Power and energy meter (3-phase, BACnet MS/TP) · BACnet points list
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP) BACnet points list
Updated 6 November 2026
The EMCOMMS is the RS485 module of the Johnson Controls EM series three-phase energy meter. It speaks BACnet MS/TP (or Modbus) and by default learns the baud rate, protocol and MAC address from the live MS/TP trunk. Objects cover system and per-phase voltage, current, power, power factor, energy (as accumulators and as analog inputs), demand power, two pulse inputs and the PowerPrint installation checks.
This page lists 267 BACnet objects for the Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP) — 199 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
- Equipment
- Power and energy meter (3-phase, BACnet MS/TP)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 267 (199 writable)
- Transport
- BACnet MS/TP
- Firmware
- 1.1.4
- Default device instance
- 665000 + last three digits of the serial number
- Also known as
- EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
Connect the RS485 terminals to a live MS/TP trunk and let the meter auto-detect baud rate, protocol and MAC address, then discover it (device ID 665 plus the last three serial digits). Read system real power, energy, voltage, current, power factor and demand, and watch the condition flags for wiring or sensor problems.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 600 | Total Real Power | Total real power, kW | Write |
| AI 700 | Total Real Energy (AI) | Total real energy, kWh | Read |
| AI 800 | Demand Total Real Power | Demand real power over the demand window, kW | Write |
| AI 420 | Phase Average RMS Voltage | Average phase voltage, V | Write |
| AI 520 | Phase Average RMS Current | Average phase current, A | Write |
| AI 550 | System Power Factor | System true power factor | Write |
| AI 410 | Line Frequency | Line frequency, Hz | Write |
| AV 400 | Active Conditions | Bit-coded active system conditions | Read |
Network setup
- Factory default is automatic: the meter learns baud rate (9600-115200), protocol and a free MAC address (0-127) by listening to an active MS/TP master on the trunk. It cannot learn on an idle line.
- Default device ID is 665000 plus the last three digits of the label serial number (serial 123456 gives 665456).
- To lock the settings, write AV 123 (MAC address), AV 124 (baud rate) and MSV 126 (parity); writing them turns the matching Auto BV off.
- MAC addresses 128-254 always run as MS/TP subordinate (no token passing); 0-127 run as master when Max Info Frames is not 0 and the address is within Max Master.
- Holding the setup button while powering up clears the learned automatic settings.
Watch out for
- Writing a new baud rate to AV 124 cannot be undone remotely; the meter goes silent until the trunk matches.
- AV 190 with the reset key wipes the whole configuration, including energy totals, MAC address and device ID.
- Leaving an energy object Out Of Service stops it from accumulating new energy.
- S and T phase objects sit at R phase instance +1000 and +2000; System Phase Selection (MSV 161) sets which phases feed the system totals.
- Accumulator (ACC) energy objects wrap to 0 at 999,999; the AI versions of the same energy do not wrap.
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| ACC | 210 | Pulse Input 1 | Pulse count at pulse input terminal 1 | Read | ||
| ACC | 220 | Pulse Input 2 | Pulse count at pulse input terminal 2 | Read | ||
| ACC | 700 | Total Real Energy (ACC) | Total real energy, system phases (integer) | kWh | Read | |
| ACC | 702 | Total Real Energy (ACC) - Import | Import part | kWh | Read | |
| ACC | 704 | Total Real Energy (ACC) - Export | Export part | kWh | Read | |
| ACC | 706 | Total Real Energy (ACC) - Net | Net (import minus export) | kWh | Read | |
| ACC | 720 | System Real Energy (ACC) | System real energy from net real power (integer) | kWh | Read | |
| ACC | 722 | System Real Energy (ACC) - Import | Import part | kWh | Read | |
| ACC | 724 | System Real Energy (ACC) - Export | Export part | kWh | Read | |
| ACC | 740 | Total Reactive Energy (ACC) | Total reactive energy, system phases (integer) | kVARh | Read | |
| ACC | 742 | Total Reactive Energy (ACC) - Import | Import part | kVARh | Read | |
| ACC | 744 | Total Reactive Energy (ACC) - Export | Export part | kVARh | Read | |
| ACC | 760 | Total Apparent Energy (ACC) | Total apparent energy, system phases (integer) | kVAh | Read | |
| ACC | 762 | Total Apparent Energy (ACC) - Import | Import part | kVAh | Read | |
| ACC | 764 | Total Apparent Energy (ACC) - Export | Export part | kVAh | Read | |
| ACC | 1700 | Total R Phase Real Energy (ACC) | R phase total real energy (integer) | kWh | Read | |
| ACC | 1702 | Total R Phase Real Energy (ACC) - Import | Import part | kWh | Read | |
| ACC | 1704 | Total R Phase Real Energy (ACC) - Export | Export part | kWh | Read | |
| ACC | 1706 | Total R Phase Real Energy (ACC) - Net | Net (import minus export) | kWh | Read | |
| ACC | 1740 | Total R Phase Reactive Energy (ACC) | R phase total reactive energy (integer) | kVARh | Read | |
| ACC | 1742 | Total R Phase Reactive Energy (ACC) - Import | Import part | kVARh | Read | |
| ACC | 1744 | Total R Phase Reactive Energy (ACC) - Export | Export part | kVARh | Read | |
| ACC | 1760 | Total R Phase Apparent Energy (ACC) | R phase total apparent energy (integer) | kVAh | Read | |
| ACC | 1762 | Total R Phase Apparent Energy (ACC) - Import | Import part | kVAh | Read | |
| ACC | 1764 | Total R Phase Apparent Energy (ACC) - Export | Export part | kVAh | Read | |
| AI | 310 | Temperature | Ambient temperature at the meter | °F | Write | |
| AI | 312 | Temperature - Smoothed | Smoothed (filtered) value | °F | Write | |
| AI | 314 | Temperature - Minimum | Lowest reading since last reset | °F | Write | |
| AI | 316 | Temperature - Maximum | Highest reading since last reset | °F | Write | |
| AI | 318 | Temperature - Average | Average since last reset | °F | Write | |
| AI | 380 | Power Supply Voltage | Meter supply voltage after rectification | V | Write | |
| AI | 382 | Power Supply Voltage - Smoothed | Smoothed (filtered) value | V | Write | |
| AI | 384 | Power Supply Voltage - Minimum | Lowest reading since last reset | V | Write | |
| AI | 386 | Power Supply Voltage - Maximum | Highest reading since last reset | V | Write | |
| AI | 388 | Power Supply Voltage - Average | Average since last reset | V | Write | |
| AImin | 410 | Line Frequency | AC line frequency | Hz | Write | |
| AI | 412 | Line Frequency - Smoothed | Smoothed (filtered) value | Hz | Write | |
| AI | 414 | Line Frequency - Minimum | Lowest reading since last reset | Hz | Write | |
| AI | 416 | Line Frequency - Maximum | Highest reading since last reset | Hz | Write | |
| AI | 418 | Line Frequency - Average | Average since last reset | Hz | Write | |
| AImin | 420 | Phase Average RMS Voltage | Average RMS voltage of valid phases | V | Write | |
| AI | 422 | Phase Average RMS Voltage - Smoothed | Smoothed (filtered) value | V | Write | |
| AI | 424 | Phase Average RMS Voltage - Minimum | Lowest reading since last reset | V | Write | |
| AI | 426 | Phase Average RMS Voltage - Maximum | Highest reading since last reset | V | Write | |
| AI | 428 | Phase Average RMS Voltage - Average | Average since last reset | V | Write | |
| AI | 450 | Phase to Phase Average RMS Voltage | Average phase-to-phase RMS voltage | V | Write | |
| AI | 452 | Phase to Phase Average RMS Voltage - Smoothed | Smoothed (filtered) value | V | Write | |
| AI | 454 | Phase to Phase Average RMS Voltage - Minimum | Lowest reading since last reset | V | Write | |
| AI | 456 | Phase to Phase Average RMS Voltage - Maximum | Highest reading since last reset | V | Write | |
| AI | 458 | Phase to Phase Average RMS Voltage - Average | Average since last reset | V | Write | |
| AImin | 520 | Phase Average RMS Current | Average RMS current of valid phases | A | Write | |
| AI | 522 | Phase Average RMS Current - Smoothed | Smoothed (filtered) value | A | Write | |
| AI | 524 | Phase Average RMS Current - Minimum | Lowest reading since last reset | A | Write | |
| AI | 526 | Phase Average RMS Current - Maximum | Highest reading since last reset | A | Write | |
| AI | 528 | Phase Average RMS Current - Average | Average since last reset | A | Write | |
| AI | 540 | Phase Average Current Angle | Average current angle of valid phases | degrees | Write | |
| AI | 542 | Phase Average Current Angle - Smoothed | Smoothed (filtered) value | degrees | Write | |
| AI | 544 | Phase Average Current Angle - Minimum | Lowest reading since last reset | degrees | Write | |
| AI | 546 | Phase Average Current Angle - Maximum | Highest reading since last reset | degrees | Write | |
| AI | 548 | Phase Average Current Angle - Average | Average since last reset | degrees | Write | |
| AImin | 550 | System Power Factor | System true power factor | Write | ||
| AI | 552 | System Power Factor - Smoothed | Smoothed (filtered) value | Write | ||
| AI | 554 | System Power Factor - Minimum | Lowest reading since last reset | Write | ||
| AI | 556 | System Power Factor - Maximum | Highest reading since last reset | Write | ||
| AI | 558 | System Power Factor - Average | Average since last reset | Write | ||
| AImin | 600 | Total Real Power | Absolute sum of phase real power | kW | Write | |
| AI | 602 | Total Real Power - Smoothed | Smoothed (filtered) value | kW | Write | |
| AI | 604 | Total Real Power - Minimum | Lowest reading since last reset | kW | Write | |
| AI | 606 | Total Real Power - Maximum | Highest reading since last reset | kW | Write | |
| AI | 608 | Total Real Power - Average | Average since last reset | kW | Write | |
| AI | 610 | Phase Average Real Power | Average phase real power | kW | Write | |
| AI | 612 | Phase Average Real Power - Smoothed | Smoothed (filtered) value | kW | Write | |
| AI | 614 | Phase Average Real Power - Minimum | Lowest reading since last reset | kW | Write | |
| AI | 616 | Phase Average Real Power - Maximum | Highest reading since last reset | kW | Write | |
| AI | 618 | Phase Average Real Power - Average | Average since last reset | kW | Write | |
| AI | 620 | Net Real Power | Signed sum of real power (negative = export) | kW | Write | |
| AI | 622 | Net Real Power - Smoothed | Smoothed (filtered) value | kW | Write | |
| AI | 624 | Net Real Power - Minimum | Lowest reading since last reset | kW | Write | |
| AI | 626 | Net Real Power - Maximum | Highest reading since last reset | kW | Write | |
| AI | 628 | Net Real Power - Overall Average | Overall average since last reset | kW | Write | |
| AI | 630 | Net Real Power - Import Average | Average while importing | kW | Write | |
| AI | 632 | Net Real Power - Export Average | Average while exporting | kW | Write | |
| AI | 640 | Total Reactive Power | Absolute sum of phase reactive power | kVAR | Write | |
| AI | 642 | Total Reactive Power - Smoothed | Smoothed (filtered) value | kVAR | Write | |
| AI | 644 | Total Reactive Power - Minimum | Lowest reading since last reset | kVAR | Write | |
| AI | 646 | Total Reactive Power - Maximum | Highest reading since last reset | kVAR | Write | |
| AI | 648 | Total Reactive Power - Average | Average since last reset | kVAR | Write | |
| AI | 650 | Phase Average Reactive Power | Average phase reactive power | kVAR | Write | |
| AI | 652 | Phase Average Reactive Power - Smoothed | Smoothed (filtered) value | kVAR | Write | |
| AI | 654 | Phase Average Reactive Power - Minimum | Lowest reading since last reset | kVAR | Write | |
| AI | 656 | Phase Average Reactive Power - Maximum | Highest reading since last reset | kVAR | Write | |
| AI | 658 | Phase Average Reactive Power - Average | Average since last reset | kVAR | Write | |
| AI | 660 | Total Apparent Power | Sum of phase apparent power | kVA | Write | |
| AI | 662 | Total Apparent Power - Smoothed | Smoothed (filtered) value | kVA | Write | |
| AI | 664 | Total Apparent Power - Minimum | Lowest reading since last reset | kVA | Write | |
| AI | 666 | Total Apparent Power - Maximum | Highest reading since last reset | kVA | Write | |
| AI | 668 | Total Apparent Power - Average | Average since last reset | kVA | Write | |
| AI | 670 | Phase Average Apparent Power | Average phase apparent power | kVA | Write | |
| AI | 672 | Phase Average Apparent Power - Smoothed | Smoothed (filtered) value | kVA | Write | |
| AI | 674 | Phase Average Apparent Power - Minimum | Lowest reading since last reset | kVA | Write | |
| AI | 676 | Phase Average Apparent Power - Maximum | Highest reading since last reset | kVA | Write | |
| AI | 678 | Phase Average Apparent Power - Average | Average since last reset | kVA | Write | |
| AImin | 700 | Total Real Energy (AI) | Total real energy, system phases (float) | kWh | Read | |
| AI | 702 | Total Real Energy (AI) - Import | Import part | kWh | Read | |
| AI | 704 | Total Real Energy (AI) - Export | Export part | kWh | Read | |
| AI | 706 | Total Real Energy (AI) - Net | Net (import minus export) | kWh | Read | |
| AI | 720 | System Real Energy (AI) | System real energy from net real power (float) | kWh | Read | |
| AI | 722 | System Real Energy (AI) - Import | Import part | kWh | Read | |
| AI | 724 | System Real Energy (AI) - Export | Export part | kWh | Read | |
| AI | 740 | Total Reactive Energy (AI) | Total reactive energy (float) | kVARh | Read | |
| AI | 742 | Total Reactive Energy (AI) - Import | Import part | kVARh | Read | |
| AI | 744 | Total Reactive Energy (AI) - Export | Export part | kVARh | Read | |
| AI | 760 | Total Apparent Energy (AI) | Total apparent energy (float) | kVAh | Read | |
| AI | 762 | Total Apparent Energy (AI) - Import | Import part | kVAh | Read | |
| AI | 764 | Total Apparent Energy (AI) - Export | Export part | kVAh | Read | |
| AImin | 800 | Demand Total Real Power | Demand total real power | kW | Write | |
| AI | 802 | Demand Total Real Power - Previous | Demand of the last completed window | kW | Write | |
| AI | 804 | Demand Total Real Power - Minimum | Lowest demand window since last reset | kW | Write | |
| AI | 806 | Demand Total Real Power - Maximum | Highest demand window since last reset | kW | Write | |
| AI | 820 | Demand Net Real Power | Demand net real power | kW | Write | |
| AI | 822 | Demand Net Real Power - Previous | Demand of the last completed window | kW | Write | |
| AI | 824 | Demand Net Real Power - Minimum | Lowest demand window since last reset | kW | Write | |
| AI | 826 | Demand Net Real Power - Maximum | Highest demand window since last reset | kW | Write | |
| AI | 840 | Demand Total Reactive Power | Demand total reactive power | kVAR | Write | |
| AI | 842 | Demand Total Reactive Power - Previous | Demand of the last completed window | kVAR | Write | |
| AI | 844 | Demand Total Reactive Power - Minimum | Lowest demand window since last reset | kVAR | Write | |
| AI | 846 | Demand Total Reactive Power - Maximum | Highest demand window since last reset | kVAR | Write | |
| AI | 860 | Demand Total Apparent Power | Demand total apparent power | kVA | Write | |
| AI | 862 | Demand Total Apparent Power - Previous | Demand of the last completed window | kVA | Write | |
| AI | 864 | Demand Total Apparent Power - Minimum | Lowest demand window since last reset | kVA | Write | |
| AI | 866 | Demand Total Apparent Power - Maximum | Highest demand window since last reset | kVA | Write | |
| AI | 1420 | R Phase RMS Voltage | R phase RMS voltage incl. voltage multiplier | V | Write | |
| AI | 1422 | R Phase RMS Voltage - Smoothed | Smoothed (filtered) value | V | Write | |
| AI | 1424 | R Phase RMS Voltage - Minimum | Lowest reading since last reset | V | Write | |
| AI | 1426 | R Phase RMS Voltage - Maximum | Highest reading since last reset | V | Write | |
| AI | 1428 | R Phase RMS Voltage - Average | Average since last reset | V | Write | |
| AI | 1440 | R to S Phase Voltage Angle | Angle between R and S phase voltages | degrees | Write | |
| AI | 1442 | R to S Phase Voltage Angle - Smoothed | Smoothed (filtered) value | degrees | Write | |
| AI | 1444 | R to S Phase Voltage Angle - Minimum | Lowest reading since last reset | degrees | Write | |
| AI | 1446 | R to S Phase Voltage Angle - Maximum | Highest reading since last reset | degrees | Write | |
| AI | 1448 | R to S Phase Voltage Angle - Average | Average since last reset | degrees | Write | |
| AI | 1450 | R to S Phase RMS Voltage | R to S phase RMS voltage | V | Write | |
| AI | 1452 | R to S Phase RMS Voltage - Smoothed | Smoothed (filtered) value | V | Write | |
| AI | 1454 | R to S Phase RMS Voltage - Minimum | Lowest reading since last reset | V | Write | |
| AI | 1456 | R to S Phase RMS Voltage - Maximum | Highest reading since last reset | V | Write | |
| AI | 1458 | R to S Phase RMS Voltage - Average | Average since last reset | V | Write | |
| AI | 1520 | RMS Current | R phase RMS current incl. current multiplier | A | Write | |
| AI | 1522 | RMS Current - Smoothed | Smoothed (filtered) value | A | Write | |
| AI | 1524 | RMS Current - Minimum | Lowest reading since last reset | A | Write | |
| AI | 1526 | RMS Current - Maximum | Highest reading since last reset | A | Write | |
| AI | 1528 | RMS Current - Average | Average since last reset | A | Write | |
| AI | 1540 | Current Angle | R phase current angle (positive = leading) | degrees | Write | |
| AI | 1542 | Current Angle - Smoothed | Smoothed (filtered) value | degrees | Write | |
| AI | 1544 | Current Angle - Minimum | Lowest reading since last reset | degrees | Write | |
| AI | 1546 | Current Angle - Maximum | Highest reading since last reset | degrees | Write | |
| AI | 1548 | Current Angle - Average | Average since last reset | degrees | Write | |
| AI | 1550 | Power Factor | R phase true power factor (negative = export) | Write | ||
| AI | 1552 | Power Factor - Smoothed | Smoothed (filtered) value | Write | ||
| AI | 1554 | Power Factor - Minimum | Lowest reading since last reset | Write | ||
| AI | 1556 | Power Factor - Maximum | Highest reading since last reset | Write | ||
| AI | 1558 | Power Factor - Average | Average since last reset | Write | ||
| AI | 1600 | Real Power | R phase real power (negative = export) | kW | Write | |
| AI | 1602 | Real Power - Smoothed | Smoothed (filtered) value | kW | Write | |
| AI | 1604 | Real Power - Minimum | Lowest reading since last reset | kW | Write | |
| AI | 1606 | Real Power - Maximum | Highest reading since last reset | kW | Write | |
| AI | 1608 | Real Power - Overall Average | Overall average since last reset | kW | Write | |
| AI | 1610 | Real Power - Import Average | Average while importing | kW | Write | |
| AI | 1612 | Real Power - Export Average | Average while exporting | kW | Write | |
| AI | 1640 | Reactive Power | R phase reactive power | kVAR | Write | |
| AI | 1642 | Reactive Power - Smoothed | Smoothed (filtered) value | kVAR | Write | |
| AI | 1644 | Reactive Power - Minimum | Lowest reading since last reset | kVAR | Write | |
| AI | 1646 | Reactive Power - Maximum | Highest reading since last reset | kVAR | Write | |
| AI | 1648 | Reactive Power - Overall Average | Overall average since last reset | kVAR | Write | |
| AI | 1650 | Reactive Power - Import Average | Average while importing | kVAR | Write | |
| AI | 1652 | Reactive Power - Export Average | Average while exporting | kVAR | Write | |
| AI | 1660 | Apparent Power | R phase apparent power | kVA | Write | |
| AI | 1662 | Apparent Power - Smoothed | Smoothed (filtered) value | kVA | Write | |
| AI | 1664 | Apparent Power - Minimum | Lowest reading since last reset | kVA | Write | |
| AI | 1666 | Apparent Power - Maximum | Highest reading since last reset | kVA | Write | |
| AI | 1668 | Apparent Power - Overall Average | Overall average since last reset | kVA | Write | |
| AI | 1670 | Apparent Power - Import Average | Average while importing | kVA | Write | |
| AI | 1672 | Apparent Power - Export Average | Average while exporting | kVA | Write | |
| AI | 1700 | Total Real Energy (AI) | R phase total real energy (float) | kWh | Read | |
| AI | 1702 | Total Real Energy (AI) - Import | Import part | kWh | Read | |
| AI | 1704 | Total Real Energy (AI) - Export | Export part | kWh | Read | |
| AI | 1706 | Total Real Energy (AI) - Net | Net (import minus export) | kWh | Read | |
| AI | 1740 | Total Reactive Energy (AI) | R phase total reactive energy (float) | kVARh | Read | |
| AI | 1742 | Total Reactive Energy (AI) - Import | Import part | kVARh | Read | |
| AI | 1744 | Total Reactive Energy (AI) - Export | Export part | kVARh | Read | |
| AI | 1760 | Total Apparent Energy (AI) | R phase total apparent energy (float) | kVAh | Read | |
| AI | 1762 | Total Apparent Energy (AI) - Import | Import part | kVAh | Read | |
| AI | 1764 | Total Apparent Energy (AI) - Export | Export part | kVAh | Read | |
| AI | 1800 | Demand Real Power | R phase demand real power (windowed average) | kW | Write | |
| AI | 1802 | Demand Real Power - Previous | Demand of the last completed window | kW | Write | |
| AI | 1804 | Demand Real Power - Minimum | Lowest demand window since last reset | kW | Write | |
| AI | 1806 | Demand Real Power - Maximum | Highest demand window since last reset | kW | Write | |
| AI | 1840 | Demand Reactive Power | R phase demand reactive power | kVAR | Write | |
| AI | 1842 | Demand Reactive Power - Previous | Demand of the last completed window | kVAR | Write | |
| AI | 1844 | Demand Reactive Power - Minimum | Lowest demand window since last reset | kVAR | Write | |
| AI | 1846 | Demand Reactive Power - Maximum | Highest demand window since last reset | kVAR | Write | |
| AI | 1860 | Demand Apparent Power | R phase demand apparent power | kVA | Write | |
| AI | 1862 | Demand Apparent Power - Previous | Demand of the last completed window | kVA | Write | |
| AI | 1864 | Demand Apparent Power - Minimum | Lowest demand window since last reset | kVA | Write | |
| AI | 1866 | Demand Apparent Power - Maximum | Highest demand window since last reset | kVA | Write | |
| AV | 103 | Reset Count | Lifetime count of firmware resets | Read | ||
| AV | 104 | Up Time | Time since last meter reset | s | Read | |
| AV | 123 | MAC Address | MS/TP MAC address, 0-254 | Write | ||
| AV | 124 | RS485 Baud Rate | RS485 baud rate, 1200-460800 | Write | ||
| AV | 134 | Smoothed Temperature Response Time | Smoothing response time for temperature | s | Write | |
| AV | 142 | Smoothed Frequency Response Time | Smoothing response time for frequency and angles | s | Write | |
| AV | 144 | Smoothed Voltage Response Time | Smoothing response time for voltage | s | Write | |
| AV | 154 | Smoothed Current Response Time | Smoothing response time for current, angle, PF | s | Write | |
| AV | 164 | Smoothed Power Response Time | Smoothing response time for power | s | Write | |
| AV | 174 | Energy Timestamp | Timestamp updated with energy accumulators | ms | Read | |
| AV | 182 | Demand Synchronization Hour | Hour of day for daily demand sync, 0-23 | h | Write | |
| AV | 183 | Demand Window Time | Maximum demand window length, 0-1440 min | min | Write | |
| AV | 184 | Elapsed Demand Window | Time into current demand window; write 0 restarts it | min | Write | |
| AV | 186 | Demand Window Count | Number of completed demand windows | Read | ||
| AV | 190 | Configuration Reset | Write the reset key to restore factory defaults | Write | ||
| AV | 192 | Statistics Reset | Write a key to reset system or all statistics | Write | ||
| AV | 194 | Energy Reset Count | Number of energy resets | Read | ||
| AV | 208 | Pulse Input Debounce Time | Pulse input debounce, 0-255 ms | ms | Write | |
| AV | 242 | PowerPrint Frequency | Expected PowerPrint line frequency | Hz | Write | |
| AV | 244 | PowerPrint Frequency Tolerance | PowerPrint frequency tolerance | Hz | Write | |
| AV | 246 | PowerPrint Voltage Tolerance | PowerPrint voltage tolerance | % | Write | |
| AV | 248 | PowerPrint Voltage Angle Tolerance | PowerPrint voltage angle tolerance | degrees | Write | |
| AVmin | 400 | Active Conditions | Bit flags of active system conditions | Read | ||
| AV | 401 | Previous Conditions | Active and latched system condition flags; write 0 clears | Write | ||
| AV | 1140 | Voltage Rating | R phase CVT rated RMS voltage | V | Read | |
| AV | 1142 | Voltage Multiplier | R phase voltage multiplier (PT ratio) | Write | ||
| AV | 1144 | PowerPrint Voltage | R phase expected PowerPrint voltage | V | Write | |
| AV | 1146 | PowerPrint Voltage Angle | R phase expected PowerPrint voltage angle | degrees | Write | |
| AV | 1150 | Current Rating | R phase CVT rated RMS current | A | Read | |
| AV | 1152 | Current Multiplier | R phase current multiplier | Write | ||
| AV | 1162 | Power Multiplier | R phase power multiplier | Write | ||
| AV | 1192 | Statistics Reset | Write a key to reset R phase statistics | Write | ||
| AV | 1400 | Active Conditions | Bit flags of active R phase conditions | Read | ||
| AV | 1401 | Previous Conditions | Active and latched R phase condition flags; write 0 clears | Write | ||
| BI | 200 | Setup Button | Active while the setup button is pressed | Read | ||
| BI | 201 | Binary Input 1 | State of pulse input terminal 1 | Read | ||
| BI | 202 | Binary Input 2 | State of pulse input terminal 2 | Read | ||
| BV | 111 | Identify Meter | Puts the status LEDs into identify mode | Write | ||
| BV | 112 | Auto Protocol | Automatic protocol detection | Write | ||
| BV | 113 | Auto MAC Address | Automatic MAC address selection | Write | ||
| BV | 114 | Auto Baud Rate | Automatic baud rate detection | Write | ||
| BV | 116 | Auto Parity | Automatic parity detection | Write | ||
| BV | 195 | Auto Reset Statistics | Automatic reset of min/max/average statistics | Write | ||
| BV | 240 | PowerPrint Alarm | Active when any PowerPrint condition is active | Read | ||
| BV | 241 | PowerPrint | PowerPrint reference set; write to set or clear | Write | ||
| BV | 1102 | CVT Present | Active when an R phase CVT is connected | Read | ||
| BV | 1161 | Power Multiplier Override | R phase power multiplier overridden | Write | ||
| MV | 122 | RS485 Protocol | RS485 protocol selection | Write | 1=Auto, 2=BACnet, 3=Modbus RTU, 4=Modbus ASCII, 5=BACnet and Modbus RTU, 6=BACnet and Modbus ASCII, 7=Modbus RTU and ASCII, 8=Any Protocol | |
| MV | 126 | RS485 Parity | RS485 parity | Write | 1=Auto, 2=No Parity, 3=Odd Parity, 4=Even Parity | |
| MV | 133 | Temperature Units | Temperature units | Write | 1=Degrees Fahrenheit, 2=Degrees Celsius | |
| MV | 152 | System Current Sensor Technology | Combined current sensor technology of the CVTs | Read | 1=Unknown Technology, 2=Conflicted Technology, 3=Multiple Technology, 4=Rogowski Coil, 5=Current Transformer | |
| MV | 153 | Angle Units | Angle units | Write | 1=Degrees, 2=Radians | |
| MV | 161 | System Phase Selection | Phases included in system values | Write | 1=3 Phase, 2=R Phase and S Phase, 3=S Phase and T Phase, 4=R Phase and T Phase | |
| MV | 162 | Power Spectrum | Wideband or fundamental power measurement | Write | 1=Wideband, 2=Fundamental | |
| MV | 163 | Power Units | Power units | Write | 1=Kilowatts, 2=Watts, 3=Megawatts | |
| MV | 173 | Energy Units | Energy units | Write | 1=Kilowatt Hours, 2=Watt Hours, 3=Megawatt Hours | |
| MV | 181 | Demand Synchronization Mode | Demand window synchronization source | Write | 1=No Synchronization, 2=Setup Button, 3=Binary Input 1 (falling), 4=Binary Input 1 (rising), 5=Binary Input 2 (falling), 6=Binary Input 2 (rising), 7=Every Hour, 8=Every Day | |
| MV | 1103 | CVT Status | R phase CVT status | Read | 1=No CVT, 2=No Error, 3=Detection Error, 4=Communication Error, 5=Configuration Error, 6=Version Error, 7=Technology Error | |
| MV | 1104 | PowerPrint Identity Status | R phase PowerPrint identity status | Write | 1=No Identity, 2=Identity Saved, 3=Identity Error | |
| MV | 1154 | Current Sensor Technology | R phase CVT current sensor technology | Read | 1=Unknown Technology, 2=Rogowski Coil, 3=Current Transformer | |
| CSV | 1010 | CVT Serial Number | R phase CVT serial number | Read | ||
| CSV | 1020 | CVT Model | R phase CVT model | Read | ||
| FILE | 25000 | User Configuration | Read-only copy of the configuration | Read |
No points match these filters.
Object ID lookup: Johnson Controls EMCOMMS 3-Phase Energy Meter point IDs by name
ACC210Pulse Input 1ACC220Pulse Input 2ACC700Total Real Energy (ACC)ACC702Total Real Energy (ACC) - ImportACC704Total Real Energy (ACC) - ExportACC706Total Real Energy (ACC) - NetACC720System Real Energy (ACC)ACC722System Real Energy (ACC) - ImportACC724System Real Energy (ACC) - ExportACC740Total Reactive Energy (ACC)ACC742Total Reactive Energy (ACC) - ImportACC744Total Reactive Energy (ACC) - ExportACC760Total Apparent Energy (ACC)ACC762Total Apparent Energy (ACC) - ImportACC764Total Apparent Energy (ACC) - ExportACC1700Total R Phase Real Energy (ACC)ACC1702Total R Phase Real Energy (ACC) - ImportACC1704Total R Phase Real Energy (ACC) - ExportACC1706Total R Phase Real Energy (ACC) - NetACC1740Total R Phase Reactive Energy (ACC)ACC1742Total R Phase Reactive Energy (ACC) - ImportACC1744Total R Phase Reactive Energy (ACC) - ExportACC1760Total R Phase Apparent Energy (ACC)ACC1762Total R Phase Apparent Energy (ACC) - ImportACC1764Total R Phase Apparent Energy (ACC) - ExportAI310TemperatureAI312Temperature - SmoothedAI314Temperature - MinimumAI316Temperature - MaximumAI318Temperature - AverageAI380Power Supply VoltageAI382Power Supply Voltage - SmoothedAI384Power Supply Voltage - MinimumAI386Power Supply Voltage - MaximumAI388Power Supply Voltage - AverageAI410Line FrequencyAI412Line Frequency - SmoothedAI414Line Frequency - MinimumAI416Line Frequency - MaximumAI418Line Frequency - AverageAI420Phase Average RMS VoltageAI422Phase Average RMS Voltage - SmoothedAI424Phase Average RMS Voltage - MinimumAI426Phase Average RMS Voltage - MaximumAI428Phase Average RMS Voltage - AverageAI450Phase to Phase Average RMS VoltageAI452Phase to Phase Average RMS Voltage - SmoothedAI454Phase to Phase Average RMS Voltage - MinimumAI456Phase to Phase Average RMS Voltage - MaximumAI458Phase to Phase Average RMS Voltage - AverageAI520Phase Average RMS CurrentAI522Phase Average RMS Current - SmoothedAI524Phase Average RMS Current - MinimumAI526Phase Average RMS Current - MaximumAI528Phase Average RMS Current - AverageAI540Phase Average Current AngleAI542Phase Average Current Angle - SmoothedAI544Phase Average Current Angle - MinimumAI546Phase Average Current Angle - MaximumAI548Phase Average Current Angle - AverageAI550System Power FactorAI552System Power Factor - SmoothedAI554System Power Factor - MinimumAI556System Power Factor - MaximumAI558System Power Factor - AverageAI600Total Real PowerAI602Total Real Power - SmoothedAI604Total Real Power - MinimumAI606Total Real Power - MaximumAI608Total Real Power - AverageAI610Phase Average Real PowerAI612Phase Average Real Power - SmoothedAI614Phase Average Real Power - MinimumAI616Phase Average Real Power - MaximumAI618Phase Average Real Power - AverageAI620Net Real PowerAI622Net Real Power - SmoothedAI624Net Real Power - MinimumAI626Net Real Power - MaximumAI628Net Real Power - Overall AverageAI630Net Real Power - Import AverageAI632Net Real Power - Export AverageAI640Total Reactive PowerAI642Total Reactive Power - SmoothedAI644Total Reactive Power - MinimumAI646Total Reactive Power - MaximumAI648Total Reactive Power - AverageAI650Phase Average Reactive PowerAI652Phase Average Reactive Power - SmoothedAI654Phase Average Reactive Power - MinimumAI656Phase Average Reactive Power - MaximumAI658Phase Average Reactive Power - AverageAI660Total Apparent PowerAI662Total Apparent Power - SmoothedAI664Total Apparent Power - MinimumAI666Total Apparent Power - MaximumAI668Total Apparent Power - AverageAI670Phase Average Apparent PowerAI672Phase Average Apparent Power - SmoothedAI674Phase Average Apparent Power - MinimumAI676Phase Average Apparent Power - MaximumAI678Phase Average Apparent Power - AverageAI700Total Real Energy (AI)AI702Total Real Energy (AI) - ImportAI704Total Real Energy (AI) - ExportAI706Total Real Energy (AI) - NetAI720System Real Energy (AI)AI722System Real Energy (AI) - ImportAI724System Real Energy (AI) - ExportAI740Total Reactive Energy (AI)AI742Total Reactive Energy (AI) - ImportAI744Total Reactive Energy (AI) - ExportAI760Total Apparent Energy (AI)AI762Total Apparent Energy (AI) - ImportAI764Total Apparent Energy (AI) - ExportAI800Demand Total Real PowerAI802Demand Total Real Power - PreviousAI804Demand Total Real Power - MinimumAI806Demand Total Real Power - MaximumAI820Demand Net Real PowerAI822Demand Net Real Power - PreviousAI824Demand Net Real Power - MinimumAI826Demand Net Real Power - MaximumAI840Demand Total Reactive PowerAI842Demand Total Reactive Power - PreviousAI844Demand Total Reactive Power - MinimumAI846Demand Total Reactive Power - MaximumAI860Demand Total Apparent PowerAI862Demand Total Apparent Power - PreviousAI864Demand Total Apparent Power - MinimumAI866Demand Total Apparent Power - MaximumAI1420R Phase RMS VoltageAI1422R Phase RMS Voltage - SmoothedAI1424R Phase RMS Voltage - MinimumAI1426R Phase RMS Voltage - MaximumAI1428R Phase RMS Voltage - AverageAI1440R to S Phase Voltage AngleAI1442R to S Phase Voltage Angle - SmoothedAI1444R to S Phase Voltage Angle - MinimumAI1446R to S Phase Voltage Angle - MaximumAI1448R to S Phase Voltage Angle - AverageAI1450R to S Phase RMS VoltageAI1452R to S Phase RMS Voltage - SmoothedAI1454R to S Phase RMS Voltage - MinimumAI1456R to S Phase RMS Voltage - MaximumAI1458R to S Phase RMS Voltage - AverageAI1520RMS CurrentAI1522RMS Current - SmoothedAI1524RMS Current - MinimumAI1526RMS Current - MaximumAI1528RMS Current - AverageAI1540Current AngleAI1542Current Angle - SmoothedAI1544Current Angle - MinimumAI1546Current Angle - MaximumAI1548Current Angle - AverageAI1550Power FactorAI1552Power Factor - SmoothedAI1554Power Factor - MinimumAI1556Power Factor - MaximumAI1558Power Factor - AverageAI1600Real PowerAI1602Real Power - SmoothedAI1604Real Power - MinimumAI1606Real Power - MaximumAI1608Real Power - Overall AverageAI1610Real Power - Import AverageAI1612Real Power - Export AverageAI1640Reactive PowerAI1642Reactive Power - SmoothedAI1644Reactive Power - MinimumAI1646Reactive Power - MaximumAI1648Reactive Power - Overall AverageAI1650Reactive Power - Import AverageAI1652Reactive Power - Export AverageAI1660Apparent PowerAI1662Apparent Power - SmoothedAI1664Apparent Power - MinimumAI1666Apparent Power - MaximumAI1668Apparent Power - Overall AverageAI1670Apparent Power - Import AverageAI1672Apparent Power - Export AverageAI1700Total Real Energy (AI)AI1702Total Real Energy (AI) - ImportAI1704Total Real Energy (AI) - ExportAI1706Total Real Energy (AI) - NetAI1740Total Reactive Energy (AI)AI1742Total Reactive Energy (AI) - ImportAI1744Total Reactive Energy (AI) - ExportAI1760Total Apparent Energy (AI)AI1762Total Apparent Energy (AI) - ImportAI1764Total Apparent Energy (AI) - ExportAI1800Demand Real PowerAI1802Demand Real Power - PreviousAI1804Demand Real Power - MinimumAI1806Demand Real Power - MaximumAI1840Demand Reactive PowerAI1842Demand Reactive Power - PreviousAI1844Demand Reactive Power - MinimumAI1846Demand Reactive Power - MaximumAI1860Demand Apparent PowerAI1862Demand Apparent Power - PreviousAI1864Demand Apparent Power - MinimumAI1866Demand Apparent Power - MaximumAV103Reset CountAV104Up TimeAV123MAC AddressAV124RS485 Baud RateAV134Smoothed Temperature Response TimeAV142Smoothed Frequency Response TimeAV144Smoothed Voltage Response TimeAV154Smoothed Current Response TimeAV164Smoothed Power Response TimeAV174Energy TimestampAV182Demand Synchronization HourAV183Demand Window TimeAV184Elapsed Demand WindowAV186Demand Window CountAV190Configuration ResetAV192Statistics ResetAV194Energy Reset CountAV208Pulse Input Debounce TimeAV242PowerPrint FrequencyAV244PowerPrint Frequency ToleranceAV246PowerPrint Voltage ToleranceAV248PowerPrint Voltage Angle ToleranceAV400Active ConditionsAV401Previous ConditionsAV1140Voltage RatingAV1142Voltage MultiplierAV1144PowerPrint VoltageAV1146PowerPrint Voltage AngleAV1150Current RatingAV1152Current MultiplierAV1162Power MultiplierAV1192Statistics ResetAV1400Active ConditionsAV1401Previous ConditionsBI200Setup ButtonBI201Binary Input 1BI202Binary Input 2BV111Identify MeterBV112Auto ProtocolBV113Auto MAC AddressBV114Auto Baud RateBV116Auto ParityBV195Auto Reset StatisticsBV240PowerPrint AlarmBV241PowerPrintBV1102CVT PresentBV1161Power Multiplier OverrideMV122RS485 ProtocolMV126RS485 ParityMV133Temperature UnitsMV152System Current Sensor TechnologyMV153Angle UnitsMV161System Phase SelectionMV162Power SpectrumMV163Power UnitsMV173Energy UnitsMV181Demand Synchronization ModeMV1103CVT StatusMV1104PowerPrint Identity StatusMV1154Current Sensor TechnologyCSV1010CVT Serial NumberCSV1020CVT ModelFILE25000User Configuration
Integration notes
- Objects from the BACnet Protocol Guide EMCOMMS (LIT-12013039, Rev 0A, 2018-08-17), pages 10-48; the guide describes one object per heading rather than in a single table.
- Only the system and R phase objects are listed. S phase and T phase objects repeat the R phase ones at instance +1000 and +2000 (for example AI 2600 and AI 3600 are S and T phase real power).
- Statistic and part objects (Smoothed, Minimum, Maximum, Average, Previous, Import, Export, Net) are printed only as an ID with a short label under their main object; the names here join the main object name and that label and may differ from the object names the meter reports.
- Units are the defaults. Power, energy, temperature and angle units follow MSV 163, MSV 173, MSV 133 and MSV 153.
- Access W covers read/write objects, write-only reset keys (AV 190, AV 192, AV 1192) and W0 objects, where only writing 0 is allowed (it resets that statistic or clears latched flags).
- The guide lists Accumulator objects (energy and pulse counts) next to Analog Input versions of the same energy values; both read the same internal register.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
How many BACnet points does the Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP) have?
This list has 267 BACnet objects: 179 analog inputs, 34 analog values, 3 binary inputs, 10 binary values, 1 file, 13 multi-state values, 25 accumulators, 2 characterstring values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP) BACnet points are writable?
199 of the 267 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP) BACnet documentation?
The source is BACnet Protocol Guide EMCOMMS (LIT-12013039), revision 2018-08-17 (Rev 0A), published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/tmILegJJiJ6TGn6bbAol6Q/content.
What are the minimum BACnet points to integrate the Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)?
Start with AI 600 Total Real Power (Total real power, kW); AI 700 Total Real Energy (AI) (Total real energy, kWh); AI 800 Demand Total Real Power (Demand real power over the demand window, kW); AI 420 Phase Average RMS Voltage (Average phase voltage, V); AI 520 Phase Average RMS Current (Average phase current, A); AI 550 System Power Factor (System true power factor); AI 410 Line Frequency (Line frequency, Hz); AV 400 Active Conditions (Bit-coded active system conditions).
How do I check these points on the real EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: BACnet Protocol Guide EMCOMMS · LIT-12013039 · rev. 2018-08-17 (Rev 0A). Object names, instances and units are reproduced as published; descriptions are our own.