- ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
Fan coil unit controller · BACnet points list
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper) BACnet points list
Updated 6 November 2026
Application #3005 is one of the fan coil applications for the Johnson Controls ATC1500 (4 UI, 2 BI, 2 BO, 4 RO, 3 CO) Advanced Terminal Unit Controller, which connects over BACnet MS/TP (it can also run N2 or Modbus). It drives a two-pipe fan coil with on/off valve control, a variable-speed fan, a two-wire PWM heating option and an optional floating fresh-air damper with position output. Points cover unit enable, occupancy and mode commands, network setpoint and network sensor overrides, fan, valve and damper status, PID tuning, fault detection flags and the controller's network settings.
This page lists 238 BACnet objects for the Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper) — 158 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
- Equipment
- Fan coil unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 238 (158 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
Set the controller to BACnet MS/TP (FC Comm Mode Wired Field Bus) with an MS/TP address of 4-127, then enable the unit with Unit Enable Mode, drive occupancy through Occupancy Schedule and write Network Setpoint (Spt Source defaults to Network Input). Read unit status, effective occupancy, zone temperature and the fan state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 28002 | Unit Enable Mode | Unit on/off: 0=Shutdown, 1=Enable | Write |
| MV 28047 | Occupancy Schedule | Occupancy from the BAS schedule | Write |
| MV 28006 | System Mode Determination | Mode command (cool only, heat only, fan only...) | Write |
| AV 28069 | Network Setpoint | Zone setpoint written by the BAS, °C/°F | Write |
| MV 28000 | Unit Status | Heat, cool, fan only, satisfied or off | Read |
| MV 28048 | Effective Occupancy | Occupancy in effect | Read |
| AV 28088 | Operational Zone Temperature | Zone temperature in use, °C/°F | Read |
| AV 28075 | Fan Speed AO | Fan speed output, % | Read |
| MV 28080 | Condensate Alarm BI | Condensate alarm input: 0=Normal, 1=Alarm | Read |
Enable & remote start
Unit Enable Mode (Shutdown or Enable, default Enable) turns the unit off or on. Effective occupancy follows Occupancy Override first, then the bypass timer, Occupancy Schedule and the occupancy sensor. System Mode Determination is the writable mode command (cool only, heat only, fan only and others). The note says a network mode command takes priority over the summer-winter changeover input.
Sensors & values from the BMS
With Spt Source at Network Input (the default) the zone setpoint comes from Network Setpoint (default 22 °C). Network Override Zone Temperature, Network Override Outdoor Air Temperature and Network Override Indoor Air Quality are writable network inputs; a network CO2 value takes priority over the local sensor, and summer-winter setpoint compensation only works with a reliable network outdoor air temperature.
Network setup
- FC Comm Mode picks the field bus (Wired Field Bus for BACnet MS/TP, N2 or Modbus). MSTP Device Address is 4-127 and Device Object ID 0-4194302.
- FCB Baud Rate defaults to Auto; Operating Baud Rate shows the rate in use and Communication Status the MS/TP state.
- Units (MV 28018) selects IP or SI; the default is SI.
Watch out for
- BACnet IDs (AV 280xx / MV 280xx) are reused across the ATC applications but do not always mean the same point; map each application from its own list.
- Occupancy Override and Occupancy Schedule read Not Set after a reset until written again; with both Not Set and no occupancy sensor the unit falls back to Default Occupancy (Occupied unless changed).
- PID tuning, minimum on/off times and fault delays are commissioning values; don't write them cyclically.
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 28000 | Unit Status | UI label: Views Unit Status | Read | 0=Heat, 1=Cool, 2=Fan Only, 3=Balancing, 4=Satisfied, 5=Off | |
| MV | 28001 | Application Tuning Reset | Write | 0=False, 1=True, 2=Hold | ||
| MVmin | 28002 | Unit Enable Mode | Write | 0=Shutdown, 1=Enable | ||
| MV | 28003 | Occupied State | Read | 0=Heating, 1=Satisfied, 2=Cooling, 3=Supp Htg, 4=Temperature Unreliable | ||
| MV | 28004 | Unoccupied State | Read | 0=Not Unoccupied, 1=Temperature Unreliable, 2=Unocc Htg/Clg Check, 3=Unoccupied Off | ||
| MVmin | 28006 | System Mode Determination | Write | 0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, 4=Purge, 5=Auto | ||
| MV | 28007 | System Mode | Read | 0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, 4=Purge, 5=Auto | ||
| MV | 28008 | Heat Cool Mode Destination | Write | 0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, 4=Purge, 5=Auto | ||
| MV | 28009 | Effective HVAC Mode | UI label: Spaces Unit Status | Read | 0=Not In Use, 1=Off, 2=Heat, 3=Cool, 4=Fan Only | |
| MV | 28010 | Device Status | Read | 0=Main Download Req, 1=Code Download, 2=Class Code Download, 3=Subclass Download, 4=Instance Download, 5=Startup, 6=Operational, 7=Subclass Upload, 8=Instance Upload, ... (list cut short in the doc) | ||
| MV | 28011 | Firmware Status | Read | 0=Firmware Versions OK, 1=Firmware Versions Do Not Match the Package | ||
| AV | 28000 | N2 Address | Range 1 to 253 | Read | ||
| AV | 28001 | Modbus Address | Range 1 to 247 | Read | ||
| AV | 28002 | MSTP Device Address | Range 4 to 127 | Read | ||
| AV | 28003 | Device Object ID | Range 0 to 4194302 | Write | ||
| MV | 28012 | FC Comm Mode | Write | 0=Wired Field Bus, 1=Wireless Field Bus, 2=N2 Field Bus, 3=Modbus Field Bus, 4=Ethernet Field Bus, 255=Indeterminate FC Bus Mode | ||
| MV | 28013 | Communication Status | Read | 0=Not Configured, 1=Active, 2=Waiting For Poll For Master, 3=Not Received Token For Long, 4=Duplicate MAC Address, 5=Forcing BAUD, 6=Remote Trunk | ||
| MV | 28014 | FCB Baud Rate | Write | 0=Auto, 1=1200, 2=9600, 3=19200, 4=38400, 5=76800 | ||
| MV | 28015 | Operating Baud Rate | Read | 0=Auto, 1=1200, 2=9600, 3=19200, 4=38400, 5=76800 | ||
| MV | 28016 | BACnet Encoding Type | Write | 0=ISO 10646 (UCS-2), 1=ANSI X3.4 (US-ASCII), 2=Microsoft DBCS code page 932 (Japanese Shift JIS), 3=ISO 10646 (UTF-8) | ||
| MV | 28017 | Time Zone | Write | 1=(UTC+00:00) Monrovia, Reykjavik, 2=(UTC+00:00) Greenwich Mean Time : Dublin, Edinburgh, Lisbon, London, 3=(UTC+01:00) Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna, 4=(UTC+01:00) Belgrade, Bratislava, Budapest, Ljubljana, Prague, 5=(UTC+01:00) Brussels, Copenhagen, Madrid, Paris, 6=(UTC+01:00) Sarajevo, Skopje, Warsaw, Zagreb, 7=(UTC+01:00) West Central Africa, 8=(UTC+02:00) Athens, Bucharest, 9=(UTC+02:00) Chisinau, ... (list cut short in the doc) | ||
| MV | 28018 | Units | Write | 0=IP, 1=SI | ||
| MV | 28019 | Relearn System | Write | 0=False, 1=True | ||
| MV | 28020 | Provider Name | Write | 0=Automatic, 1=Manual | ||
| MV | 28027 | Heating Control Status | Read | 0=Normal, 1=Low, 2=Timing Low, 3=High, 4=Timing High, 5=Disabled, 6=Overridden | ||
| MV | 28028 | 2 Pipe Valve BO | UI label: HC-C | Read | 0=Off, 1=On, 2=Hold | |
| AV | 28005 | Heating Setpoint | Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| AV | 28006 | Htg Minimum On Time | Range 0 to 1200 seconds | s | Write | |
| AV | 28007 | Htg Minimum Off Time | Range 0 to 1200 seconds | s | Write | |
| AV | 28008 | Limited Max Heating Value | UI label: Limited Max Value; Range 10 to 100% | % | Write | |
| MV | 28029 | Heating Mode | Read | 0=Off, 1=Max, 2=Limited Max, 3=Hold, 4=Water Flush, 5=Control, 6=Failsoft | ||
| MV | 28030 | Heating Adaptive Tuning Enable | UI label: Htg Adaptive Tuning | Write | 0=Disable, 1=Enable | |
| MV | 28031 | Heating Manual Tuning | UI label: Htg Standard Tuning | Write | 0=Yes, 1=No | |
| AV | 28009 | Heat Prop Band | Range 1 to 200 | Write | ||
| AV | 28010 | Heat Integral Time | Range 0 to 1800 seconds | s | Write | |
| AV | 28011 | Heat Saturation Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28012 | Heat Process Range | Range 0 to 1800 | Write | ||
| AV | 28013 | Heat Time Constant | Range 1 to 1800 seconds | s | Write | |
| AV | 28014 | Heat Process Dead Time | Range 0 to 1800 seconds | s | Write | |
| AV | 28015 | Heat Period | Range 0 to 1800 seconds | s | Write | |
| MV | 28032 | Heating Process ID | UI label: Htg Process ID | Write | 0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, 4=CHWS-T HEX, 5=CHWS-T Mixing, 6=CWS-T, 7=DA-H, 8=DA-T, ... (list cut short in the doc) | |
| MV | 28033 | Two Position Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| AV | 28016 | Control Band | Range 0 to 5 delta °C (0 to 5 delta °F) | delta °C/°F | Write | |
| AV | 28018 | Cooling Setpoint | Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| MV | 28034 | Cooling Control Status | Read | 0=Normal, 1=Low, 2=Timing Low, 3=High, 4=Timing High, 5=Disabled, 6=Overridden | ||
| AV | 28019 | Clg Minimum On Time | Range 0 to 1200 seconds | s | Write | |
| AV | 28020 | Clg Minimum Off Time | Range 0 to 1200 seconds | s | Write | |
| AV | 28021 | Limited Max Cooling Value | UI label: Limited Max Value; Range 10 to 100% | % | Write | |
| MV | 28036 | Cooling Mode | Read | 0=Off, 1=Max, 2=Limited Max, 3=Hold, 4=Water Flush, 5=Control, 6=Failsoft | ||
| MV | 28037 | Cooling Adaptive Tuning Enable | UI label: Clg Adaptive Tuning | Write | 0=Disable, 1=Enable | |
| MV | 28038 | Cooling Manual Tuning | UI label: Clg Standard Tuning | Write | 0=Yes, 1=No | |
| AV | 28022 | Cool Prop Band | UI label: Clg Proportional Band; Range 1 to 200 | Write | ||
| AV | 28023 | Cool Integral Time | UI label: Clg Integral Time; Range 0 to 1800 seconds | s | Write | |
| AV | 28024 | Cool Saturation Time | UI label: Clg Saturation Time; Range 1 to 1800 seconds | s | Write | |
| AV | 28025 | Cool Process Range | UI label: Clg Process Range; Range 0 to 1800 | Write | ||
| AV | 28026 | Cool Time Constant | UI label: Clg Time Constant; Range 1 to 1800 seconds | s | Write | |
| AV | 28027 | Cool Process Dead Time | UI label: Clg Process Dead Time; Range 1 to 1800 seconds | s | Write | |
| AV | 28028 | Cool Period | UI label: Clg Period; Range 0 to 1800 seconds | s | Write | |
| MV | 28039 | Cool Process ID | UI label: Clg Process ID | Write | 0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, 4=CHWS-T HEX, 5=CHWS-T Mixing, 6=CWS-T, 7=DA-H, 8=DA-T, ... (list cut short in the doc) | |
| MV | 28040 | Damper State | UI label: State | Read | 0=Off, 1=On, 2=Max | |
| AV | 28029 | Damper Maximum Position | UI label: Damper Max Position; Range 0 to 100% | % | Write | |
| AV | 28030 | Damper Minimum Position | UI label: OA Damper Minimum Position; Range 0 to 100% | % | Write | |
| AV | 28031 | Damper Percent Cmd | Range 0 to 100% | % | Read | |
| MV | 28041 | Damper OpenClose | Read | 0=Close, 1=Open | ||
| AV | 28032 | CO2 Prop Band | Range 0 to 10000 ppm | ppm | Write | |
| AV | 28033 | OA Damper PAO | Range 0 to 100% | % | Read | |
| MV | 28043 | Damper Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| AV | 28034 | Return CO2 Sensor Offset | Range -2000 to 2000 ppm | ppm | Write | |
| MV | 28045 | IAQ | UI label: State | Read | 0=Unreliable, 1=Low Priority, 2=Medium Priority, 3=High Priority, 4=Timed Override, 5=Input Not Installed | |
| MV | 28046 | Occupancy Override | Write | 0=Occupied, 1=UnOccupied, 2=Bypass, 3=Standby, 4=Not Set | ||
| MVmin | 28047 | Occupancy Schedule | Write | 0=Occupied, 1=UnOccupied, 2=Standby, 3=Not Set | ||
| MVmin | 28048 | Effective Occupancy | Read | 0=Occupied, 1=UnOccupied, 2=Bypass, 3=Standby | ||
| AV | 28035 | Bypass Time | Range 0 to 7200 seconds | s | Write | |
| AV | 28036 | Off Delay | UI label: Delay; Range 0 to 600 seconds | s | Write | |
| MV | 28049 | Temporary Occupancy | UI label: Spaces Occupancy | Write | 0=Normal, 1=Trigger | |
| MV | 28050 | FDD Enable | Write | 0=Disable, 1=Enable | ||
| AV | 28037 | Start Delay | Range 0 to 86400 seconds | s | Write | |
| AV | 28038 | Insufficient Htg Cap Sat Delay | Range 0 to 86400 seconds | s | Write | |
| AV | 28039 | Insufficient Htg Cap Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28040 | Insufficient Clg Cap Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28041 | Low Zone Temp Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28042 | High Zone Temp Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28043 | ZN Spt Out Of Comfort Lim Min T Spt | Range -20 to 40°C (-4 to 104°F) | °C/°F | Write | |
| AV | 28044 | ZN Spt Out Of Comfort Lim Max T Spt | Range -20 to 40°C (-4 to 104°F) | °C/°F | Write | |
| AV | 28045 | Changeover Setting Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28046 | Setpoint Compensation Winter Max Diff | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28047 | Setpoint Compensation Summer Max Diff | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28048 | Insufficient Clg Cap Sat Delay | Range 0 to 86400 seconds | s | Write | |
| MV | 28051 | FDD | UI label: State | Read | 0=Disable, 1=Enable | |
| AV | 28049 | Simultaneous HtgClg Zone Max Error | Range 0 to 100 delta °C (0 to 100 delta °F) | delta °C/°F | Write | |
| MV | 28052 | Window Open While Occupied Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28053 | Window Open While Unoccupied Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28054 | Insufficient Cooling Capacity Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28055 | Insufficient Heating Capacity Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28056 | Zone Spt Outside Comfort Limits Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28057 | High Zone Temp Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28058 | Low Zone Temp Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28059 | Incorrect Changeover Setting Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28060 | Incorrect Setpoint Compensation Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28061 | Simultaneous Htg and Clg Fault | Read | 0=Normal, 1=Alarm | ||
| AV | 28050 | Window Open In Occ In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28051 | Window Open In Unocc In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28052 | Low Zone Temp In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28053 | High Zone Temp In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28054 | Changeover Setting In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28055 | Simultaneous Htg Clg In Fault Time | Range 0 to 86400 seconds | s | Write | |
| MV | 28062 | Window Open In Occ Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28063 | Window Open In Unocc Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28064 | Insufficient Htg Cap Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28065 | Insufficient Clg Cap Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28066 | Low Zone Temp Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28067 | High Zone Temp Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28068 | Changeover Setting Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28069 | Setpoint Compensation Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28070 | ZN Spt Out Of Comfort Lim Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28071 | Simultaneous Htg Clg Fault Enable | Write | 0=Disable, 1=Enable | ||
| AV | 28056 | ecoClgSetpoint | Range 20 to 30°C (68 to 86°F) | °C/°F | Write | |
| MV | 28072 | Energy Indicator | UI label: Energy Indication | Read | 0=Off, 1=Red, 2=Green | |
| AV | 28057 | ecoHtgSetpoint | Range 15 to 25°C (59 to 77°F) | °C/°F | Write | |
| MV | 28073 | Energy Indication Enable | UI label: Enable | Write | 0=Disable, 1=Enable | |
| MV | 28074 | Energy Indicator Reset | Write | 0=False, 1=True | ||
| AV | 28058 | ecoHtgSetpoint Diff | UI label: ecoHtgSptDiff; Range 0 to 10 delta °C (0 to 10 delta °F) | delta °C/°F | Write | |
| AV | 28059 | ecoClgSetpoint Diff | UI label: ecoClgSptDiff; Range 0 to 10 delta °C (0 to 10 delta °F) | delta °C/°F | Write | |
| AV | 28060 | CO2 Setpoint | Range 0 to 10000 ppm | ppm | Write | |
| AV | 28061 | Unocc Cooling Setpoint | Range 15 to 30°C (59 to 86°F) | °C/°F | Write | |
| AV | 28062 | Unocc Heating Setpoint | Range 10 to 25°C (50 to 77°F) | °C/°F | Write | |
| AV | 28063 | Standby Cooling Setpoint | Range 10 to 30°C (50 to 86°F) | °C/°F | Write | |
| AV | 28064 | Standby Heating Setpoint | Range 10 to 30°C (50 to 86°F) | °C/°F | Write | |
| AV | 28065 | Freeze Stat Setpoint | Range -20 to 10°C (-4 to 50°F) | °C/°F | Write | |
| AV | 28066 | Frost Protect Differential | UI label: Differential; Range 0 to 15 delta °C (0 to 27 delta °F) | delta °C/°F | Write | |
| AV | 28067 | Effective Cooling Setpoint | UI label: Eff Clg Spt; Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28068 | Effective Heating Setpoint | UI label: Eff Htg Spt; Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AVmin | 28069 | Network Setpoint | UI label: NSP&P Setpoint; Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Write | |
| AV | 28070 | Deadband | Range 0 to 10 delta °C (0 to 18 delta °F) | delta °C/°F | Write | |
| MV | 28075 | Spt Source | UI label: Zone Setpoint Source | Write | 0=Network Input, 1=Sensor Input, 2=Multiple Inputs | |
| MV | 29990 | Space Vote | Read | 0=Urgent Heat, 1=Heat, 2=Satisfied, 3=Cool, 4=Urgent Cool | ||
| AV | 28071 | Low Range | Range 0 to 100% | % | Write | |
| AV | 28072 | High Range | Range 0 to 100% | % | Write | |
| AV | 28073 | Low Range Diff | Range 0 to 100% | % | Write | |
| AV | 28074 | High Range Diff | Range 0 to 100% | % | Write | |
| MV | 28077 | Fan BO | Read | 0=Off, 1=On, 2=Hold | ||
| AVmin | 28075 | Fan Speed AO | Range 0 to 100% | % | Read | |
| AV | 28076 | Percent Cmd | Range 0 to 100% | % | Read | |
| MV | 28078 | Fan Mode | UI label: Mode | Read | 0=Off, 1=On, 2=Max | |
| AV | 28077 | Minimum Speed | Range 0 to 100% | % | Write | |
| AV | 28078 | Max Speed Cooling | Range 0 to 100% | % | Write | |
| AV | 28079 | Max Speed Heating | Range 0 to 100% | % | Write | |
| AV | 28080 | Supply Fan Low | Range 0 to 100% | % | Write | |
| AV | 28081 | Supply Fan Medium | Range 0 to 100% | % | Write | |
| AV | 28082 | Fan Min Out Value | Range 0 to 100% | % | Write | |
| MV | 28079 | Fan BO Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| AV | 28083 | Fan Max Out Value | Range 0 to 100% | % | Write | |
| AV | 28084 | Network Override Indoor Air Quality | Range 0 to 10000 ppm | ppm | Write | |
| AV | 28085 | Operational Indoor Air Quality | UI label: Present Value; Range 0 to 10000 ppm | ppm | Read | |
| AV | 28086 | Network Override Outdoor Air Temperature | Range -46 to 94°C (-50.8 to 201.2°F) | °C/°F | Write | |
| AV | 28087 | Network Override Zone Temperature | Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Write | |
| AVmin | 28088 | Operational Zone Temperature | UI label: Present Value; Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Read | |
| AV | 28089 | Operational Outdoor Air Temperature | UI label: Present Value; Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Read | |
| MVmin | 28080 | Condensate Alarm BI | Read | 0=Normal, 1=Alarm, 2=Hold | ||
| MV | 28081 | SummerWinter BI | Read | 0=Summer, 1=Winter, 2=Hold | ||
| MV | 28082 | Window Status BI | Read | 0=Close, 1=Open, 2=Hold | ||
| MV | 28083 | Occupancy Sensor BI | Read | 0=Occupied, 1=Unoccupied, 2=Hold | ||
| MV | 28084 | Occupancy Sensor Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28085 | Window Contact Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28086 | Dew Point Contact Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28087 | Summer Winter Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28088 | Safety Tstat BI | Read | 0=Normal, 1=Alarm, 2=Hold | ||
| MV | 28089 | Safety Tstat Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| AV | 28090 | Effective Cooling Shift | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28091 | Effective Heating Shift | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28092 | Winter Setpoint | Range -40 to 20°C (-40 to 68°F) | °C/°F | Write | |
| AV | 28093 | Summer Setpoint | Range 10 to 60°C (50 to 140°F) | °C/°F | Write | |
| AV | 28094 | Summer Change Limit | Range -10 to 10 delta °C (-18 to 18 delta °F) | delta °C/°F | Write | |
| AV | 28095 | Winter Change Limit | Range -10 to 10 delta °C (-18 to 18 delta °F) | delta °C/°F | Write | |
| AV | 28096 | Summer Gain | Range 0 to 10 | Write | ||
| AV | 28097 | Winter Gain | Range -10 to 10 | Write | ||
| MV | 28090 | SummerWinter | Read | 0=Summer, 1=Winter | ||
| MV | 28091 | Start Commission | Write | 0=Normal, 1=Trigger | ||
| MV | 28092 | HC-C Ovrd | Write | 0=Off, 1=On | ||
| MV | 28093 | SF-C Ovrd | Write | 0=Off, 1=On | ||
| AV | 28098 | HC-O Ovrd | Range 0 to 100% | % | Write | |
| AV | 28099 | SF-O Ovrd | Range 0 to 100% | % | Write | |
| MV | 28094 | OAD-C Ovrd | Write | 0=Off, 1=On | ||
| MV | 28095 | SFL-C Ovrd | Write | 0=Off, 1=On | ||
| MV | 28096 | SFM-C Ovrd | Write | 0=Off, 1=On | ||
| MV | 28097 | SFH-C Ovrd | Write | 0=Off, 1=On | ||
| AV | 28100 | OAD-O Ovrd | Range 0 to 100% | % | Write | |
| AV | 28101 | SuppHtg-O Ovrd | Range 0 to 100% | % | Write | |
| MV | 28098 | Fan Status | Read | 0=Off, 1=On | ||
| AV | 28102 | Zone Temperature | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28103 | CO2 | UI label: Carbon Dioxide; Range 0 to 10000 ppm | ppm | Read | |
| MV | 28099 | Zone Occupancy Request | UI label: Occupancy Request | Read | 0=Occupied, 1=UnOccupied, 2=Not Set | |
| AV | 28104 | Warmer/Cooler Adjust | UI label: Setpoint Request; Range -100 to 100 delta °C (-100 to 100 delta °F) | delta °C/°F | Read | |
| AV | 28105 | Setpoint Offset | UI label: Active Fan Status; Range 0.01 to 10 delta °C (0.02 to 18 delta °F) | delta °C/°F | Write | |
| MV | 28100 | Indoor Air Quality Sensor Installed | UI label: Carbon Dioxide | Read | 0=Reliable, 1=No Input, 2=Out of range high, 3=Out of range low, 4=Open, 5=Shorted, 6=No Output, 7=Unreliable, 8=Process Error, ... (list cut short in the doc) | |
| MV | 28101 | Occupancy Status Display | Read | 0=Occupied, 1=UnOccupied, 2=Standby, 3=Not Set | ||
| MV | 28102 | Fan Speed Request | Read | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High | ||
| AV | 28106 | Active Setpoint | UI label: NSP&P Active Setpoint; Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Write | |
| AV | 28107 | Network/Zone Sensor Setpoint | UI label: NSP&P Setpoint; Range 10 to 40°C (50 to 104°F) | °C/°F | Read | |
| AV | 28108 | Zone Temperature Setpoint Alternate | UI label: NSP&P Active Setpoint; Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Read | |
| AV | 28109 | Heating Percent Cmd | Range 0 to 100% | % | Read | |
| AV | 28122 | Cooling Percent Cmd | Range 0 to 100% | % | Read | |
| MV | 28115 | Damper | UI label: Floating Damper | Read | 0=On/Off, 1=Floating | |
| MV | 28116 | Fan Type | Read | 0=Constant Volume Fan, 1=Fixed Variable Fan | ||
| MV | 28117 | Valve | UI label: Valve Type | Read | 0=Staged, 1=Proportional | |
| AV | 28133 | Application Details | UI label: App SW Version; Range 0 to 1000000000 | Read | ||
| AV | 28134 | Application Name | UI label: App Name; Range 0 to 10000 | Read | ||
| MV | 28118 | Fan Cycling | UI label: FAN-CYCLE | Write | 0=No, 1=Yes | |
| AV | 28135 | Fan On Threshold | Range 0 to 100% | % | Write | |
| AV | 28136 | Fan Off Threshold | Range 0 to 100% | % | Write | |
| AV | 28137 | Heating Purge Duration | UI label: HTG-PURGETIME; Range 0 to 1800 seconds | s | Write | |
| MV | 28119 | Fan State | UI label: FAN-STATE | Read | 0=Off, 1=On | |
| MV | 28120 | Off During Unoccupied | Write | 0=False, 1=True, 2=Hold | ||
| MV | 28121 | Cooling Fan Required | Write | 0=No, 1=Yes | ||
| MV | 28122 | Heating Fan Required | Write | 0=No, 1=Yes | ||
| MV | 28123 | Fan Speed Override | Write | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High | ||
| MV | 28124 | Eff Fan Speed Cmd | UI label: Effective Fan Override | Read | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High | |
| AV | 28138 | Electric Heat DAO | UI label: SUPHTG-O; Range 0 to 100% | % | Read | |
| AV | 28139 | Aux Heat Setpoint | UI label: Setpoint; Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| MV | 28125 | Reheat Control Status | UI label: Control Status | Read | 0=Normal, 1=Low, 2=Timing Low, 3=High, 4=Timing High, 5=Disabled, 6=Overridden | |
| AV | 28140 | Reheat Percent Cmd | UI label: Percent Cmd; Range 0 to 100% | % | Read | |
| AV | 28141 | Aux Heat Process Variable | UI label: Process Variable; Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| MV | 28126 | Reheat IsAvailable | UI label: Supp Heating isAvailable | Write | 0=No, 1=Yes | |
| AV | 28142 | Electric Heat Cycle Time | UI label: SUPHTG-O; Range 0 to 1200 seconds | s | Write | |
| AV | 28143 | High Threshold | UI label: SUPHTG-O; Range 0 to 100% | % | Write | |
| AV | 28144 | Low Threshold | UI label: SUPHTG-O; Range 0 to 100% | % | Write | |
| MV | 28127 | Reheat Mode | UI label: Mode | Read | 0=Off, 1=Max, 2=Limited Max, 3=Hold, 4=Water Flush, 5=Control, 6=Failsoft | |
| MV | 28128 | Aux Heat Adaptive Tuning Enable | UI label: Adaptive Tuning | Write | 0=False, 1=True, 2=Hold | |
| MV | 28129 | Aux Heat Manual Tuning | UI label: Standard Tuning | Write | 0=Yes, 1=No | |
| MV | 28130 | Aux Heat Process ID | UI label: Process ID | Write | 0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, 4=CHWS-T HEX, 5=CHWS-T Mixing, 6=CWS-T, 7=DA-H, 8=DA-T, ... (list cut short in the doc) | |
| AV | 28145 | Aux Heat Prop Band | UI label: Heat Prop Band; Range 1 to 200 | Write | ||
| AV | 28146 | Aux Heat Integral Time | UI label: Heat Integral Time; Range 0 to 1800 seconds | s | Write | |
| AV | 28147 | Aux Heat Saturation Time | UI label: Heat Saturation Time; Range 1 to 1800 seconds | s | Write | |
| AV | 28148 | Aux Heat Process Range | UI label: Heat Process Range; Range 0 to 1800 | Write | ||
| AV | 28149 | Aux Heat Time Constant | UI label: Heat Time Constant; Range 1 to 1800 seconds | s | Write | |
| AV | 28150 | Aux Heat Process Dead Time | UI label: Heat Process Dead Time; Range 1 to 1800 seconds | s | Write | |
| AV | 28151 | Aux Heat Period | UI label: Heat Period; Range 0 to 1800 seconds | s | Write | |
| AV | 28152 | Damper Stroke Time | Range 1 to 240 seconds | s | Write |
No points match these filters.
Object ID lookup: Johnson Controls ATC1500 App #3005 point IDs by name
MV28000Unit StatusMV28001Application Tuning ResetMV28002Unit Enable ModeMV28003Occupied StateMV28004Unoccupied StateMV28006System Mode DeterminationMV28007System ModeMV28008Heat Cool Mode DestinationMV28009Effective HVAC ModeMV28010Device StatusMV28011Firmware StatusAV28000N2 AddressAV28001Modbus AddressAV28002MSTP Device AddressAV28003Device Object IDMV28012FC Comm ModeMV28013Communication StatusMV28014FCB Baud RateMV28015Operating Baud RateMV28016BACnet Encoding TypeMV28017Time ZoneMV28018UnitsMV28019Relearn SystemMV28020Provider NameMV28027Heating Control StatusMV280282 Pipe Valve BOAV28005Heating SetpointAV28006Htg Minimum On TimeAV28007Htg Minimum Off TimeAV28008Limited Max Heating ValueMV28029Heating ModeMV28030Heating Adaptive Tuning EnableMV28031Heating Manual TuningAV28009Heat Prop BandAV28010Heat Integral TimeAV28011Heat Saturation TimeAV28012Heat Process RangeAV28013Heat Time ConstantAV28014Heat Process Dead TimeAV28015Heat PeriodMV28032Heating Process IDMV28033Two Position PolarityAV28016Control BandAV28018Cooling SetpointMV28034Cooling Control StatusAV28019Clg Minimum On TimeAV28020Clg Minimum Off TimeAV28021Limited Max Cooling ValueMV28036Cooling ModeMV28037Cooling Adaptive Tuning EnableMV28038Cooling Manual TuningAV28022Cool Prop BandAV28023Cool Integral TimeAV28024Cool Saturation TimeAV28025Cool Process RangeAV28026Cool Time ConstantAV28027Cool Process Dead TimeAV28028Cool PeriodMV28039Cool Process IDMV28040Damper StateAV28029Damper Maximum PositionAV28030Damper Minimum PositionAV28031Damper Percent CmdMV28041Damper OpenCloseAV28032CO2 Prop BandAV28033OA Damper PAOMV28043Damper PolarityAV28034Return CO2 Sensor OffsetMV28045IAQMV28046Occupancy OverrideMV28047Occupancy ScheduleMV28048Effective OccupancyAV28035Bypass TimeAV28036Off DelayMV28049Temporary OccupancyMV28050FDD EnableAV28037Start DelayAV28038Insufficient Htg Cap Sat DelayAV28039Insufficient Htg Cap Zone Max ErrorAV28040Insufficient Clg Cap Zone Max ErrorAV28041Low Zone Temp Zone Max ErrorAV28042High Zone Temp Zone Max ErrorAV28043ZN Spt Out Of Comfort Lim Min T SptAV28044ZN Spt Out Of Comfort Lim Max T SptAV28045Changeover Setting Zone Max ErrorAV28046Setpoint Compensation Winter Max DiffAV28047Setpoint Compensation Summer Max DiffAV28048Insufficient Clg Cap Sat DelayMV28051FDDAV28049Simultaneous HtgClg Zone Max ErrorMV28052Window Open While Occupied FaultMV28053Window Open While Unoccupied FaultMV28054Insufficient Cooling Capacity FaultMV28055Insufficient Heating Capacity FaultMV28056Zone Spt Outside Comfort Limits FaultMV28057High Zone Temp FaultMV28058Low Zone Temp FaultMV28059Incorrect Changeover Setting FaultMV28060Incorrect Setpoint Compensation FaultMV28061Simultaneous Htg and Clg FaultAV28050Window Open In Occ In Fault TimeAV28051Window Open In Unocc In Fault TimeAV28052Low Zone Temp In Fault TimeAV28053High Zone Temp In Fault TimeAV28054Changeover Setting In Fault TimeAV28055Simultaneous Htg Clg In Fault TimeMV28062Window Open In Occ Fault EnableMV28063Window Open In Unocc Fault EnableMV28064Insufficient Htg Cap Fault EnableMV28065Insufficient Clg Cap Fault EnableMV28066Low Zone Temp Fault EnableMV28067High Zone Temp Fault EnableMV28068Changeover Setting Fault EnableMV28069Setpoint Compensation Fault EnableMV28070ZN Spt Out Of Comfort Lim Fault EnableMV28071Simultaneous Htg Clg Fault EnableAV28056ecoClgSetpointMV28072Energy IndicatorAV28057ecoHtgSetpointMV28073Energy Indication EnableMV28074Energy Indicator ResetAV28058ecoHtgSetpoint DiffAV28059ecoClgSetpoint DiffAV28060CO2 SetpointAV28061Unocc Cooling SetpointAV28062Unocc Heating SetpointAV28063Standby Cooling SetpointAV28064Standby Heating SetpointAV28065Freeze Stat SetpointAV28066Frost Protect DifferentialAV28067Effective Cooling SetpointAV28068Effective Heating SetpointAV28069Network SetpointAV28070DeadbandMV28075Spt SourceMV29990Space VoteAV28071Low RangeAV28072High RangeAV28073Low Range DiffAV28074High Range DiffMV28077Fan BOAV28075Fan Speed AOAV28076Percent CmdMV28078Fan ModeAV28077Minimum SpeedAV28078Max Speed CoolingAV28079Max Speed HeatingAV28080Supply Fan LowAV28081Supply Fan MediumAV28082Fan Min Out ValueMV28079Fan BO PolarityAV28083Fan Max Out ValueAV28084Network Override Indoor Air QualityAV28085Operational Indoor Air QualityAV28086Network Override Outdoor Air TemperatureAV28087Network Override Zone TemperatureAV28088Operational Zone TemperatureAV28089Operational Outdoor Air TemperatureMV28080Condensate Alarm BIMV28081SummerWinter BIMV28082Window Status BIMV28083Occupancy Sensor BIMV28084Occupancy Sensor PolarityMV28085Window Contact PolarityMV28086Dew Point Contact PolarityMV28087Summer Winter PolarityMV28088Safety Tstat BIMV28089Safety Tstat PolarityAV28090Effective Cooling ShiftAV28091Effective Heating ShiftAV28092Winter SetpointAV28093Summer SetpointAV28094Summer Change LimitAV28095Winter Change LimitAV28096Summer GainAV28097Winter GainMV28090SummerWinterMV28091Start CommissionMV28092HC-C OvrdMV28093SF-C OvrdAV28098HC-O OvrdAV28099SF-O OvrdMV28094OAD-C OvrdMV28095SFL-C OvrdMV28096SFM-C OvrdMV28097SFH-C OvrdAV28100OAD-O OvrdAV28101SuppHtg-O OvrdMV28098Fan StatusAV28102Zone TemperatureAV28103CO2MV28099Zone Occupancy RequestAV28104Warmer/Cooler AdjustAV28105Setpoint OffsetMV28100Indoor Air Quality Sensor InstalledMV28101Occupancy Status DisplayMV28102Fan Speed RequestAV28106Active SetpointAV28107Network/Zone Sensor SetpointAV28108Zone Temperature Setpoint AlternateAV28109Heating Percent CmdAV28122Cooling Percent CmdMV28115DamperMV28116Fan TypeMV28117ValveAV28133Application DetailsAV28134Application NameMV28118Fan CyclingAV28135Fan On ThresholdAV28136Fan Off ThresholdAV28137Heating Purge DurationMV28119Fan StateMV28120Off During UnoccupiedMV28121Cooling Fan RequiredMV28122Heating Fan RequiredMV28123Fan Speed OverrideMV28124Eff Fan Speed CmdAV28138Electric Heat DAOAV28139Aux Heat SetpointMV28125Reheat Control StatusAV28140Reheat Percent CmdAV28141Aux Heat Process VariableMV28126Reheat IsAvailableAV28142Electric Heat Cycle TimeAV28143High ThresholdAV28144Low ThresholdMV28127Reheat ModeMV28128Aux Heat Adaptive Tuning EnableMV28129Aux Heat Manual TuningMV28130Aux Heat Process IDAV28145Aux Heat Prop BandAV28146Aux Heat Integral TimeAV28147Aux Heat Saturation TimeAV28148Aux Heat Process RangeAV28149Aux Heat Time ConstantAV28150Aux Heat Process Dead TimeAV28151Aux Heat PeriodAV28152Damper Stroke Time
Integration notes
- Objects from the BACnet and N2 bus points table on pages 49-67 of the application note (LIT-12013084).
- All objects are analog values (AV) or multistate values (MV); physical inputs and outputs show up as MV/AV status points. Access W means the table marks the object Writeable; multistate states keep the 0-based numbers printed in the note.
- For 6 multistate objects the note prints only the first states and then '...'; the full sets are in Metasys System Enumeration Sets (LIT-12011361).
- This note prints some names with a second, user-interface label in brackets; the first name is used here and the bracketed label is in the description.
- Application #3006 prints the same table except for the damper output: this one has AV 28033 OA Damper PAO, MV 28043 Damper Polarity; #3006 has MV 28042 OA Damper BO, MV 28044 Damper Polarity.
- Units come from the range column: temperatures follow the controller Units setting (MV 28018, default SI so °C).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
How many BACnet points does the Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper) have?
This list has 238 BACnet objects: 129 analog values, 109 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper) BACnet points are writable?
158 of the 238 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper) BACnet documentation?
The source is Advanced Terminal Unit Controller Application Note - Application #3005 (LIT-12013084), revision April 2023, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/uKbA2GcR_qERAy9CPF7LNg/content.
What are the minimum BACnet points to integrate the Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)?
Start with MV 28002 Unit Enable Mode (Unit on/off: 0=Shutdown, 1=Enable); MV 28047 Occupancy Schedule (Occupancy from the BAS schedule); MV 28006 System Mode Determination (Mode command (cool only, heat only, fan only...)); AV 28069 Network Setpoint (Zone setpoint written by the BAS, °C/°F); MV 28000 Unit Status (Heat, cool, fan only, satisfied or off); MV 28048 Effective Occupancy (Occupancy in effect); AV 28088 Operational Zone Temperature (Zone temperature in use, °C/°F); AV 28075 Fan Speed AO (Fan speed output, %); MV 28080 Condensate Alarm BI (Condensate alarm input: 0=Normal, 1=Alarm).
How do I enable BMS control of the Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)?
Unit Enable Mode (Shutdown or Enable, default Enable) turns the unit off or on. Effective occupancy follows Occupancy Override first, then the bypass timer, Occupancy Schedule and the occupancy sensor. System Mode Determination is the writable mode command (cool only, heat only, fan only and others). The note says a network mode command takes priority over the summer-winter changeover input.
Can the BMS supply sensor values to the Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)?
With Spt Source at Network Input (the default) the zone setpoint comes from Network Setpoint (default 22 °C). Network Override Zone Temperature, Network Override Outdoor Air Temperature and Network Override Indoor Air Quality are writable network inputs; a network CO2 value takes priority over the local sensor, and summer-winter setpoint compensation only works with a reliable network outdoor air temperature.
How do I check these points on the real ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: Advanced Terminal Unit Controller Application Note - Application #3005 · LIT-12013084 · rev. April 2023. Object names, instances and units are reproduced as published; descriptions are our own.