- PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pump controller · BACnet points list
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820) BACnet points list
Updated 6 November 2026
The PEAK 18 is a factory-programmed SMART Equipment controller (BTL-listed B-ASC) that reads the heat pump's Aurora (ABC) board over Modbus and serves the data as BACnet MS/TP objects with IDs 5001 and up. It covers occupancy and setpoints, network override inputs for space temperature, humidity and IAQ, thermostat and stage outputs, Aurora fault code, lockout and pressure switches, plus device and network settings.
This page lists 153 BACnet objects for the Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820) — 57 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
- Equipment
- Water-source heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 153 (57 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Give the controller a unique MS/TP address (4-127) from the local display or MAP Gateway; baud defaults to auto. Command occupancy with MV 5059 Manual Occupancy Mode, write the occupied cooling and heating setpoints, and use the network override inputs if the BMS supplies space temperature. Read operational occupancy and space temperature, the Aurora stage outputs, lockout and fault code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 5026 | Mode | Unit mode: Shutdown or Enable | Write |
| MV 5059 | Manual Occupancy Mode | Occupancy override from the BMS | Write |
| AV 5053 | Occupied Cooling Setpoint | Occupied cooling setpoint | Write |
| AV 5054 | Occupied Heating Setpoint | Occupied heating setpoint | Write |
| BV 5096 | ABC-1 Reset Faults | Reset Aurora board faults | Write |
| MV 5030 | Operational Occupancy | Occupancy in effect | Read |
| AV 5032 | Operational Space Temperature | Space temperature the unit controls to | Read |
| BV 5079 | ABC-1 CC - Compressor Contactor Enable | Compressor contactor output | Read |
| BV 5078 | ABC-1 Unit Lockout Status | Unit locked out | Read |
| MV 5076 | ABC-1 Active Fault Code | Active Aurora fault | Read |
Enable & remote start
The sequence runs when the Mode point is set to Enable. Occupancy follows the local schedule and can be overridden with Manual Occupancy Mode.
Heartbeat & communication loss
A value written to Network Override Space Temperature becomes the control input and restarts a 15-minute timeout; if the BMS stops writing, the input is treated as unreliable and ignored.
Sensors & values from the BMS
AV 5034 Network Override Space Temperature, AV 5042 Network Override Zone Humidity, AV 5039 Network Override Indoor Air Quality and AV 5045 Network Override Space Setpoint Offset accept BMS values; the matching Source objects show which input is in use.
Network setup
- Valid MS/TP addresses are 4-127; set the address from the local display or MAP Gateway.
- Baud defaults to Auto (follows the trunk); 9600, 19200 and 38400 can be set manually.
- BACnet MS/TP, N2 or Modbus is chosen from the local display or MAP Gateway.
- The application is factory programmed and cannot be changed in the field; configuration and parameter changes are made from the local display or MAP Gateway.
Watch out for
- On dual-compressor units the second Aurora board appears as ABC-2 objects (5118-5153); map both boards' lockout and fault points.
- Installed-option flags (sensor, damper, economizer installed) are commissioning settings, not commands.
- State numbers for the multistate objects are not printed; read the state text from the device.
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 5001 | Demand Ventilation Indoor Air Quality Setpoint | Range 0 to 5000 | ppm | Write | |
| AV | 5002 | Demand Ventilation Differential Setpoint | Range 0 to 5000 | ppm | Write | |
| MV | 5003 | Damper Position | Read | Close, Open | ||
| AV | 5004 | Comfort Ventilation Lower Setpoint | Range 0 to 5000 | ppm | Write | |
| AV | 5005 | Comfort Ventilation Upper Setpoint | Range 0 to 5000 | ppm | Write | |
| AV | 5006 | Damper Min Out | Range 0 to 100 | % | Write | |
| AV | 5007 | Rate Limit | Range 0 to 100 | Change per Minute | Write | |
| AV | 5008 | Damper Position | Range 0 to 100 | % | Write | |
| MV | 5009 | Water Side Economizer Valve Command | Read | Close, Open | ||
| AV | 5010 | Water Side Economizer Enable Setpoint | Range 0 to 60 | °F | Write | |
| AV | 5011 | Water Side Economizer Supply Water Temp | °F | Read | ||
| MV | 5012 | Unit Status | State set: System Mode | Write | ||
| AV | 5013 | Number of Heat Pump Stages Installed | Range 1 to 2; Single-compressor table only | Write | ||
| MV | 5014 | Thermostat Only Control Enabled | Write | No, Yes | ||
| BV | 5015 | Water Side Economizer Installed | Write | |||
| BV | 5016 | Outdoor Air Damper Installed | Write | |||
| MV | 5017 | Outdoor Air Damper 2 Position | Write | No, Yes | ||
| MV | 5018 | Reversing Valve Polarity | Write | On For Htg, On For Clg | ||
| BV | 5019 | Hum Sensor Installed | Write | |||
| BV | 5020 | Indoor Air Quality Sensor Installed | Write | |||
| MV | 5021 | Fan Command | Read | Off, On | ||
| AV | 5022 | Supply Air Temperature | °F | Read | ||
| MV | 5023 | Continuous Fan Operation in Occupied Mode | Write | Yes, No | ||
| MV | 5024 | Reversing Valve | Read | Off, On | ||
| MV | 5025 | Supplemental Heat | Read | Off, On | ||
| MVmin | 5026 | Mode | Write | Shutdown, Enable | ||
| MV | 5027 | Compressor Stage 1 Command | Read | Off, On | ||
| MV | 5028 | Compressor Stage 2 Command | Read | Off, On | ||
| MV | 5029 | Plug and Play Occupancy Request | State set: Effective Occupancy Source | Read | ||
| MVmin | 5030 | Operational Occupancy | State set: Occ Effective | Read | ||
| MV | 5031 | Occupancy Input Source | State set: Occ Override | Write | ||
| AVmin | 5032 | Operational Space Temperature | °F | Read | ||
| MV | 5033 | Space Temperature Source | State set: Effective Input Source | Read | ||
| AV | 5034 | Network Override Space Temperature | Range 0 to 100 | °F | Write | |
| AV | 5035 | Operational Indoor Air Quality | ppm | Read | ||
| MV | 5036 | Indoor Air Quality Source | State set: Effective Input Source 2 | Read | ||
| AV | 5037 | Indoor Air Quality | ppm | Read | ||
| AV | 5038 | Indoor Air Quality Sensor Range | Range 0 to 5000 | ppm | Write | |
| AV | 5039 | Network Override Indoor Air Quality | Range 0 to 5000 | ppm | Write | |
| AV | 5040 | Operational Space Humidity | %RH | Read | ||
| MV | 5041 | Space Humidity Source | State set: Effective Input Source 2 | Read | ||
| AV | 5042 | Network Override Zone Humidity | Range 0 to 100 | %RH | Write | |
| AV | 5043 | Operational Space Temperature Setpoint Offset | Δ°F | Read | ||
| MV | 5044 | Space Temperature Setpoint Offset Source | State set: Effective Input Source 2 | Read | ||
| AV | 5045 | Network Override Space Setpoint Offset | Range -5 to 5 | Δ°F | Write | |
| AV | 5046 | Space Temperature Setpoint Offset Range | Range 0 to 5 | Δ°F | Write | |
| AV | 5047 | Number of Network Sensors Online | Read | |||
| MV | 5048 | Netsensor Battery Fault | Read | Normal, Alarm | ||
| MV | 5049 | Netsensor Signal Strength Fault | Read | Normal, Alarm | ||
| MV | 5050 | Scheduled Occupancy | State set: Occ Schedule | Read | ||
| AV | 5051 | Effective Cooling Setpoint | °F | Read | ||
| AV | 5052 | Effective Heating Setpoint | °F | Read | ||
| AVmin | 5053 | Occupied Cooling Setpoint | Range 0 to 100 | °F | Write | |
| AVmin | 5054 | Occupied Heating Setpoint | Range 0 to 100 | °F | Write | |
| AV | 5055 | Unoccupied Cooling Setpoint | Range 0 to 100 | °F | Write | |
| AV | 5056 | Unoccupied Heating Setpoint | Range 0 to 100 | °F | Write | |
| AV | 5057 | Standby Cooling Setpoint | Range 0 to 100 | °F | Write | |
| AV | 5058 | Standby Heating Setpoint | Range 0 to 100 | °F | Write | |
| MVmin | 5059 | Manual Occupancy Mode | State set: Occ Override | Write | ||
| MV | 5060 | Y1 - Thermostat | Read | Off, On | ||
| MV | 5061 | Y2 - Thermostat | Read | Off, On | ||
| MV | 5062 | W1 - Thermostat | Read | Off, On | ||
| MV | 5063 | G - Thermostat | Read | Off, On | ||
| MV | 5064 | Reversing Valve | Read | Off, On | ||
| MV | 5065 | Dehumidification Enable | Read | Off, On | ||
| MV | 5066 | ABC-1 Y1 - Heat/Cool Stage 1 | Read | Off, On | ||
| MV | 5067 | ABC-1 Y2 - Heat/Cool Stage 2 | Read | Off, On | ||
| MV | 5068 | ABC-1 W - Heat Stage 3 or Emergency Heat | Read | Off, On | ||
| MV | 5069 | ABC-1 O - Reversing Valve | Read | Off, On | ||
| MV | 5070 | ABC-1 G - Fan | Read | Off, On | ||
| AV | 5071 | ABC-1 Airflow Blower Only Speed Level | Range 1 to 12 | Write | ||
| AV | 5072 | ABC-1 Airflow Low Speed Level | Range 1 to 12 | Write | ||
| AV | 5073 | ABC-1 Airflow High Speed Level | Range 1 to 12 | Write | ||
| AV | 5074 | ABC-1 Airflow EH Blower Speed Level | Range 1 to 12 | Write | ||
| MV | 5075 | ABC-1 DH - Dehumidification | Read | Off, On | ||
| MVmin | 5076 | ABC-1 Active Fault Code | State set: Aurora Fault Names | Read | ||
| BV | 5077 | ABC-1 DDC Control Enabled | Read | |||
| BVmin | 5078 | ABC-1 Unit Lockout Status | Read | |||
| BVmin | 5079 | ABC-1 CC - Compressor Contactor Enable | Read | |||
| BV | 5080 | ABC-1 CC2 - Compressor Speed Output | Read | |||
| BV | 5081 | ABC-1 F - Fan (Blower) | Read | |||
| BV | 5082 | ABC-1 EH1 - Electric Heat 1 | Read | |||
| BV | 5083 | ABC-1 EH2 - Electric Heat 2 | Read | |||
| BV | 5084 | ABC-1 ACC - Accessory Relay | Read | |||
| BV | 5085 | ABC-1 L - Lockout | Read | |||
| BV | 5086 | ABC-1 ALM - Alarm | Read | |||
| BV | 5087 | ABC-1 RV - Reversing Valve | Read | |||
| AV | 5088 | ABC-1 Airflow Current Speed Level | Read | |||
| BV | 5089 | ABC-1 High Pressure Switch | Read | |||
| BV | 5090 | ABC-1 Low Pressure Switch | Read | |||
| AV | 5091 | ABC-1 Coax Temperature | °F | Read | ||
| AV | 5092 | ABC-1 Air Coil Temperature | °F | Read | ||
| AV | 5093 | ABC-1 Condensate Input | Read | |||
| BV | 5094 | ABC-1 Emergency Shutdown | Write | |||
| BV | 5095 | ABC-1 Load Shed | Write | |||
| BVmin | 5096 | ABC-1 Reset Faults | Write | |||
| AV | 5097 | ABC-1 Firmware Revision | Read | |||
| AV | 5098 | ABC-1 Firmware Beta ID | Read | |||
| MV | 5099 | ABC-1 H - Humidification | Read | Off, On | ||
| AV | 5100 | ABC-1 DDC Thermostat Calls | Read | |||
| AV | 5101 | ABC-1 Output Status | Read | |||
| MV | 5102 | Language | State set: Internationalization Languages | Write | ||
| MV | 5103 | Units | State set: Unit Set | Write | ||
| CSV | 5104 | Description | Write | |||
| CSV | 5105 | Device Name | Write | |||
| MV | 5106 | Time Zone | State set: Time Zone | Write | ||
| MV | 5107 | Communication Status | State set: MSTPDL Port Status | Read | ||
| AV | 5108 | Address | Range 4 to 127 | Write | ||
| AV | 5109 | Device OID | Range 0 to 4194302 | Write | ||
| MV | 5110 | Operating Baud Rate | State set: MSTPDL Baud Rate | Read | ||
| MV | 5111 | Baud Rate | State set: MSTPDL Baud Rate | Write | ||
| CSV | 5112 | Firmware Main Version | Read | |||
| CSV | 5113 | Application Version | Read | |||
| CSV | 5114 | Hardware Version | Read | |||
| MV | 5115 | Calibration Data Fault | Read | Yes, No | ||
| CSV | 5116 | Unit Serial Number | Write | |||
| CSV | 5117 | Model Name | Write | |||
| MV | 5118 | ABC-2 Y1 - Heat/Cool Stage 1 | Second Aurora board (dual compressor) | Read | Off, On | |
| MV | 5119 | ABC-2 Y2 - Heat/Cool Stage 2 | Second Aurora board (dual compressor) | Read | Off, On | |
| MV | 5120 | ABC-2 W - Heat Stage 3 or Emergency Heat | Second Aurora board (dual compressor) | Read | Off, On | |
| MV | 5121 | ABC-2 G - Fan | Second Aurora board (dual compressor) | Read | Off, On | |
| AV | 5122 | ABC-2 Airflow Blower Only Speed Level | Range 1 to 12; Second Aurora board (dual compressor) | Write | ||
| AV | 5123 | ABC-2 Airflow Low Speed Level | Range 1 to 12; Second Aurora board (dual compressor) | Write | ||
| AV | 5124 | ABC-2 Airflow High Speed Level | Range 1 to 12; Second Aurora board (dual compressor) | Write | ||
| AV | 5125 | ABC-2 Airflow EH Blower Speed Level | Range 1 to 12; Second Aurora board (dual compressor) | Write | ||
| MV | 5126 | ABC-2 DH - Dehumidification | Second Aurora board (dual compressor) | Read | Off, On | |
| MV | 5127 | ABC-2 Active Fault Code | State set: Aurora Fault Names; Second Aurora board (dual compressor) | Read | ||
| BV | 5128 | ABC-2 DDC Control Enabled | Second Aurora board (dual compressor) | Read | ||
| BV | 5129 | ABC-2 Unit Lockout Status | Second Aurora board (dual compressor) | Read | ||
| BV | 5130 | ABC-2 CC - Compressor Contactor Enable | Second Aurora board (dual compressor) | Read | ||
| BV | 5131 | ABC-2 CC2 - Compressor Speed Output | Second Aurora board (dual compressor) | Read | ||
| BV | 5132 | ABC-2 F - Fan (Blower) | Second Aurora board (dual compressor) | Read | ||
| BV | 5133 | ABC-2 EH1 - Electric Heat 1 | Second Aurora board (dual compressor) | Read | ||
| BV | 5134 | ABC-2 EH2 - Electric Heat 2 | Second Aurora board (dual compressor) | Read | ||
| BV | 5135 | ABC-2 ACC - Accessory Relay | Second Aurora board (dual compressor) | Read | ||
| BV | 5136 | ABC-2 L - Lockout | Second Aurora board (dual compressor) | Read | ||
| BV | 5137 | ABC-2 ALM - Alarm | Second Aurora board (dual compressor) | Read | ||
| BV | 5138 | ABC-2 RV - Reversing Valve | Second Aurora board (dual compressor) | Read | ||
| AV | 5139 | ABC-2 Airflow Current Speed Level | Second Aurora board (dual compressor) | Read | ||
| BV | 5140 | ABC-2 High Pressure Switch | Second Aurora board (dual compressor) | Read | ||
| BV | 5141 | ABC-2 Low Pressure Switch | Second Aurora board (dual compressor) | Read | ||
| AV | 5142 | ABC-2 Coax Temperature | Second Aurora board (dual compressor) | °F | Read | |
| AV | 5143 | ABC-2 Air Coil Temperature | Second Aurora board (dual compressor) | °F | Read | |
| AV | 5144 | ABC-2 Condensate Input | Second Aurora board (dual compressor) | Read | ||
| BV | 5145 | ABC-2 Emergency Shutdown | Second Aurora board (dual compressor) | Write | ||
| BV | 5146 | ABC-2 Load Shed | Second Aurora board (dual compressor) | Write | ||
| BV | 5147 | ABC-2 Reset Faults | Second Aurora board (dual compressor) | Write | ||
| AV | 5148 | ABC-2 Firmware Revision | Second Aurora board (dual compressor) | Read | ||
| AV | 5149 | ABC-2 Firmware Beta ID | Second Aurora board (dual compressor) | Read | ||
| MV | 5150 | ABC-2 H - Humidification | Second Aurora board (dual compressor) | Read | Off, On | |
| AV | 5151 | ABC-2 DDC Thermostat Calls | Second Aurora board (dual compressor) | Read | ||
| AV | 5152 | ABC-2 Output Status | Second Aurora board (dual compressor) | Read | ||
| MV | 5153 | ABC-2 O - Reversing Valve | Second Aurora board (dual compressor) | Read | Off, On |
No points match these filters.
Object ID lookup: Johnson Controls PEAK 18 SMART Equipment WSHP point IDs by name
AV5001Demand Ventilation Indoor Air Quality SetpointAV5002Demand Ventilation Differential SetpointMV5003Damper PositionAV5004Comfort Ventilation Lower SetpointAV5005Comfort Ventilation Upper SetpointAV5006Damper Min OutAV5007Rate LimitAV5008Damper PositionMV5009Water Side Economizer Valve CommandAV5010Water Side Economizer Enable SetpointAV5011Water Side Economizer Supply Water TempMV5012Unit StatusAV5013Number of Heat Pump Stages InstalledMV5014Thermostat Only Control EnabledBV5015Water Side Economizer InstalledBV5016Outdoor Air Damper InstalledMV5017Outdoor Air Damper 2 PositionMV5018Reversing Valve PolarityBV5019Hum Sensor InstalledBV5020Indoor Air Quality Sensor InstalledMV5021Fan CommandAV5022Supply Air TemperatureMV5023Continuous Fan Operation in Occupied ModeMV5024Reversing ValveMV5025Supplemental HeatMV5026ModeMV5027Compressor Stage 1 CommandMV5028Compressor Stage 2 CommandMV5029Plug and Play Occupancy RequestMV5030Operational OccupancyMV5031Occupancy Input SourceAV5032Operational Space TemperatureMV5033Space Temperature SourceAV5034Network Override Space TemperatureAV5035Operational Indoor Air QualityMV5036Indoor Air Quality SourceAV5037Indoor Air QualityAV5038Indoor Air Quality Sensor RangeAV5039Network Override Indoor Air QualityAV5040Operational Space HumidityMV5041Space Humidity SourceAV5042Network Override Zone HumidityAV5043Operational Space Temperature Setpoint OffsetMV5044Space Temperature Setpoint Offset SourceAV5045Network Override Space Setpoint OffsetAV5046Space Temperature Setpoint Offset RangeAV5047Number of Network Sensors OnlineMV5048Netsensor Battery FaultMV5049Netsensor Signal Strength FaultMV5050Scheduled OccupancyAV5051Effective Cooling SetpointAV5052Effective Heating SetpointAV5053Occupied Cooling SetpointAV5054Occupied Heating SetpointAV5055Unoccupied Cooling SetpointAV5056Unoccupied Heating SetpointAV5057Standby Cooling SetpointAV5058Standby Heating SetpointMV5059Manual Occupancy ModeMV5060Y1 - ThermostatMV5061Y2 - ThermostatMV5062W1 - ThermostatMV5063G - ThermostatMV5064Reversing ValveMV5065Dehumidification EnableMV5066ABC-1 Y1 - Heat/Cool Stage 1MV5067ABC-1 Y2 - Heat/Cool Stage 2MV5068ABC-1 W - Heat Stage 3 or Emergency HeatMV5069ABC-1 O - Reversing ValveMV5070ABC-1 G - FanAV5071ABC-1 Airflow Blower Only Speed LevelAV5072ABC-1 Airflow Low Speed LevelAV5073ABC-1 Airflow High Speed LevelAV5074ABC-1 Airflow EH Blower Speed LevelMV5075ABC-1 DH - DehumidificationMV5076ABC-1 Active Fault CodeBV5077ABC-1 DDC Control EnabledBV5078ABC-1 Unit Lockout StatusBV5079ABC-1 CC - Compressor Contactor EnableBV5080ABC-1 CC2 - Compressor Speed OutputBV5081ABC-1 F - Fan (Blower)BV5082ABC-1 EH1 - Electric Heat 1BV5083ABC-1 EH2 - Electric Heat 2BV5084ABC-1 ACC - Accessory RelayBV5085ABC-1 L - LockoutBV5086ABC-1 ALM - AlarmBV5087ABC-1 RV - Reversing ValveAV5088ABC-1 Airflow Current Speed LevelBV5089ABC-1 High Pressure SwitchBV5090ABC-1 Low Pressure SwitchAV5091ABC-1 Coax TemperatureAV5092ABC-1 Air Coil TemperatureAV5093ABC-1 Condensate InputBV5094ABC-1 Emergency ShutdownBV5095ABC-1 Load ShedBV5096ABC-1 Reset FaultsAV5097ABC-1 Firmware RevisionAV5098ABC-1 Firmware Beta IDMV5099ABC-1 H - HumidificationAV5100ABC-1 DDC Thermostat CallsAV5101ABC-1 Output StatusMV5102LanguageMV5103UnitsCSV5104DescriptionCSV5105Device NameMV5106Time ZoneMV5107Communication StatusAV5108AddressAV5109Device OIDMV5110Operating Baud RateMV5111Baud RateCSV5112Firmware Main VersionCSV5113Application VersionCSV5114Hardware VersionMV5115Calibration Data FaultCSV5116Unit Serial NumberCSV5117Model NameMV5118ABC-2 Y1 - Heat/Cool Stage 1MV5119ABC-2 Y2 - Heat/Cool Stage 2MV5120ABC-2 W - Heat Stage 3 or Emergency HeatMV5121ABC-2 G - FanAV5122ABC-2 Airflow Blower Only Speed LevelAV5123ABC-2 Airflow Low Speed LevelAV5124ABC-2 Airflow High Speed LevelAV5125ABC-2 Airflow EH Blower Speed LevelMV5126ABC-2 DH - DehumidificationMV5127ABC-2 Active Fault CodeBV5128ABC-2 DDC Control EnabledBV5129ABC-2 Unit Lockout StatusBV5130ABC-2 CC - Compressor Contactor EnableBV5131ABC-2 CC2 - Compressor Speed OutputBV5132ABC-2 F - Fan (Blower)BV5133ABC-2 EH1 - Electric Heat 1BV5134ABC-2 EH2 - Electric Heat 2BV5135ABC-2 ACC - Accessory RelayBV5136ABC-2 L - LockoutBV5137ABC-2 ALM - AlarmBV5138ABC-2 RV - Reversing ValveAV5139ABC-2 Airflow Current Speed LevelBV5140ABC-2 High Pressure SwitchBV5141ABC-2 Low Pressure SwitchAV5142ABC-2 Coax TemperatureAV5143ABC-2 Air Coil TemperatureAV5144ABC-2 Condensate InputBV5145ABC-2 Emergency ShutdownBV5146ABC-2 Load ShedBV5147ABC-2 Reset FaultsAV5148ABC-2 Firmware RevisionAV5149ABC-2 Firmware Beta IDMV5150ABC-2 H - HumidificationAV5151ABC-2 DDC Thermostat CallsAV5152ABC-2 Output StatusMV5153ABC-2 O - Reversing Valve
Integration notes
- The guide prints two tables: Table 9 for a single-compressor unit (one Aurora board, ABC-1) and Table 10 for a dual-compressor unit, which adds ABC-2 objects 5118-5153. Both are merged here; AV 5013 Number of Heat Pump Stages Installed appears only in Table 9.
- Access is from the Writeable column (TRUE = writable).
- Multistate objects carry named state sets (Off/On, Occ Override, Effective Input Source, Aurora Fault Names and so on). Two-word sets are shown as states; the other set names are given in the description. The guide does not print the state numbers.
- Units are imperial; the guide also lists SI units and limits.
- CSV 5104 is a real object named Description, and MV 5103 is named Units.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
How many BACnet points does the Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820) have?
This list has 153 BACnet objects: 57 analog values, 36 binary values, 53 multi-state values, 7 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820) BACnet points are writable?
57 of the 153 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820) BACnet documentation?
The source is PEAK 18 24 Volt SMART Equipment Controller Application and Troubleshooting Guide (Tables 9 and 10, BACnet Exposed Objects) (147.00-EG1 (517)), revision 2017-05, published free by Johnson Controls at https://docs.johnsoncontrols.com/ductedsystems/api/khub/documents/BcW0j0n4dRaKYtNhapJY2w/content.
What are the minimum BACnet points to integrate the Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)?
Start with MV 5026 Mode (Unit mode: Shutdown or Enable); MV 5059 Manual Occupancy Mode (Occupancy override from the BMS); AV 5053 Occupied Cooling Setpoint (Occupied cooling setpoint); AV 5054 Occupied Heating Setpoint (Occupied heating setpoint); BV 5096 ABC-1 Reset Faults (Reset Aurora board faults); MV 5030 Operational Occupancy (Occupancy in effect); AV 5032 Operational Space Temperature (Space temperature the unit controls to); BV 5079 ABC-1 CC - Compressor Contactor Enable (Compressor contactor output); BV 5078 ABC-1 Unit Lockout Status (Unit locked out); MV 5076 ABC-1 Active Fault Code (Active Aurora fault).
How do I enable BMS control of the Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)?
The sequence runs when the Mode point is set to Enable. Occupancy follows the local schedule and can be overridden with Manual Occupancy Mode.
Does the Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820) need a BACnet heartbeat or have a communication timeout?
A value written to Network Override Space Temperature becomes the control input and restarts a 15-minute timeout; if the BMS stops writing, the input is treated as unreliable and ignored.
Can the BMS supply sensor values to the Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)?
AV 5034 Network Override Space Temperature, AV 5042 Network Override Zone Humidity, AV 5039 Network Override Indoor Air Quality and AV 5045 Network Override Space Setpoint Offset accept BMS values; the matching Source objects show which input is in use.
How do I check these points on the real PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: PEAK 18 24 Volt SMART Equipment Controller Application and Troubleshooting Guide (Tables 9 and 10, BACnet Exposed Objects) · 147.00-EG1 (517) · rev. 2017-05. Object names, instances and units are reproduced as published; descriptions are our own.