- ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
Fan coil unit controller · BACnet points list
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper) BACnet points list
Updated 6 November 2026
Application #4004 is one of the fan coil applications for the Johnson Controls ATC1500 (4 UI, 2 BI, 2 BO, 4 RO, 3 CO) Advanced Terminal Unit Controller, which connects over BACnet MS/TP (it can also run N2 or Modbus). It drives a four-pipe fan coil with 0-10 V proportional valve control, a multi-speed (staged) fan, a two-wire PWM heating option and an optional on/off fresh-air damper. Points cover unit enable, occupancy and mode commands, network setpoint and network sensor overrides, fan, valve and damper status, PID tuning, fault detection flags and the controller's network settings.
This page lists 229 BACnet objects for the Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper) — 151 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
- Equipment
- Fan coil unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 229 (151 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
Set the controller to BACnet MS/TP (FC Comm Mode Wired Field Bus) with an MS/TP address of 4-127, then enable the unit with Unit Enable Mode, drive occupancy through Occupancy Schedule and write Network Setpoint (Spt Source defaults to Network Input). Read unit status, effective occupancy, zone temperature and the fan state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 28002 | Unit Enable Mode | Unit on/off: 0=Shutdown, 1=Enable | Write |
| MV 28046 | Occupancy Schedule | Occupancy from the BAS schedule | Write |
| MV 28006 | System Mode | Mode command (cool only, heat only, fan only...) | Write |
| AV 28065 | Network Setpoint | Zone setpoint written by the BAS, °C/°F | Write |
| MV 28000 | Unit Status | Heat, cool, fan only, satisfied or off | Read |
| MV 28047 | Effective Occupancy | Occupancy in effect | Read |
| AV 28090 | Operational Zone Temperature | Zone temperature in use, °C/°F | Read |
| MV 28023 | Fan Speed Status | Fan speed: 0=Off, 1=Low, 2=Medium, 3=High | Read |
| MV 28079 | Condensate Alarm BI | Condensate alarm input: 0=Normal, 1=Alarm | Read |
Enable & remote start
Unit Enable Mode (Shutdown or Enable, default Enable) turns the unit off or on. Effective occupancy follows Occupancy Override first, then the bypass timer, Occupancy Schedule and the occupancy sensor. System Mode is the writable mode command (cool only, heat only, fan only and others).
Sensors & values from the BMS
With Spt Source at Network Input (the default) the zone setpoint comes from Network Setpoint (default 22 °C). Network Override Zone Temperature, Network Override Outdoor Air Temperature and Network Override Indoor Air Quality are writable network inputs; a network CO2 value takes priority over the local sensor, and summer-winter setpoint compensation only works with a reliable network outdoor air temperature.
Network setup
- FC Comm Mode picks the field bus (Wired Field Bus for BACnet MS/TP, N2 or Modbus). MSTP Device Address is 4-127 and Device Object ID 0-4194302.
- FCB Baud Rate defaults to Auto; Operating Baud Rate shows the rate in use and Communication Status the MS/TP state.
- Units (MV 28016) selects IP or SI; the default is SI.
Watch out for
- BACnet IDs (AV 280xx / MV 280xx) are reused across the ATC applications but do not always mean the same point; map each application from its own list.
- Occupancy Override and Occupancy Schedule read Not Set after a reset until written again; with both Not Set and no occupancy sensor the unit falls back to Default Occupancy (Occupied unless changed).
- PID tuning, minimum on/off times and fault delays are commissioning values; don't write them cyclically.
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 28000 | Unit Status | Read | 0=Heat, 1=Cool, 2=Fan Only, 3=Balancing, 4=Satisfied, 5=Off | ||
| MV | 28001 | Application Tuning Reset | Write | 0=False, 1=True, 2=Hold | ||
| MVmin | 28002 | Unit Enable Mode | Write | 0=Shutdown, 1=Enable | ||
| MV | 28003 | Occupied State | Read | 0=Heating, 1=Satisfied, 2=Cooling, 3=Supp Htg, 4=Temperature Unreliable | ||
| MV | 28004 | Unoccupied State | Read | 0=Not Unoccupied, 1=Temperature Unreliable, 2=Unocc Htg/Clg Check, 3=Unoccupied Off | ||
| MVmin | 28006 | System Mode | Write | 0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, ... (list cut short in the doc) | ||
| MV | 28007 | Effective HVAC Mode | Read | 0=Not In Use, 1=Off, 2=Heat, 3=Cool, 4=Fan Only | ||
| MV | 28008 | Device Status | Read | 0=Main Download Req, 1=Code Download, 2=Class Code Download, 3=Subclass Download, ... (list cut short in the doc) | ||
| MV | 28009 | Firmware Status | Read | 0=Firmware Versions OK, 1=Firmware Versions Do Not Match the Package | ||
| AV | 28000 | N2 Address | Range 1 to 253 | Write | ||
| AV | 28001 | Modbus Address | Range 1 to 247 | Write | ||
| AV | 28002 | MSTP Device Address | Range 4 to 127 | Write | ||
| AV | 28003 | Device Object ID | Range 0 to 4194302 | Write | ||
| MV | 28010 | FC Comm Mode | Write | 0=Wired Field Bus, 1=Wireless Field Bus, 2=N2 Field Bus, 3=Modbus Field Bus, ... (list cut short in the doc) | ||
| MV | 28011 | Communication Status | Read | 0=Not Configured, 1=Active, 2=Waiting For Poll For Master, 3=Not Received Token For Long, ... (list cut short in the doc) | ||
| MV | 28012 | FCB Baud Rate | Write | 0=Auto, 1=1200, 2=9600, 3=19200, ... (list cut short in the doc) | ||
| MV | 28013 | Operating Baud Rate | Read | 0=Auto, 1=1200, 2=9600, 3=19200, ... (list cut short in the doc) | ||
| MV | 28014 | BACnet Encoding Type | Write | 0=ISO 10646 (UCS-2), 1=ANSI X3.4 (US-ASCII), 2=Microsoft DBCS code page 932 (Japanese Shift JIS), 3=ISO 10646 (UTF-8) | ||
| MV | 28015 | Time Zone | Write | 1=(UTC+00:00) Monrovia, Reykjavik, 2=(UTC+00:00) Greenwich Mean Time : Dublin, Edinburgh, Lisbon, London, 3=(UTC+01:00) Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna, 4=(UTC+01:00) Belgrade, Bratislava, Budapest, Ljubljana, Prague, ... (list cut short in the doc) | ||
| MV | 28016 | Units | Write | 0=IP, 1=SI | ||
| MV | 28017 | Relearn System | Write | 0=False, 1=True | ||
| MV | 28018 | Provider Name | Write | 0=Automatic, 1=Manual | ||
| MV | 28019 | Fan Speed 1 BO | Read | 0=Off, 1=On, 2=Hold | ||
| MV | 28020 | Fan Speed 2 BO | Read | 0=Off, 1=On, 2=Hold | ||
| MV | 28021 | Fan Speed 3 BO | Read | 0=Off, 1=On, 2=Hold | ||
| MV | 28022 | Number of Speeds | Write | 0=One Speed, 1=Two Speed, 2=Three Speed | ||
| MVmin | 28023 | Fan Speed Status | Read | 0=Off, 1=Low, 2=Medium, 3=High | ||
| MV | 28024 | Fan OnOff | Read | 0=Off, 1=On | ||
| MV | 28039 | Damper State | Read | 0=Off, 1=On, 2=Max | ||
| AV | 28030 | Damper Maximum Position | Range 0 to 100% | % | Write | |
| AV | 28031 | Damper Minimum Position | Range 0 to 100% | % | Write | |
| AV | 28162 | Damper Stroke Time | Range 1 to 240 seconds | s | Write | |
| AV | 28032 | Damper Percent Cmd | Range 0 to 100% | % | Read | |
| MV | 28040 | Damper OpenClose | Read | 0=Close, 1=Open | ||
| AV | 28033 | CO2 Prop Band | Range 0 to 10000 ppm | ppm | Write | |
| MV | 28041 | OA Damper BO | Read | 0=Close, 1=Open, 2=Hold | ||
| MV | 28043 | Damper Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| AV | 28035 | Return CO2 Sensor Offset | Range -2000 to 2000 ppm | ppm | Write | |
| MV | 28044 | IAQ | Read | 0=Unreliable, 1=Low Priority, 2=Medium Priority, 3=High Priority, ... (list cut short in the doc) | ||
| MV | 28045 | Occupancy Override | Write | 0=Occupied, 1=UnOccupied, 2=Bypass, 3=Standby, 4=Not Set | ||
| MVmin | 28046 | Occupancy Schedule | Write | 0=Occupied, 1=UnOccupied, 2=Standby, 3=Not Set | ||
| MVmin | 28047 | Effective Occupancy | Read | 0=Occupied, 1=UnOccupied, 2=Bypass, 3=Standby | ||
| AV | 28036 | Bypass Time | Range 0 to 7200 seconds | s | Write | |
| AV | 28037 | Off Delay | Range 0 to 600 seconds | s | Write | |
| MV | 28048 | Temporary Occupancy | Write | 0=Normal, 1=Trigger | ||
| MV | 28049 | FDD Enable | Write | 0=Disable, 1=Enable | ||
| AV | 28038 | Start Delay | Range 0 to 86400 seconds | s | Write | |
| AV | 28039 | Insufficient Htg Cap Sat Delay | Range 0 to 86400 seconds | s | Write | |
| AV | 28040 | Insufficient Htg Cap Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28041 | Insufficient Clg Cap Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28042 | Low Zone Temp Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28043 | High Zone Temp Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28044 | ZN Spt Out Of Comfort Lim Min T Spt | Range -20 to 40°C (-4 to 104°F) | °C/°F | Write | |
| AV | 28045 | ZN Spt Out Of Comfort Lim Max T Spt | Range -20 to 40°C (-4 to 104°F) | °C/°F | Write | |
| AV | 28046 | Setpoint Compensation Winter Max Diff | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28047 | Setpoint Compensation Summer Max Diff | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28048 | Insufficient Clg Cap Sat Delay | Range 0 to 86400 seconds | s | Write | |
| MV | 28050 | FDD | Read | 0=Disable, 1=Enable | ||
| AV | 28049 | Simultaneous HtgClg Zone Max Error | Range 0 to 100 delta °C | delta °C/°F | Write | |
| AV | 28050 | DAT Not Responding Htg Threshold Temp | Range 0 to 100°C (32 to 212°F) | °C/°F | Write | |
| AV | 28051 | DAT Not Responding Clg Threshold Temp | Range 0 to 100°C (32 to 212°F) | °C/°F | Write | |
| MV | 28051 | Window Open While Occupied Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28052 | Window Open While Unoccupied Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28053 | Insufficient Cooling Capacity Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28054 | Insufficient Heating Capacity Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28055 | Zone Spt Outside Comfort Limits Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28056 | High Zone Temp Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28057 | Low Zone Temp Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28058 | Incorrect Setpoint Compensation Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28059 | Simultaneous Htg and Clg Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28060 | DAT Not Responding Fault | Read | 0=Normal, 1=Alarm | ||
| AV | 28052 | Window Open In Occ In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28053 | Window Open In Unocc In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28054 | Low Zone Temp In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28055 | High Zone Temp In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28056 | Simultaneous Htg Clg In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28057 | DAT Not Responding In Fault Time | Range 0 to 86400 seconds | s | Write | |
| MV | 28061 | Window Open In Occ Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28062 | Window Open In Unocc Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28063 | Insufficient Htg Cap Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28064 | Insufficient Clg Cap Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28065 | Low Zone Temp Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28066 | High Zone Temp Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28067 | Setpoint Compensation Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28068 | ZN Spt Out Of Comfort Lim Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28069 | Simultaneous Htg Clg Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28070 | DAT Not Responding Fault Enable | Write | 0=Disable, 1=Enable | ||
| AV | 28058 | ecoClgSetpoint | Range 20 to 30°C (68 to 86°F) | °C/°F | Write | |
| MV | 28071 | Energy Indicator | Read | 0=Off, 1=Red, 2=Green | ||
| AV | 28059 | ecoHtgSetpoint | Range 15 to 25°C (59 to 77°F) | °C/°F | Write | |
| MV | 28072 | Energy Indication Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28073 | Energy Indicator Reset | Write | 0=False, 1=True | ||
| AV | 28060 | ecoHtgSetpoint Diff | Range 0 to 10 delta °C (0 to 10 delta °F) | delta °C/°F | Write | |
| AV | 28061 | ecoClgSetpoint Diff | Range 0 to 10 delta °C (0 to 10 delta °F) | delta °C/°F | Write | |
| AV | 28062 | CO2 Setpoint | Range 0 to 10000 ppm | ppm | Write | |
| AV | 28063 | Unocc Cooling Setpoint | Range 15 to 30°C (59 to 86°F) | °C/°F | Write | |
| AV | 28064 | Unocc Heating Setpoint | Range 10 to 25°C (50 to 77°F) | °C/°F | Write | |
| AVmin | 28065 | Network Setpoint | Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Write | |
| AV | 28066 | Standby Cooling Setpoint | Range 10 to 30°C (50 to 86°F) | °C/°F | Write | |
| AV | 28067 | Standby Heating Setpoint | Range 10 to 30°C (50 to 86°F) | °C/°F | Write | |
| AV | 28068 | Freeze Stat Setpoint | Range -20 to 10°C (-4 to 50°F) | °C/°F | Write | |
| AV | 28069 | Frost Protect Differential | Range 0 to 15 delta °C (0 to 27 delta °F) | delta °C/°F | Write | |
| AV | 28070 | Effective Cooling Setpoint | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28071 | Effective Heating Setpoint | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28072 | Deadband | Range 0 to 10 delta °C (0 to 18 delta °F) | delta °C/°F | Write | |
| MV | 28074 | Spt Source | Write | 0=Network Input, 1=Sensor Input, 2=Multiple Inputs | ||
| MV | 29990 | Space Vote | Read | 0=Urgent Heat, 1=Heat, 2=Satisfied, 3=Cool, 4=Urgent Cool | ||
| AV | 28073 | Low Range | Range 0 to 100% | % | Write | |
| AV | 28074 | High Range | Range 0 to 100% | % | Write | |
| AV | 28075 | Low Range Diff | Range 0 to 100% | % | Write | |
| AV | 28076 | High Range Diff | Range 0 to 100% | % | Write | |
| AV | 28086 | Network Override Indoor Air Quality | Range 0 to 10000 ppm | ppm | Write | |
| AV | 28087 | Operational Indoor Air Quality | Range 0 to 10000 ppm | ppm | Read | |
| AV | 28088 | Network Override Outdoor Air Temperature | Range -46 to 94°C (-50.8 to 201.2°F) | °C/°F | Write | |
| AV | 28089 | Network Override Zone Temperature | Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Write | |
| AVmin | 28090 | Operational Zone Temperature | Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Read | |
| AV | 28091 | Operational Outdoor Air Temperature | Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Read | |
| MVmin | 28079 | Condensate Alarm BI | Read | 0=Normal, 1=Alarm, 2=Hold | ||
| MV | 28080 | Window Status BI | Read | 0=Close, 1=Open, 2=Hold | ||
| MV | 28081 | Occupancy Sensor BI | Read | 0=Occupied, 1=Unoccupied, 2=Hold | ||
| MV | 28082 | Occupancy Sensor Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28083 | Window Contact Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28084 | Dew Point Contact Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28085 | Safety Tstat BI | Read | 0=Normal, 1=Alarm, 2=Hold | ||
| MV | 28086 | Safety Tstat Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| AV | 28092 | Effective Cooling Shift | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28093 | Effective Heating Shift | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28094 | Winter Setpoint | Range -40 to 20°C (-40 to 68°F) | °C/°F | Write | |
| AV | 28095 | Summer Setpoint | Range 10 to 60°C (50 to 140°F) | °C/°F | Write | |
| AV | 28096 | Summer Change Limit | Range -10 to 10 delta °C (-18 to 18 delta °F) | delta °C/°F | Write | |
| AV | 28097 | Winter Change Limit | Range -10 to 10 delta °C (-18 to 18 delta °F) | delta °C/°F | Write | |
| AV | 28098 | Summer Gain | Range 0 to 10 | Write | ||
| AV | 28099 | Winter Gain | Range -10 to 10 | Write | ||
| MV | 28087 | Start Commission | Write | 0=Normal, 1=Trigger | ||
| MV | 28088 | SF-C Ovrd | Write | 0=Off, 1=On | ||
| AV | 28100 | SF-O Ovrd | Range 0 to 100% | % | Write | |
| MV | 28089 | OAD-C Ovrd | Write | 0=Off, 1=On | ||
| AV | 28101 | OAD-O Ovrd | Range 0 to 100% | % | Write | |
| AV | 28102 | SuppHtg-O Ovrd | Range 0 to 100% | % | Write | |
| AV | 28104 | Heating Override Check | Range 0 to 100 | Write | ||
| AV | 28105 | Cooling Override Check | Range 0 to 100 | Write | ||
| AV | 28106 | Zone Temperature | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28107 | CO2 | Range 0 to 10000 ppm | ppm | Read | |
| MV | 28096 | Zone Occupancy Request | Read | 0=Occupied, 1=UnOccupied, 2=Not Set | ||
| AV | 28108 | Warmer/Cooler Adjust | Range -100 to 100 delta °C (-100 to 100 delta °F) | delta °C/°F | Read | |
| AV | 28109 | Setpoint Offset | Range 0.01 to 10 delta °C (0.02 to 18 delta °F) | delta °C/°F | Write | |
| MV | 28097 | Indoor Air Quality Sensor Installed | Read | 0=Reliable, 1=No Input, 2=Out of range high, 3=Out of range low, ... (list cut short in the doc) | ||
| MV | 28098 | Occupancy Status Display | Read | 0=Occupied, 1=UnOccupied, 2=Standby, 3=Not Set | ||
| MV | 28099 | Fan Speed Request | Read | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High | ||
| AV | 28110 | Network/Zone Sensor Setpoint | Range 10 to 40°C (50 to 104°F) | °C/°F | Read | |
| AV | 28111 | Active Setpoint | Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Write | |
| AV | 28112 | Zone Temperature Setpoint Alternate | Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Read | |
| AV | 28113 | Heating Percent Cmd | Range 0 to 100% | % | Read | |
| AV | 28127 | Cooling Percent Cmd | Range 0 to 100% | % | Read | |
| MV | 28100 | Heating Control Status | Read | 0=Normal, 1=Low, 2=Timing Low, 3=High, ... (list cut short in the doc) | ||
| AV | 28114 | Limited Max Heating Value | Range 0 to 100% | % | Write | |
| MV | 28101 | Heating Mode | Read | 0=Off, 1=Max, 2=Limited Max, 3=Hold, ... (list cut short in the doc) | ||
| AV | 28115 | Heating Valve AO | Range 0 to 100% | % | Read | |
| AV | 28116 | Heating Setpoint | Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| MV | 28102 | Heating Adaptive Tuning Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28103 | Heating Manual Tuning | Write | 0=Yes, 1=No | ||
| AV | 28117 | Heat Prop Band | Range 1 to 200 | Write | ||
| AV | 28118 | Heat Integral Time | Range 0 to 1800 seconds | s | Write | |
| AV | 28119 | Heat Saturation Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28120 | Heat Process Range | Range 0 to 1800 | Write | ||
| AV | 28121 | Heat Time Constant | Range 1 to 1800 seconds | s | Write | |
| AV | 28122 | Heat Period | Range 0 to 1800 seconds | s | Write | |
| MV | 28104 | Heating Process ID | Write | 0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, ... (list cut short in the doc) | ||
| AV | 28123 | Heat Process Dead Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28124 | Heating Proportional Min Out Value | Range 0 to 100% | % | Write | |
| AV | 28125 | Heating Proportional Max Out Value | Range 0 to 100% | % | Write | |
| AV | 28126 | 6-Way Valve AO | Range 0 to 100% | % | Read | |
| MV | 28105 | 6-Way Valve Control | Write | 0=Heating/Cooling, 1=Cooling/Heating | ||
| MV | 28106 | Cooling Control Status | Read | 0=Normal, 1=Low, 2=Timing Low, 3=High, ... (list cut short in the doc) | ||
| AV | 28128 | Cooling Setpoint | Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| AV | 28129 | Limited Max Cooling Value | Range 10 to 100% | % | Write | |
| AV | 28130 | Cooling Valve AO | Range 0 to 100% | % | Read | |
| MV | 28107 | Cooling Mode | Read | 0=Off, 1=Max, 2=Limited Max, 3=Hold, ... (list cut short in the doc) | ||
| MV | 28108 | Cooling Adaptive Tuning Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28109 | Cooling Manual Tuning | Write | 0=Yes, 1=No | ||
| AV | 28131 | Cool Prop Band | Range 1 to 200 | Write | ||
| AV | 28132 | Cool Integral Time | Range 0 to 1800 seconds | s | Write | |
| AV | 28133 | Cool Saturation Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28134 | Cool Process Range | Range 0 to 1800 | Write | ||
| AV | 28135 | Cool Time Constant | Range 1 to 1800 seconds | s | Write | |
| AV | 28136 | Cool Process Dead Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28137 | Cool Period | Range 0 to 1800 seconds | s | Write | |
| MV | 28110 | Cool Process ID | Write | 0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, ... (list cut short in the doc) | ||
| AV | 28138 | Cooling Proportional Min Out Value | Range 0 to 100% | % | Write | |
| AV | 28139 | Cooling Proportional Max Out Value | Range 0 to 100% | % | Write | |
| MV | 28113 | Damper | Read | 0=On/Off, 1=Floating | ||
| MV | 28114 | Fan Type | Read | 0=Constant Volume Fan, 1=Fixed Variable Fan | ||
| MV | 28115 | Valve | Read | 0=Staged, 1=Proportional | ||
| AV | 28140 | Application Details | Range 0 to 1000000000 | Read | ||
| AV | 28141 | Application Name | Range 0 to 10000 | Read | ||
| MV | 28117 | Fan Cycling | Write | 0=No, 1=Yes | ||
| AV | 28142 | Fan On Threshold | Range 0 to 100% | % | Write | |
| AV | 28143 | Fan Off Threshold | Range 0 to 100% | % | Write | |
| AV | 28144 | Heating Purge Duration | Range 0 to 1800 seconds | s | Write | |
| MV | 28118 | Fan State | Read | 0=Off, 1=On | ||
| MV | 28119 | Off During Unoccupied | Write | 0=False, 1=True, 2=Hold | ||
| MV | 28120 | Cooling Fan Required | Write | 0=No, 1=Yes | ||
| MV | 28121 | Heating Fan Required | Write | 0=No, 1=Yes | ||
| MV | 28122 | Fan Speed Override | Write | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High | ||
| MV | 28123 | Eff Fan Speed Cmd | Read | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High | ||
| AV | 28145 | Electric Heat DAO | Range 0 to 100% | % | Read | |
| AV | 28146 | Aux Heat Setpoint | Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| MV | 28124 | Reheat Control Status | Read | 0=Normal, 1=Low, 2=Timing Low, 3=High, ... (list cut short in the doc) | ||
| AV | 28147 | Reheat Percent Cmd | Range 0 to 100% | % | Read | |
| AV | 28148 | Aux Heat Process Variable | Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| MV | 28125 | Reheat IsAvailable | Write | 0=No, 1=Yes | ||
| AV | 28149 | Electric Heat Cycle Time | Range 0 to 1200 seconds | s | Write | |
| AV | 28150 | High Threshold | Range 0 to 100% | % | Write | |
| AV | 28151 | Low Threshold | Range 0 to 100% | % | Write | |
| MV | 28126 | Reheat Mode | Read | 0=Off, 1=Max, 2=Limited Max, 3=Hold, ... (list cut short in the doc) | ||
| MV | 28127 | Aux Heat Adaptive Tuning Enable | Write | 0=False, 1=True, 2=Hold | ||
| MV | 28128 | Aux Heat Manual Tuning | Write | 0=Yes, 1=No | ||
| MV | 28129 | Aux Heat Process ID | Write | 0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, ... (list cut short in the doc) | ||
| AV | 28152 | Aux Heat Prop Band | Range 1 to 200 | Write | ||
| AV | 28153 | Aux Heat Integral Time | Range 0 to 1800 seconds | s | Write | |
| AV | 28154 | Aux Heat Saturation Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28155 | Aux Heat Process Range | Range 0 to 1800 | Write | ||
| AV | 28156 | Aux Heat Time Constant | Range 1 to 1800 seconds | s | Write | |
| AV | 28157 | Aux Heat Process Dead Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28158 | Aux Heat Period | Range 0 to 1800 seconds | s | Write | |
| AV | 28159 | Discharge Temperature AI | Range -45 to 120°C (-49 to 248°F) | °C/°F | Read | |
| AV | 28160 | Zone CO2 Sensor AI | Range 0 to 2000 ppm | ppm | Read | |
| AV | 28161 | DAT Sensor Offset | Range -45 to 120°C (-49 to 248°F) | °C/°F | Write | |
| MV | 29992 | Fan Test | Write | 0=Off, 1=Low, 2=Medium, 3=High |
No points match these filters.
Object ID lookup: Johnson Controls ATC1500 App #4004 point IDs by name
MV28000Unit StatusMV28001Application Tuning ResetMV28002Unit Enable ModeMV28003Occupied StateMV28004Unoccupied StateMV28006System ModeMV28007Effective HVAC ModeMV28008Device StatusMV28009Firmware StatusAV28000N2 AddressAV28001Modbus AddressAV28002MSTP Device AddressAV28003Device Object IDMV28010FC Comm ModeMV28011Communication StatusMV28012FCB Baud RateMV28013Operating Baud RateMV28014BACnet Encoding TypeMV28015Time ZoneMV28016UnitsMV28017Relearn SystemMV28018Provider NameMV28019Fan Speed 1 BOMV28020Fan Speed 2 BOMV28021Fan Speed 3 BOMV28022Number of SpeedsMV28023Fan Speed StatusMV28024Fan OnOffMV28039Damper StateAV28030Damper Maximum PositionAV28031Damper Minimum PositionAV28162Damper Stroke TimeAV28032Damper Percent CmdMV28040Damper OpenCloseAV28033CO2 Prop BandMV28041OA Damper BOMV28043Damper PolarityAV28035Return CO2 Sensor OffsetMV28044IAQMV28045Occupancy OverrideMV28046Occupancy ScheduleMV28047Effective OccupancyAV28036Bypass TimeAV28037Off DelayMV28048Temporary OccupancyMV28049FDD EnableAV28038Start DelayAV28039Insufficient Htg Cap Sat DelayAV28040Insufficient Htg Cap Zone Max ErrorAV28041Insufficient Clg Cap Zone Max ErrorAV28042Low Zone Temp Zone Max ErrorAV28043High Zone Temp Zone Max ErrorAV28044ZN Spt Out Of Comfort Lim Min T SptAV28045ZN Spt Out Of Comfort Lim Max T SptAV28046Setpoint Compensation Winter Max DiffAV28047Setpoint Compensation Summer Max DiffAV28048Insufficient Clg Cap Sat DelayMV28050FDDAV28049Simultaneous HtgClg Zone Max ErrorAV28050DAT Not Responding Htg Threshold TempAV28051DAT Not Responding Clg Threshold TempMV28051Window Open While Occupied FaultMV28052Window Open While Unoccupied FaultMV28053Insufficient Cooling Capacity FaultMV28054Insufficient Heating Capacity FaultMV28055Zone Spt Outside Comfort Limits FaultMV28056High Zone Temp FaultMV28057Low Zone Temp FaultMV28058Incorrect Setpoint Compensation FaultMV28059Simultaneous Htg and Clg FaultMV28060DAT Not Responding FaultAV28052Window Open In Occ In Fault TimeAV28053Window Open In Unocc In Fault TimeAV28054Low Zone Temp In Fault TimeAV28055High Zone Temp In Fault TimeAV28056Simultaneous Htg Clg In Fault TimeAV28057DAT Not Responding In Fault TimeMV28061Window Open In Occ Fault EnableMV28062Window Open In Unocc Fault EnableMV28063Insufficient Htg Cap Fault EnableMV28064Insufficient Clg Cap Fault EnableMV28065Low Zone Temp Fault EnableMV28066High Zone Temp Fault EnableMV28067Setpoint Compensation Fault EnableMV28068ZN Spt Out Of Comfort Lim Fault EnableMV28069Simultaneous Htg Clg Fault EnableMV28070DAT Not Responding Fault EnableAV28058ecoClgSetpointMV28071Energy IndicatorAV28059ecoHtgSetpointMV28072Energy Indication EnableMV28073Energy Indicator ResetAV28060ecoHtgSetpoint DiffAV28061ecoClgSetpoint DiffAV28062CO2 SetpointAV28063Unocc Cooling SetpointAV28064Unocc Heating SetpointAV28065Network SetpointAV28066Standby Cooling SetpointAV28067Standby Heating SetpointAV28068Freeze Stat SetpointAV28069Frost Protect DifferentialAV28070Effective Cooling SetpointAV28071Effective Heating SetpointAV28072DeadbandMV28074Spt SourceMV29990Space VoteAV28073Low RangeAV28074High RangeAV28075Low Range DiffAV28076High Range DiffAV28086Network Override Indoor Air QualityAV28087Operational Indoor Air QualityAV28088Network Override Outdoor Air TemperatureAV28089Network Override Zone TemperatureAV28090Operational Zone TemperatureAV28091Operational Outdoor Air TemperatureMV28079Condensate Alarm BIMV28080Window Status BIMV28081Occupancy Sensor BIMV28082Occupancy Sensor PolarityMV28083Window Contact PolarityMV28084Dew Point Contact PolarityMV28085Safety Tstat BIMV28086Safety Tstat PolarityAV28092Effective Cooling ShiftAV28093Effective Heating ShiftAV28094Winter SetpointAV28095Summer SetpointAV28096Summer Change LimitAV28097Winter Change LimitAV28098Summer GainAV28099Winter GainMV28087Start CommissionMV28088SF-C OvrdAV28100SF-O OvrdMV28089OAD-C OvrdAV28101OAD-O OvrdAV28102SuppHtg-O OvrdAV28104Heating Override CheckAV28105Cooling Override CheckAV28106Zone TemperatureAV28107CO2MV28096Zone Occupancy RequestAV28108Warmer/Cooler AdjustAV28109Setpoint OffsetMV28097Indoor Air Quality Sensor InstalledMV28098Occupancy Status DisplayMV28099Fan Speed RequestAV28110Network/Zone Sensor SetpointAV28111Active SetpointAV28112Zone Temperature Setpoint AlternateAV28113Heating Percent CmdAV28127Cooling Percent CmdMV28100Heating Control StatusAV28114Limited Max Heating ValueMV28101Heating ModeAV28115Heating Valve AOAV28116Heating SetpointMV28102Heating Adaptive Tuning EnableMV28103Heating Manual TuningAV28117Heat Prop BandAV28118Heat Integral TimeAV28119Heat Saturation TimeAV28120Heat Process RangeAV28121Heat Time ConstantAV28122Heat PeriodMV28104Heating Process IDAV28123Heat Process Dead TimeAV28124Heating Proportional Min Out ValueAV28125Heating Proportional Max Out ValueAV281266-Way Valve AOMV281056-Way Valve ControlMV28106Cooling Control StatusAV28128Cooling SetpointAV28129Limited Max Cooling ValueAV28130Cooling Valve AOMV28107Cooling ModeMV28108Cooling Adaptive Tuning EnableMV28109Cooling Manual TuningAV28131Cool Prop BandAV28132Cool Integral TimeAV28133Cool Saturation TimeAV28134Cool Process RangeAV28135Cool Time ConstantAV28136Cool Process Dead TimeAV28137Cool PeriodMV28110Cool Process IDAV28138Cooling Proportional Min Out ValueAV28139Cooling Proportional Max Out ValueMV28113DamperMV28114Fan TypeMV28115ValveAV28140Application DetailsAV28141Application NameMV28117Fan CyclingAV28142Fan On ThresholdAV28143Fan Off ThresholdAV28144Heating Purge DurationMV28118Fan StateMV28119Off During UnoccupiedMV28120Cooling Fan RequiredMV28121Heating Fan RequiredMV28122Fan Speed OverrideMV28123Eff Fan Speed CmdAV28145Electric Heat DAOAV28146Aux Heat SetpointMV28124Reheat Control StatusAV28147Reheat Percent CmdAV28148Aux Heat Process VariableMV28125Reheat IsAvailableAV28149Electric Heat Cycle TimeAV28150High ThresholdAV28151Low ThresholdMV28126Reheat ModeMV28127Aux Heat Adaptive Tuning EnableMV28128Aux Heat Manual TuningMV28129Aux Heat Process IDAV28152Aux Heat Prop BandAV28153Aux Heat Integral TimeAV28154Aux Heat Saturation TimeAV28155Aux Heat Process RangeAV28156Aux Heat Time ConstantAV28157Aux Heat Process Dead TimeAV28158Aux Heat PeriodAV28159Discharge Temperature AIAV28160Zone CO2 Sensor AIAV28161DAT Sensor OffsetMV29992Fan Test
Integration notes
- Objects from the BACnet and N2 bus points table on pages 48-59 of the application note (LIT-12013091).
- All objects are analog values (AV) or multistate values (MV); physical inputs and outputs show up as MV/AV status points. Access W means the table marks the object Writeable; multistate states keep the 0-based numbers printed in the note.
- For 18 multistate objects the note prints only the first states and then '...'; the full sets are in Metasys System Enumeration Sets (LIT-12011361).
- Application #4003 prints the same table except for the damper output: this one has MV 28041 OA Damper BO, MV 28043 Damper Polarity; #4003 has AV 28034 OA Damper PAO, MV 28042 Damper Polarity.
- Units come from the range column: temperatures follow the controller Units setting (MV 28016, default SI so °C).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
How many BACnet points does the Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper) have?
This list has 229 BACnet objects: 126 analog values, 103 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper) BACnet points are writable?
151 of the 229 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper) BACnet documentation?
The source is Advanced Terminal Unit Controller Application Note - Application #4004 (LIT-12013091), revision April 2023, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/jYVlE_He_qVLYsjY~BqXRA/content.
What are the minimum BACnet points to integrate the Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)?
Start with MV 28002 Unit Enable Mode (Unit on/off: 0=Shutdown, 1=Enable); MV 28046 Occupancy Schedule (Occupancy from the BAS schedule); MV 28006 System Mode (Mode command (cool only, heat only, fan only...)); AV 28065 Network Setpoint (Zone setpoint written by the BAS, °C/°F); MV 28000 Unit Status (Heat, cool, fan only, satisfied or off); MV 28047 Effective Occupancy (Occupancy in effect); AV 28090 Operational Zone Temperature (Zone temperature in use, °C/°F); MV 28023 Fan Speed Status (Fan speed: 0=Off, 1=Low, 2=Medium, 3=High); MV 28079 Condensate Alarm BI (Condensate alarm input: 0=Normal, 1=Alarm).
How do I enable BMS control of the Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)?
Unit Enable Mode (Shutdown or Enable, default Enable) turns the unit off or on. Effective occupancy follows Occupancy Override first, then the bypass timer, Occupancy Schedule and the occupancy sensor. System Mode is the writable mode command (cool only, heat only, fan only and others).
Can the BMS supply sensor values to the Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)?
With Spt Source at Network Input (the default) the zone setpoint comes from Network Setpoint (default 22 °C). Network Override Zone Temperature, Network Override Outdoor Air Temperature and Network Override Indoor Air Quality are writable network inputs; a network CO2 value takes priority over the local sensor, and summer-winter setpoint compensation only works with a reliable network outdoor air temperature.
How do I check these points on the real ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: Advanced Terminal Unit Controller Application Note - Application #4004 · LIT-12013091 · rev. April 2023. Object names, instances and units are reproduced as published; descriptions are our own.