- HMS1655 Fume Hood Controller (BACnet MS/TP)
Laboratory VAV controller (fume hood) · BACnet points list
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The HMS1655 is a fume hood controller and monitor that holds face velocity by driving the exhaust damper and reports sash, pressure, airflow and temperature inputs. Over BACnet MS/TP it exposes six inputs, four analog outputs and four relays, occupancy and emergency purge commands, setpoints, alarm limits, air change and volumetric offset values, network-written sensor values and multistate operating mode and alarm status objects.
This page lists 93 BACnet objects for the Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP) — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- HMS1655 Fume Hood Controller (BACnet MS/TP)
- Equipment
- Laboratory VAV controller (fume hood)
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 93 (62 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Map the operating mode and emergency purge commands, the face velocity setpoint, measured face velocity, sash position and exhaust damper signal, and the face velocity alarm status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MO 1 | Fume Hood Operating Mode | 1 occupied, 2 unoccupied, 3 decommissioned | Write |
| BV 2 | Emergency Purge. Maximum flow | Emergency purge to maximum flow | Write |
| AV 1 | AI-1 Setpoint. Fume Hood Face Velocity Setpoint | Face velocity setpoint | Write |
| BV 1 | Occupancy Status | Occupancy status | Write |
| AI 1 | Analog Input 1. Default: Fume Hood Face Velocity | Measured face velocity | Read |
| AI 2 | Analog Input 2. Default: Sash Position Sensor) | Sash position | Read |
| AO 1 | Analog Output 1. Default: Exhaust Damper Position | Exhaust damper signal | Read |
| MO 3 | Fume Hood Face Velocity Alarm Status | 1 normal, 2 warning, 3 alarm | Read |
Enable & remote start
Fume Hood Operating Mode (MSO 1) is read/write: 1 = occupied, 2 = unoccupied, 3 = decommissioned. Emergency Purge (BV 2) drives maximum flow.
Sensors & values from the BMS
AV 44-47 are writable network variables for humidity, temperature, air changes and differential pressure sent from the BAS.
Network setup
- BACnet MS/TP only.
- Device ID Offset (AV 48) is writable over the network (range 0 to 4,194,000).
Watch out for
- Alarm limits, deadbands and override levels are setup values; don't write them cyclically.
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Analog Input 1. Default: Fume Hood Face Velocity | Face velocity (default use of AI 1) | Read | ||
| AImin | 2 | Analog Input 2. Default: Sash Position Sensor) | Sash position (default use of AI 2) | Read | ||
| AI | 3 | Analog Input 3. Default: DP Sensor | Differential pressure (default use of AI 3) | Read | ||
| AI | 4 | Analog Input 4. Default: Exhaust Air Flow Volume | Exhaust airflow (default use of AI 4) | Read | ||
| AI | 5 | Thermistor Input 1. Default: Ambient Temperature | Ambient temperature | Read | ||
| AI | 6 | Thermistor Input 2. Default: Duct Temperature | Duct temperature | Read | ||
| AOmin | 1 | Analog Output 1. Default: Exhaust Damper Position | Exhaust damper signal | Read | ||
| AO | 2 | Analog Output 2 Spare control output | Spare analog output | Read | ||
| AO | 3 | Analog Output 3 Spare control output | Spare analog output | Read | ||
| AO | 4 | Analog Output 4 Spare control output | Spare analog output | Read | ||
| BI | 1 | Digital Input 1. Default: Fume Hood Sash Switch | Sash switch (default) | Read | ||
| BI | 2 | Digital Input 2. Default: spare digital input | Spare digital input | Read | ||
| BI | 3 | Digital Input 3. Spare digital input | Spare digital input | Read | ||
| BI | 4 | Digital Input 4. Spare digital input | Spare digital input | Read | ||
| BO | 1 | Relay Output 1. Default: Primary Alarm Relay Output | Primary alarm relay | Read | ||
| BO | 2 | Relay Output 2. Default: Secondary Alarm Relay Output | Secondary alarm relay | Read | ||
| BO | 3 | Relay Output 3. Spare relay output | Spare relay | Read | ||
| BO | 4 | Relay Output 4. Spare relay output | Spare relay | Read | ||
| BVmin | 1 | Occupancy Status | Occupancy status | Write | ||
| BVmin | 2 | Emergency Purge. Maximum flow | Emergency purge (maximum flow) | Write | ||
| AVmin | 1 | AI-1 Setpoint. Fume Hood Face Velocity Setpoint | Face velocity setpoint | Write | ||
| AV | 2 | AI-2 Setpoint | Setpoint for AI 2 | Write | ||
| AV | 3 | AI-3 Setpoint | Setpoint for AI 3 | Write | ||
| AV | 4 | AI-4 Setpoint | Setpoint for AI 4 | Write | ||
| AV | 5 | TI-1 Setpoint. Ambient Temperature Setpoint | Ambient temperature setpoint | Write | ||
| AV | 6 | TI-2 Setpoint | Setpoint for thermistor input 2 | Write | ||
| AV | 7 | Air Change Rate based on Flow Input at AI-1 | Air change rate from the AI 1 flow | Write | ||
| AV | 8 | Air Change Rate based on Flow Input at AI-2 | Air change rate from the AI 2 flow | Write | ||
| AV | 9 | Air Change Rate based on Flow Input at AI-3 | Air change rate from the AI 3 flow | Write | ||
| AV | 10 | Air Change Rate based on Flow Input at AI-4 | Air change rate from the AI 4 flow | Write | ||
| AV | 11 | Total Air Changes (AI-3/4) | Total air changes from AI 3 and AI 4 | Write | ||
| AV | 12 | Alarm Relay 1 High Setpoint | Relay 1 alarm high setpoint | Write | ||
| AV | 13 | Alarm Relay 1 Low Setpoint | Relay 1 alarm low setpoint | Write | ||
| AV | 14 | Alarm Relay 2 High Setpoint | Relay 2 alarm high setpoint | Write | ||
| AV | 15 | Alarm Relay 2 Low Setpoint | Relay 2 alarm low setpoint | Write | ||
| AV | 16 | Alarm Relay 3 High Setpoint | Relay 3 alarm high setpoint | Write | ||
| AV | 17 | Alarm Relay 3 Low Setpoint | Relay 3 alarm low setpoint | Write | ||
| AV | 18 | Alarm Relay 4 High Setpoint | Relay 4 alarm high setpoint | Read | ||
| AV | 19 | Alarm Relay 4 Low Setpoint | Relay 4 alarm low setpoint | Read | ||
| AV | 20 | AI-1 Low Alarm Setpoint. Low Face Velocity Alarm | Face velocity low alarm limit | Write | ||
| AV | 21 | AI-1 Low Warning Setpoint. Low Face Velocity Warning | Face velocity low warning limit | Write | ||
| AV | 22 | AI-1 High Warning Setpoint. High Face Velocity Warning | Face velocity high warning limit | Write | ||
| AV | 23 | AI-1 High Alarm Setpoint. High Face Velocity Alarm | Face velocity high alarm limit | Write | ||
| AV | 24 | AI-2 Low Alarm Setpoint | AI 2 low alarm limit | Write | ||
| AV | 25 | AI-2 Low Warning Setpoint | AI 2 low warning limit | Write | ||
| AV | 26 | AI-2 High Warning Setpoint | AI 2 high warning limit | Write | ||
| AV | 27 | AI-2 High Alarm Setpoint | AI 2 high alarm limit | Write | ||
| AV | 28 | AI-3 Low Alarm Setpoint | AI 3 low alarm limit | Write | ||
| AV | 29 | AI-3 Low Warning Setpoint | AI 3 low warning limit | Write | ||
| AV | 30 | AI-3 High Warning Setpoint | AI 3 high warning limit | Write | ||
| AV | 31 | AI-3 High Alarm Setpoint | AI 3 high alarm limit | Write | ||
| AV | 32 | AI-4 Low Alarm Setpoint | AI 4 low alarm limit | Write | ||
| AV | 33 | AI-4 Low Warning Setpoint | AI 4 low warning limit | Write | ||
| AV | 34 | AI-4 High Warning Setpoint | AI 4 high warning limit | Write | ||
| AV | 35 | AI-4 High Alarm Setpoint | AI 4 high alarm limit | Write | ||
| AV | 36 | TI-1 Low Alarm Setpoint | TI 1 low alarm limit | Write | ||
| AV | 37 | TI-1 Low Warning Setpoint | TI 1 low warning limit | Write | ||
| AV | 38 | TI-1 High Warning Setpoint | TI 1 high warning limit | Write | ||
| AV | 39 | TI-1 High Alarm Setpoint | TI 1 high alarm limit | Write | ||
| AV | 40 | TI-2 Low Alarm Setpoint | TI 2 low alarm limit | Write | ||
| AV | 41 | TI-2 Low Warning Setpoint | TI 2 low warning limit | Write | ||
| AV | 42 | TI-2 High Warning Setpoint | TI 2 high warning limit | Write | ||
| AV | 43 | TI-2 High Alarm Setpoint | TI 2 high alarm limit | Write | ||
| AV | 44 | Writable Network Variable – Humidity | Humidity written by the BAS | Write | ||
| AV | 45 | Writable Network Variable – Temperature | Temperature written by the BAS | Write | ||
| AV | 46 | Writable Network Variable – Air Changes | Air changes written by the BAS | Write | ||
| AV | 47 | Writable Network Variable – Differential Pressure | Differential pressure written by the BAS | Write | ||
| AV | 48 | Device ID Offset (range: 0 to 4,194,000) | Offset added to form the device ID | Write | ||
| AV | 49 | Duct Air Flow based on AI-1 flow input | Duct airflow from the AI 1 flow input | Read | ||
| AV | 50 | Duct Air Flow based on AI-2 flow input | Duct airflow from the AI 2 flow input | Read | ||
| AV | 51 | Duct Air Flow based on AI-3 flow input (Supply Flow) | Supply airflow from AI 3 | Read | ||
| AV | 52 | Duct Air Flow based on AI-4 flow input (Exhaust Flow) | Exhaust airflow from AI 4 | Read | ||
| AV | 53 | Volumetric Offset (Supply Flow – Exhaust Flow) | Supply minus exhaust airflow | Read | ||
| AV | 54 | Volumetric Offset Setpoint | Volumetric offset setpoint | Write | ||
| AV | 55 | AO-1 Override Level | Override level for AO 1 | Write | ||
| AV | 56 | AO-2 Override Level | Override level for AO 2 | Write | ||
| AV | 57 | AO-3 Override Level | Override level for AO 3 | Write | ||
| AV | 58 | AO-4 Override Level | Override level for AO 4 | Write | ||
| AV | 59 | AI-1 Deadband Setting | Deadband for AI 1 | Write | ||
| AV | 60 | AI-2 Deadband Setting | Deadband for AI 2 | Write | ||
| AV | 61 | AI-3 Deadband Setting | Deadband for AI 3 | Write | ||
| AV | 62 | AI-4 Deadband Setting | Deadband for AI 4 | Write | ||
| AV | 63 | TI-1 Deadband Setting | Deadband for thermistor input 1 | Write | ||
| AV | 64 | TI-2 Deadband Setting | Deadband for thermistor input 2 | Write | ||
| MOmin | 1 | Fume Hood Operating Mode | Hood operating mode | Write | 1=occupied, 2=unoccupied, 3=decommisioned | |
| MO | 2 | Secondary Operating Mode | Secondary operating mode | Write | 1=occupied, 2=unoccupied, 3=decommisioned | |
| MOmin | 3 | Fume Hood Face Velocity Alarm Status | Face velocity alarm state | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 4 | Secondary Face Velocity Alarm Status | Secondary face velocity alarm state | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 5 | AI-3 Alarm Status | AI 3 alarm state | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 6 | AI-4 Alarm Status | AI 4 alarm state | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 7 | TI-1 Alarm Status | Thermistor input 1 alarm state | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 8 | TI-2 Alarm Status | Thermistor input 2 alarm state | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 9 | OS CTRL STATUS | Occupancy sensor control | Write | 1=disabled, 2=enabled |
No points match these filters.
Object ID lookup: Johnson Controls HMS1655 Fume Hood Controller point IDs by name
AI1Analog Input 1. Default: Fume Hood Face VelocityAI2Analog Input 2. Default: Sash Position Sensor)AI3Analog Input 3. Default: DP SensorAI4Analog Input 4. Default: Exhaust Air Flow VolumeAI5Thermistor Input 1. Default: Ambient TemperatureAI6Thermistor Input 2. Default: Duct TemperatureAO1Analog Output 1. Default: Exhaust Damper PositionAO2Analog Output 2 Spare control outputAO3Analog Output 3 Spare control outputAO4Analog Output 4 Spare control outputBI1Digital Input 1. Default: Fume Hood Sash SwitchBI2Digital Input 2. Default: spare digital inputBI3Digital Input 3. Spare digital inputBI4Digital Input 4. Spare digital inputBO1Relay Output 1. Default: Primary Alarm Relay OutputBO2Relay Output 2. Default: Secondary Alarm Relay OutputBO3Relay Output 3. Spare relay outputBO4Relay Output 4. Spare relay outputBV1Occupancy StatusBV2Emergency Purge. Maximum flowAV1AI-1 Setpoint. Fume Hood Face Velocity SetpointAV2AI-2 SetpointAV3AI-3 SetpointAV4AI-4 SetpointAV5TI-1 Setpoint. Ambient Temperature SetpointAV6TI-2 SetpointAV7Air Change Rate based on Flow Input at AI-1AV8Air Change Rate based on Flow Input at AI-2AV9Air Change Rate based on Flow Input at AI-3AV10Air Change Rate based on Flow Input at AI-4AV11Total Air Changes (AI-3/4)AV12Alarm Relay 1 High SetpointAV13Alarm Relay 1 Low SetpointAV14Alarm Relay 2 High SetpointAV15Alarm Relay 2 Low SetpointAV16Alarm Relay 3 High SetpointAV17Alarm Relay 3 Low SetpointAV18Alarm Relay 4 High SetpointAV19Alarm Relay 4 Low SetpointAV20AI-1 Low Alarm Setpoint. Low Face Velocity AlarmAV21AI-1 Low Warning Setpoint. Low Face Velocity WarningAV22AI-1 High Warning Setpoint. High Face Velocity WarningAV23AI-1 High Alarm Setpoint. High Face Velocity AlarmAV24AI-2 Low Alarm SetpointAV25AI-2 Low Warning SetpointAV26AI-2 High Warning SetpointAV27AI-2 High Alarm SetpointAV28AI-3 Low Alarm SetpointAV29AI-3 Low Warning SetpointAV30AI-3 High Warning SetpointAV31AI-3 High Alarm SetpointAV32AI-4 Low Alarm SetpointAV33AI-4 Low Warning SetpointAV34AI-4 High Warning SetpointAV35AI-4 High Alarm SetpointAV36TI-1 Low Alarm SetpointAV37TI-1 Low Warning SetpointAV38TI-1 High Warning SetpointAV39TI-1 High Alarm SetpointAV40TI-2 Low Alarm SetpointAV41TI-2 Low Warning SetpointAV42TI-2 High Warning SetpointAV43TI-2 High Alarm SetpointAV44Writable Network Variable – HumidityAV45Writable Network Variable – TemperatureAV46Writable Network Variable – Air ChangesAV47Writable Network Variable – Differential PressureAV48Device ID Offset (range: 0 to 4,194,000)AV49Duct Air Flow based on AI-1 flow inputAV50Duct Air Flow based on AI-2 flow inputAV51Duct Air Flow based on AI-3 flow input (Supply Flow)AV52Duct Air Flow based on AI-4 flow input (Exhaust Flow)AV53Volumetric Offset (Supply Flow – Exhaust Flow)AV54Volumetric Offset SetpointAV55AO-1 Override LevelAV56AO-2 Override LevelAV57AO-3 Override LevelAV58AO-4 Override LevelAV59AI-1 Deadband SettingAV60AI-2 Deadband SettingAV61AI-3 Deadband SettingAV62AI-4 Deadband SettingAV63TI-1 Deadband SettingAV64TI-2 Deadband SettingMO1Fume Hood Operating ModeMO2Secondary Operating ModeMO3Fume Hood Face Velocity Alarm StatusMO4Secondary Face Velocity Alarm StatusMO5AI-3 Alarm StatusMO6AI-4 Alarm StatusMO7TI-1 Alarm StatusMO8TI-2 Alarm StatusMO9OS CTRL STATUS
Integration notes
- The guide lists each object with a functional description, not an Object_Name string; that description is used as the point name here.
- Multistate objects are printed as MSO (multistate output) and are shown here as MO.
- Alarm Relay 4 High/Low Setpoint (AV 18/19) are marked N/A for read/write in the table; they are shown as read-only.
- What AI 1-4 measure depends on how each input is configured; the names give the factory default use.
- Units are not printed in the BACnet table.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HMS1655 Fume Hood Controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
How many BACnet points does the Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP) have?
This list has 93 BACnet objects: 6 analog inputs, 4 analog outputs, 64 analog values, 4 binary inputs, 4 binary outputs, 2 binary values, 9 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP) BACnet points are writable?
62 of the 93 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP) BACnet documentation?
The source is HMS1655 Fume Hood Controller Installation Guide (LIT-12013211), revision 2024-05, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/ZFysYMk8XVZk9JcDCr24Pw/content.
What are the minimum BACnet points to integrate the Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)?
Start with MO 1 Fume Hood Operating Mode (1 occupied, 2 unoccupied, 3 decommissioned); BV 2 Emergency Purge. Maximum flow (Emergency purge to maximum flow); AV 1 AI-1 Setpoint. Fume Hood Face Velocity Setpoint (Face velocity setpoint); BV 1 Occupancy Status (Occupancy status); AI 1 Analog Input 1. Default: Fume Hood Face Velocity (Measured face velocity); AI 2 Analog Input 2. Default: Sash Position Sensor) (Sash position); AO 1 Analog Output 1. Default: Exhaust Damper Position (Exhaust damper signal); MO 3 Fume Hood Face Velocity Alarm Status (1 normal, 2 warning, 3 alarm).
How do I enable BMS control of the Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)?
Fume Hood Operating Mode (MSO 1) is read/write: 1 = occupied, 2 = unoccupied, 3 = decommissioned. Emergency Purge (BV 2) drives maximum flow.
Can the BMS supply sensor values to the Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)?
AV 44-47 are writable network variables for humidity, temperature, air changes and differential pressure sent from the BAS.
How do I check these points on the real HMS1655 Fume Hood Controller (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: HMS1655 Fume Hood Controller Installation Guide · LIT-12013211 · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.