VAV terminal unit controller · BACnet points list

Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat) BACnet points list

Updated 4 November 2026

Short answer

Application 1717-4 (Incr HW Reheat) is one of the ten preloaded applications in the Johnson Controls VAV1717 controller, which has a built-in damper actuator and velocity pressure sensor and runs on BACnet MS/TP. It controls a single-duct VAV box with an incremental (floating) hot water reheat valve. Points cover occupancy and unit enable, temperature and airflow setpoints, zone sensors, airflow in L/s, CFM and CMH, damper output, the reheat valve output and the loop and state diagnostics.

This page lists 91 BACnet objects for the Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat) — 40 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.

Manufacturer
Johnson Controls
Model
VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
Equipment
VAV terminal unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
91 (40 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat
Source document
VAV1717 and VAV1732 VAV Controllers Application Note · LIT-12013794 · rev. 2021-08-09
Download CSV 91 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.

BMS integration notes: Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)

Integration in brief

Set the MS/TP address on the DIP switches, load the 1717-4 application, then enable the unit with UNITEN-MODE, drive occupancy through OCC-SCHEDULE and write the occupied setpoints. Read zone temperature, effective occupancy, airflow and damper output plus the heat command.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 77UNITEN-MODEUnit enable: Shutdown or EnableWrite
MV 59OCC-SCHEDULEOccupancy from the BAS scheduleWrite
AV 3474CLGOCC-SPOccupied cooling setpoint, °CWrite
AV 3475HTGOCC-SPOccupied heating setpoint, °CWrite
MV 3290EFF-OCCOccupancy in effectRead
AV 278004ZN-TZone temperature, °CRead
AV 3515SA-FSupply airflow, L/sRead
AO 2131DPR-ODamper output, %Read
AO 2015HTG-OHeating valve output, %Read

Enable & remote start

UNITEN-MODE (Shutdown or Enable, default Enable) turns the box on or off. Occupancy comes from OCC-SCHEDULE (Occupied, Unoccupied, Standby or Not Set) written by the supervisory schedule; OCC-OVERRIDE overrides it, and EFF-OCC shows the result. SYSTEM-MODE (default Auto) can force cool only, heat only, fan only, water flush or purge.

Sensors & values from the BMS

SA-T (writable, default 13 °C) is the supply air temperature used for automatic warmup: warmup starts when SA-T and ZN-T are reliable and SA-T exceeds ZN-T plus WCT-DIFF; otherwise the BAS can command warmup with WC-C. With ZONE SETPOINT SOURCE set to Remote, the box uses BAS ZN-SP instead of the sensor setpoint.

Network setup

Watch out for

Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

91 of 91 shown
Type
Multi-state
Access
Show
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat) BACnet Points List
DescriptionStates
AI1094DA-VPDischarge air velocity pressurePaRead
AI277993ZN-CO2Netsensor zone CO2ppmRead
AI278084ZN-HNetsensor zone humidity%RHRead
AV1103ZN-SP-NSNetsensor zone setpoint°CRead
AI277984ZN-SP-TE730TE730 zone setpoint°CRead
AI1106ZN-T-NSNetsensor zone temperature°CRead
AI277990ZN-T-TE730TE730 zone temperature°CRead
BV1105ZN-TOCC-NSNetsensor zone temporary occupancy; default InactiveReadInactive, Active
BI277987ZN-TOCC-TE730TE730 zone temporary occupancy; default InactiveReadInactive, Active
AOmin2131DPR-OSupply air damper output%Read
MV2086OCC-MODEOccupancy status displayRead
AOmin2015HTG-OHeating output%Read
AV4174HTG-ABSEFFORTHeating absolute effort%Read
AV4173HTG-ABSERRORHeating absolute error°CRead
AV4175HTG-ERRORHeating error°CRead
AV4176HTG-EWMAHeating exponentially weighted moving average%Read
MV3309HTG-OUTSTATEHeating output stateReadOff, Max, Limited Max, Hold, Water Flush, Control, Failsoft
MV3385SAD-OUTSTATESupply air damper output stateReadBypass, Hold, Control Flow Unreliable, Control Flow Reliable
AV4410SAFLOW-ABSEFFORTSupply airflow absolute effort%Read
AV4409SAFLOW-ABSERRORSupply airflow absolute errorL/sRead
AV4411SAFLOW-ERRORSupply airflow errorL/sRead
AV4412SAFLOW-EWMASupply airflow exponentially weighted moving average%Read
AV3384SAFLOW-SPSupply airflow setpoint; default 0.0 L/sL/sWrite
AV5715SPMAXPOSSupply air damper maximum position; default 80%%Write
AV4246CLG-ABSEFFORTCooling absolute effort%Read
AV4245CLG-ABSERRORCooling absolute error°CRead
AV4247CLG-ERRORCooling error°CRead
AV4248CLG-EWMACooling exponentially weighted moving average%Read
AV3615CLG-OCooling output%Read
MV3387SAFLOW-OUTSTATESupply airflow output stateReadMin, Max, Hold, Control, Heating, Warmup, Failsoft
MV278083MIN FLOW RESET TYPEMinimum flow reset type; default NoneWriteNone, CO2
AV3266CLDWN-MINFLOWCooldown minimum flow; default 100 L/sL/sWrite
AV3267CLG-MINFLOWCooling minimum flowL/sRead
AV3272CLGUNOCC-MINFLOWUnoccupied cooling minimum flow; default 0 L/sL/sWrite
AV3268HTG-MINFLOWHeating minimum flowL/sRead
AV3273HTGUNOCC-MINFLOWUnoccupied heating minimum flow; default 100 L/sL/sWrite
AV3270MINFLOWCO2-PBCO2 minimum flow proportional band; default 400 ppmppmWrite
AV3271MINFLOWCO2-SPCO2 minimum flow setpoint; default 700 ppmppmWrite
AV3269OCC-LEVELOccupancy level; default 0Write
AV3274WU-MINFLOWWarmup minimum flow; default 100 L/sL/sWrite
MVmin3290EFF-OCCEffective occupancy; default OccupiedReadOccupied, Unoccupied, Bypass, Standby
AV3289OCCMODE-BYPASSTIMEOccupancy mode bypass time; default 3600 ssWrite
AV5871PRESS-REQZone pressure requestRead
AV3386SAD-STSupply air damper stroke time; default 60 ssWrite
AVmin3515SA-FSupply air flowL/sRead
AV5869CLG-REQZone cooling requestRead
AV5870HTG-REQZone heating requestRead
MV3468WC-SWarmup cooldown status; default NormalReadNormal, Warmup, Cooldown, Coast
AV3469WCT-DIFFWarmup cooldown temperature differential; default 8°C°CWrite
AVmin3474CLGOCC-SPOccupied cooling setpoint; default 23°C°CWrite
AV3476CLGSTBY-SPStandby cooling setpoint; default 25°C°CWrite
AV3478CLGUNOCC-SPUnoccupied cooling setpoint; default 28°C°CWrite
AV3472EFFCLG-SPEffective cooling setpoint°CRead
AV3473EFFHTG-SPEffective heating setpoint°CRead
AVmin3475HTGOCC-SPOccupied heating setpoint; default 21°C°CWrite
AV3477HTGSTBY-SPStandby heating setpoint; default 19°C°CWrite
AV3479HTGUNOCC-SPUnoccupied heating setpoint; default 16°C°CWrite
MV3091AUTOCAL-STATEAutocalibration stateReadUncalibrated, Waiting to Calibrate, Waiting for Damper, Autocalibrate, Normal
AV3108CLG-MAXFLOWCooling maximum flow; default 500 L/sL/sWrite
AV3109CLGOCC-MINFLOWOccupied cooling minimum flow; default 100 L/sL/sWrite
AV3110HTGOCC-MINFLOWOccupied heating minimum flow; default 100 L/sL/sWrite
AV3111SA-AREASupply air box area; default 0.032 m²m²Write
AV3112SA-KFACTORSupply air pickup gain; default 2Write
MV3466ZNT-STATEZone temperature state; default SatisfiedReadSatisfied, Supp Htg, Supp Htg + Box Htg, Box Htg + Supp Htg, Prmy Clg, Temperature Unreliable
BV3391PFRESTART-ENPower fail restart enable; default TRUEWrite
AV3392PFRESTART-TIMEPower fail restart time; default 60 ssWrite
MV3393UNITEN-STATEUnit enable stateReadShutdown, Enable
AV3450UNOCC-SATTIMEUnoccupied saturation time; default 300 ssWrite
MV3452UNOCC-STATEUnoccupied stateReadSatisfied, Prmy Clg, Supp Htg, Box Htg, Box Htg + Supp Htg, Temperature Unreliable, Unocc Ctrl Not Req'd
MV3471WC-STATEWarmup cooldown stateReadNormal, Warmup Satisfied, Warmup Unreliable, Cooldown, Cooldown Unreliable, Prmy Htg, Prmy Htg + Supp Htg, Prmy Htg + Supp Htg + Box Htg, Prmy Htg + Box Htg, Prmy Htg + Box Htg + Supp Htg, Coast
BV4AUTOCAL-CAutocalibration command; default FALSERead
AV277997BAS-ZN-SPBAS zone setpoint; default 25°C°CWrite
AV27FLUSHPOSFlush position; default 100%%Write
BV7HTG-ENHeating enable; default TRUEWrite
MV58OCC-OVERRIDEOccupancy override; default Not SetWriteOccupied, Unoccupied, Bypass, Standby, Not Set
MVmin59OCC-SCHEDULEOccupancy schedule; default Not SetWriteOccupied, Unoccupied, Standby, Not Set
AV75SA-TSupply air temperature; default 13°C°CWrite
MV76SYSTEM-MODESystem mode; default AutoWriteCool Only, Heat Only, Fan Only, Water Flush, Purge, Auto
BV769TUNING-RESETPID tuning reset; default FALSEWrite
MVmin77UNITEN-MODEUnit enable mode; default EnableWriteShutdown, Enable
MV80WC-CWarmup cooldown command; default NormalWriteNormal, Warmup, Cooldown, Coast
MV277996ZONE SETPOINT SOURCEZone setpoint source; default LocalWriteLocal, Remote
AV25270CLG-REQ SRCCooling request sourceRead
AV278000EFFECTIVE-ZN-SPEffective zone setpoint°CRead
AV25269PRESS-REQ SRCZone pressure request sourceRead
AV278002SA-F-CFMSupply airflow in cubic feet per minuteCFMRead
AV278003SA-F-CMHSupply airflow in cubic meters per hourCMHRead
AV278001SA-F-L/SSupply airflow in liters per secondL/sRead
AVmin278004ZN-TZone temperature°CRead
AV278005ZN-T OFFSET (NS)Zone temperature offset for Netsensor; default 0Δ°CWrite
AV278006ZN-T OFFSET (TE730)Zone temperature offset for TE730; default 0Δ°CWrite
Object ID lookup: Johnson Controls VAV1717 App 1717-4 Incr HW Reheat point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)

How many BACnet points does the Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat) have?

This list has 91 BACnet objects: 6 analog inputs, 2 analog outputs, 59 analog values, 1 binary input, 5 binary values, 18 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat) BACnet points are writable?

40 of the 91 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat) BACnet documentation?

The source is VAV1717 and VAV1732 VAV Controllers Application Note (LIT-12013794), revision 2021-08-09, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/1A9bXr239BVM1oXYaNZBSA/content.

What are the minimum BACnet points to integrate the Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)?

Start with MV 77 UNITEN-MODE (Unit enable: Shutdown or Enable); MV 59 OCC-SCHEDULE (Occupancy from the BAS schedule); AV 3474 CLGOCC-SP (Occupied cooling setpoint, °C); AV 3475 HTGOCC-SP (Occupied heating setpoint, °C); MV 3290 EFF-OCC (Occupancy in effect); AV 278004 ZN-T (Zone temperature, °C); AV 3515 SA-F (Supply airflow, L/s); AO 2131 DPR-O (Damper output, %); AO 2015 HTG-O (Heating valve output, %).

How do I enable BMS control of the Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)?

UNITEN-MODE (Shutdown or Enable, default Enable) turns the box on or off. Occupancy comes from OCC-SCHEDULE (Occupied, Unoccupied, Standby or Not Set) written by the supervisory schedule; OCC-OVERRIDE overrides it, and EFF-OCC shows the result. SYSTEM-MODE (default Auto) can force cool only, heat only, fan only, water flush or purge.

Can the BMS supply sensor values to the Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)?

SA-T (writable, default 13 °C) is the supply air temperature used for automatic warmup: warmup starts when SA-T and ZN-T are reliable and SA-T exceeds ZN-T plus WCT-DIFF; otherwise the BAS can command warmup with WC-C. With ZONE SETPOINT SOURCE set to Remote, the box uses BAS ZN-SP instead of the sensor setpoint.

How do I check these points on the real VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Johnson Controls BACnet points lists

Source: VAV1717 and VAV1732 VAV Controllers Application Note · LIT-12013794 · rev. 2021-08-09. Object names, instances and units are reproduced as published; descriptions are our own.