TP Networked Thermostat Controller Technical Bulletin (Rev 1.0), published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/PIGe3jav7ZDIZJecfZS20g/content.
What are the minimum BACnet points to integrate the Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)?
Start with BV 1101 POWER (Fan coil on/off command); MV 1301 ORP-MODE (Mode: Cooling, Heating or Ventilation); MV 1302 FAN-S (Fan speed: Auto, Low, Med or High); AV 1202 ZN-SP (Setpoint, 5-35 °C); MV 1303 OCC-S (Occupancy; BAS can override at priority 8); AV 1201 EFF-ZNT (Room temperature, °C); MV 1304 ERROR (Error status: OK, E1, E2, HI, LO).
How do I enable BMS control of the Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)?
POWER (BV 1101) turns the fan coil on or off. LC-PWR-PRI (MV 1305) decides whether the touch button writes power at priority 16 (Normal) or priority 8 (High, held for 6 hours), which matters if the BAS also commands POWER.
Can the BMS supply sensor values to the Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)?
RZN-T (AI 1008) reads a wired remote sensor; the guide lists no BAS-written temperature object.
How do I check these points on the real T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: T8800 series BACnet MS/TP Networked Thermostat Controller Technical Bulletin · Rev 1.0. Object names, instances and units are reproduced as published; descriptions are our own.