Fan-powered VAV terminal unit controller · BACnet points list

Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan) BACnet points list

Updated 4 November 2026

Short answer

Application 1732-8 (Incr HW Reheat Var Speed Series Fan) is one of the ten preloaded applications in the Johnson Controls VAV1732 controller, which has a built-in damper actuator and velocity pressure sensor and runs on BACnet MS/TP. It controls a series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve. Points cover occupancy and unit enable, temperature and airflow setpoints, zone sensors, airflow in L/s, CFM and CMH, damper output, the reheat valve output, the fan command and the loop and state diagnostics.

This page lists 97 BACnet objects for the Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan) — 41 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.

Manufacturer
Johnson Controls
Model
VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
Equipment
Fan-powered VAV terminal unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
97 (41 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan
Source document
VAV1717 and VAV1732 VAV Controllers Application Note · LIT-12013794 · rev. 2021-08-09
Download CSV 97 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.

BMS integration notes: Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)

Integration in brief

Set the MS/TP address on the DIP switches, load the 1732-8 application, then enable the unit with UNITEN-MODE, drive occupancy through OCC-SCHEDULE and write the occupied setpoints. Read zone temperature, effective occupancy, airflow and damper output plus the heat and fan commands.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 77UNITEN-MODEUnit enable: Shutdown or EnableWrite
MV 59OCC-SCHEDULEOccupancy from the BAS scheduleWrite
AV 3474CLGOCC-SPOccupied cooling setpoint, °CWrite
AV 3475HTGOCC-SPOccupied heating setpoint, °CWrite
MV 3290EFF-OCCOccupancy in effectRead
AV 277998ZN-TZone temperature, °CRead
AV 3515SA-FSupply airflow, L/sRead
AO 2131DPR-ODamper output, %Read
AO 2015HTG-OHeating valve output, %Read
BO 2045SF-CBox fan on/off outputRead

Enable & remote start

UNITEN-MODE (Shutdown or Enable, default Enable) turns the box on or off. Occupancy comes from OCC-SCHEDULE (Occupied, Unoccupied, Standby or Not Set) written by the supervisory schedule; OCC-OVERRIDE overrides it, and EFF-OCC shows the result. SYSTEM-MODE (default Auto) can force cool only, heat only, fan only, water flush or purge.

Sensors & values from the BMS

SA-T (writable, default 13 °C) is the supply air temperature used for automatic warmup: warmup starts when SA-T and ZN-T are reliable and SA-T exceeds ZN-T plus WCT-DIFF; otherwise the BAS can command warmup with WC-C. With ZONE SETPOINT SOURCE set to Remote, the box uses BAS ZN-SP instead of the sensor setpoint.

Network setup

Watch out for

Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

97 of 97 shown
Type
Multi-state
Access
Show
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan) BACnet Points List
DescriptionStates
AI1094DA-VPDischarge air velocity pressurePaRead
AI278061ZN-CO2Netsensor zone CO2ppmRead
AI278064ZN-HNetsensor zone humidity%RHRead
AV1103ZN-SP-NSNetsensor zone setpoint°CRead
AI277988ZN-SP-TE730TE730 zone setpoint°CRead
AI1106ZN-T-NSNetsensor zone temperature°CRead
AI277994ZN-T-TE730TE730 zone temperature°CRead
BV1105ZN-TOCC-NSNetsensor zone temporary occupancy; default InactiveReadInactive, Active
BI277991ZN-TOCC-TE730TE730 zone temporary occupancy; default InactiveReadInactive, Active
AOmin2131DPR-OSupply air damper output%Read
MV2086OCC-MODEOccupancy status displayRead
AOmin2015HTG-OHeating output%Read
BOmin2045SF-CSupply fan commandRead
AO2049SF-OSupply fan output%Read
AV4174HTG-ABSEFFORTHeating absolute effort%Read
AV4173HTG-ABSERRORHeating absolute error°CRead
AV4175HTG-ERRORHeating error°CRead
AV4176HTG-EWMAHeating exponentially weighted moving average%Read
MV3309HTG-OUTSTATEHeating output stateReadOff, Max, Limited Max, Hold, Water Flush, Control, Failsoft
MV3341FAN-OUTSTATEFan output stateReadOff, On, Hold
AV78179FAN-SPEEDFan speed%Read
MV3385SAD-OUTSTATESupply air damper output stateReadBypass, Hold, Control Flow Unreliable, Control Flow Reliable
AV4410SAFLOW-ABSEFFORTSupply airflow absolute effort%Read
AV4409SAFLOW-ABSERRORSupply airflow absolute errorL/sRead
AV4411SAFLOW-ERRORSupply airflow errorL/sRead
AV4412SAFLOW-EWMASupply airflow exponentially weighted moving average%Read
AV3384SAFLOW-SPSupply airflow setpoint; default 0.0 L/sL/sWrite
AV5715SPMAXPOSSupply air damper maximum position; default 80%%Write
AV4246CLG-ABSEFFORTCooling absolute effort%Read
AV4245CLG-ABSERRORCooling absolute error°CRead
AV4247CLG-ERRORCooling error°CRead
AV4248CLG-EWMACooling exponentially weighted moving average%Read
AV3615CLG-OCooling output%Read
MV3387SAFLOW-OUTSTATESupply airflow output stateReadMin, Max, Hold, Control, Heating, Warmup, Failsoft
MV278018MIN FLOW RESET TYPEMinimum flow reset type; default NoneWriteNone, CO2
AV3266CLDWN-MINFLOWCooldown minimum flow; default 100 L/sL/sWrite
AV3267CLG-MINFLOWCooling minimum flowL/sRead
AV3272CLGUNOCC-MINFLOWUnoccupied cooling minimum flow; default 0 L/sL/sWrite
AV3268HTG-MINFLOWHeating minimum flowL/sRead
AV3273HTGUNOCC-MINFLOWUnoccupied heating minimum flow; default 100 L/sL/sWrite
AV3270MINFLOWCO2-PBCO2 minimum flow proportional band; default 400 ppmppmWrite
AV3271MINFLOWCO2-SPCO2 minimum flow setpoint; default 700 ppmppmWrite
AV3269OCC-LEVELOccupancy level; default 0Write
AV3274WU-MINFLOWWarmup minimum flow; default 100 L/sL/sWrite
MVmin3290EFF-OCCEffective occupancy; default OccupiedReadOccupied, Unoccupied, Bypass, Standby
AV3289OCCMODE-BYPASSTIMEOccupancy mode bypass time; default 3600 ssWrite
AV5871PRESS-REQZone pressure requestRead
AV3386SAD-STSupply air damper stroke time; default 60 ssWrite
AVmin3515SA-FSupply air flowL/sRead
AV5869CLG-REQZone cooling requestRead
AV5870HTG-REQZone heating requestRead
MV3468WC-SWarmup cooldown status; default NormalReadNormal, Warmup, Cooldown, Coast
AV3469WCT-DIFFWarmup cooldown temperature differential; default 8°C°CWrite
AVmin3474CLGOCC-SPOccupied cooling setpoint; default 23°C°CWrite
AV3478CLGUNOCC-SPUnoccupied cooling setpoint; default 28°C°CWrite
AV3476CLGSTBY-SPStandby cooling setpoint; default 25°C°CWrite
AV3472EFFCLG-SPEffective cooling setpoint°CRead
AV3473EFFHTG-SPEffective heating setpoint°CRead
AVmin3475HTGOCC-SPOccupied heating setpoint; default 21°C°CWrite
AV3477HTGSTBY-SPStandby heating setpoint; default 19°C°CWrite
AV3479HTGUNOCC-SPUnoccupied heating setpoint; default 16°C°CWrite
MV3091AUTOCAL-STATEAutocalibration stateReadUncalibrated, Waiting to Calibrate, Waiting for Damper, Autocalibrate, Normal
AV3108CLG-MAXFLOWCooling maximum flow; default 500 L/sL/sWrite
AV3109CLGOCC-MINFLOWOccupied cooling minimum flow; default 100 L/sL/sWrite
AV3110HTGOCC-MINFLOWOccupied heating minimum flow; default 100 L/sL/sWrite
AV3111SA-AREASupply air box area; default 0.032 m²m²Write
AV3112SA-KFACTORSupply air pickup gain; default 2Write
MV3466ZNT-STATEZone temperature state; default SatisfiedReadSatisfied, Supp Htg, Supp Htg + Box Htg, Box Htg + Supp Htg, Prmy Clg, Temperature Unreliable
MV3343FAN-STATEFan stateReadOff, On
AV3342HTG-PURGETIMEHeating purge time; default 120 ssWrite
BV3391PFRESTART-ENPower fail restart enable; default TRUEWrite
AV3392PFRESTART-TIMEPower fail restart time; default 60 ssWrite
MV3393UNITEN-STATEUnit enable stateReadShutdown, Enable
AV3450UNOCC-SATTIMEUnoccupied saturation time; default 300 ssWrite
MV3452UNOCC-STATEUnoccupied stateReadSatisfied, Prmy Clg, Supp Htg, Box Htg, Box Htg + Supp Htg, Temperature Unreliable, Unocc Ctrl Not Req'd
MV3471WC-STATEWarmup cooldown stateReadNormal, Warmup Satisfied, Warmup Unreliable, Cooldown, Cooldown Unreliable, Prmy Htg, Prmy Htg + Supp Htg, Prmy Htg + Supp Htg + Box Htg, Prmy Htg + Box Htg, Prmy Htg + Box Htg + Supp Htg, Coast
BV4AUTOCAL-CAutocalibration command; default FALSERead
AV277985BAS-ZN-SPBAS zone setpoint; default 25°C°CWrite
AV27FLUSHPOSFlush position; default 100%%Write
BV7HTG-ENHeating enable; default TRUEWrite
MV58OCC-OVERRIDEOccupancy override; default Not SetWriteOccupied, Unoccupied, Bypass, Standby, Not Set
MVmin59OCC-SCHEDULEOccupancy schedule; default Not SetWriteOccupied, Unoccupied, Standby, Not Set
AV75SA-TSupply air temperature; default 13°C°CWrite
MV76SYSTEM-MODESystem mode; default AutoWriteCool Only, Heat Only, Fan Only, Water Flush, Purge, Auto
BV769TUNING-RESETPID tuning reset; default FALSEWrite
MVmin77UNITEN-MODEUnit enable mode; default EnableWriteShutdown, Enable
MV80WC-CWarmup cooldown command; default NormalWriteNormal, Warmup, Cooldown, Coast
MV277984ZONE SETPOINT SOURCEZone setpoint source; default LocalWriteLocal, Remote
AV25270CLG-REQ SRCCooling request sourceRead
AV277997EFFECTIVE-ZN-SPEffective zone setpoint°CRead
AV25269PRESS-REQ SRCZone pressure request sourceRead
AV277999SA-F-CFMSupply airflow in cubic feet per minuteCFMRead
AV278000SA-F-CMHSupply airflow in cubic meters per hourCMHRead
AV278001SA-F-L/SSupply airflow in liters per secondL/sRead
AVmin277998ZN-TZone temperature°CRead
AV278002ZN-T OFFSET (NS)Zone temperature offset for Netsensor; default 0Δ°CWrite
AV278003ZN-T OFFSET (TE730)Zone temperature offset for TE730; default 0Δ°CWrite
Object ID lookup: Johnson Controls VAV1732 App 1732-8 Incr HW Reheat Var Speed Series Fan point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)

How many BACnet points does the Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan) have?

This list has 97 BACnet objects: 6 analog inputs, 3 analog outputs, 61 analog values, 1 binary input, 1 binary output, 5 binary values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan) BACnet points are writable?

41 of the 97 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan) BACnet documentation?

The source is VAV1717 and VAV1732 VAV Controllers Application Note (LIT-12013794), revision 2021-08-09, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/1A9bXr239BVM1oXYaNZBSA/content.

What are the minimum BACnet points to integrate the Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)?

Start with MV 77 UNITEN-MODE (Unit enable: Shutdown or Enable); MV 59 OCC-SCHEDULE (Occupancy from the BAS schedule); AV 3474 CLGOCC-SP (Occupied cooling setpoint, °C); AV 3475 HTGOCC-SP (Occupied heating setpoint, °C); MV 3290 EFF-OCC (Occupancy in effect); AV 277998 ZN-T (Zone temperature, °C); AV 3515 SA-F (Supply airflow, L/s); AO 2131 DPR-O (Damper output, %); AO 2015 HTG-O (Heating valve output, %); BO 2045 SF-C (Box fan on/off output).

How do I enable BMS control of the Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)?

UNITEN-MODE (Shutdown or Enable, default Enable) turns the box on or off. Occupancy comes from OCC-SCHEDULE (Occupied, Unoccupied, Standby or Not Set) written by the supervisory schedule; OCC-OVERRIDE overrides it, and EFF-OCC shows the result. SYSTEM-MODE (default Auto) can force cool only, heat only, fan only, water flush or purge.

Can the BMS supply sensor values to the Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)?

SA-T (writable, default 13 °C) is the supply air temperature used for automatic warmup: warmup starts when SA-T and ZN-T are reliable and SA-T exceeds ZN-T plus WCT-DIFF; otherwise the BAS can command warmup with WC-C. With ZONE SETPOINT SOURCE set to Remote, the box uses BAS ZN-SP instead of the sensor setpoint.

How do I check these points on the real VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Johnson Controls BACnet points lists

Source: VAV1717 and VAV1732 VAV Controllers Application Note · LIT-12013794 · rev. 2021-08-09. Object names, instances and units are reproduced as published; descriptions are our own.