  4. ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)

Fan coil unit controller · BACnet points list

Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper) BACnet points list

Updated 6 November 2026

Short answer

Application #2007 is one of the fan coil applications for the Johnson Controls ATC1100 (2 UI, 2 BI, 2 BO, 3 RO, 2 CO) Advanced Terminal Unit Controller, which connects over BACnet MS/TP (it can also run N2 or Modbus). It drives a two-pipe fan coil with on/off valve control, a variable-speed fan and an optional on/off fresh-air damper. Points cover unit enable, occupancy and mode commands, network setpoint and network sensor overrides, fan, valve and damper status, PID tuning, fault detection flags and the controller's network settings.

This page lists 208 BACnet objects for the Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper) — 140 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.

Manufacturer
Johnson Controls
Model
ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
Equipment
Fan coil unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
208 (140 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller
Source document
Advanced Terminal Unit Controller Application Note - Application #2007 · LIT-12013077 · rev. April 2023
Download CSV 208 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.

BMS integration notes: Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)

Integration in brief

Set the controller to BACnet MS/TP (FC Comm Mode Wired Field Bus) with an MS/TP address of 4-127, then enable the unit with Unit Enable Mode, drive occupancy through Occupancy Schedule and write Network Setpoint (Spt Source defaults to Network Input). Read unit status, effective occupancy, zone temperature and the fan state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 28002Unit Enable ModeUnit on/off: 0=Shutdown, 1=EnableWrite
MV 28048Occupancy ScheduleOccupancy from the BAS scheduleWrite
MV 28006System Mode DeterminationMode command (cool only, heat only, fan only...)Write
AV 28063Network SetpointZone setpoint written by the BAS, °C/°FWrite
MV 28000Unit StatusHeat, cool, fan only, satisfied or offRead
MV 28049Effective OccupancyOccupancy in effectRead
AV 28085Operational Zone TemperatureZone temperature in use, °C/°FRead
AV 28072Fan Speed AOFan speed output, %Read
MV 28081Condensate Alarm BICondensate alarm input: 0=Normal, 1=AlarmRead

Enable & remote start

Unit Enable Mode (Shutdown or Enable, default Enable) turns the unit off or on. Effective occupancy follows Occupancy Override first, then the bypass timer, Occupancy Schedule and the occupancy sensor. System Mode Determination is the writable mode command (cool only, heat only, fan only and others). The note says a network mode command takes priority over the summer-winter changeover input.

Sensors & values from the BMS

With Spt Source at Network Input (the default) the zone setpoint comes from Network Setpoint (default 22 °C). Network Override Zone Temperature, Network Override Outdoor Air Temperature and Network Override Indoor Air Quality are writable network inputs; a network CO2 value takes priority over the local sensor, and summer-winter setpoint compensation only works with a reliable network outdoor air temperature.

Network setup

Watch out for

Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

208 of 208 shown
Type
AnalogMulti-state
Access
Show
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper) BACnet Points List
DescriptionStates
MVmin28000Unit StatusRead0=Heat, 1=Cool, 2=Fan Only, 3=Balancing, 4=Satisfied, 5=Off
MV28001Application Tuning ResetWrite0=False, 1=True, 2=Hold
MVmin28002Unit Enable ModeWrite0=Shutdown, 1=Enable
MV28003Occupied StateRead0=Heating, 1=Satisfied, 2=Cooling, 3=Supp Htg, 4=Temperature Unreliable
MV28004Unoccupied StateRead0=Not Unoccupied, 1=Temperature Unreliable, 2=Unocc Htg/Clg Check, 3=Unoccupied Off
MVmin28006System Mode DeterminationWrite0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, ... (list cut short in the doc)
MV28007System ModeRead0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, ... (list cut short in the doc)
MV28008Heat Cool Mode DestinationWrite0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, ... (list cut short in the doc)
MV28009Effective HVAC ModeRead0=Not In Use, 1=Off, 2=Heat, 3=Cool, 4=Fan Only
MV28010Device StatusRead0=Main Download Req, 1=Code Download, 2=Class Code Download, 3=Subclass Download, ... (list cut short in the doc)
MV28011Firmware StatusRead0=Firmware Versions OK, 1=Firmware Versions Do Not Match the Package
AV28000N2 AddressRange 1 to 253Write
AV28001Modbus AddressRange 1 to 247Write
AV28002MSTP Device AddressRange 4 to 127Write
AV28003Device Object IDRange 0 to 4194302Write
MV28012FC Comm ModeWrite0=Wired Field Bus, 1=Wireless Field Bus, 2=N2 Field Bus, 3=Modbus Field Bus, ... (list cut short in the doc)
MV28013Communication StatusRead0=Not Configured, 1=Active, 2=Waiting For Poll For Master, 3=Not Received Token For Long, ... (list cut short in the doc)
MV28014FCB Baud RateWrite0=Auto, 1=1200, 2=9600, 3=19200, ... (list cut short in the doc)
MV28015Operating Baud RateRead0=Auto, 1=1200, 2=9600, 3=19200, ... (list cut short in the doc)
MV28016BACnet Encoding TypeWrite0=ISO 10646 (UCS-2), 1=ANSI X3.4 (US-ASCII), 2=Microsoft DBCS code page 932 (Japanese Shift JIS), 3=ISO 10646 (UTF-8)
MV28017Time ZoneWrite1=(UTC+00:00) Monrovia, Reykjavik, 2=(UTC+00:00) Greenwich Mean Time : Dublin, Edinburgh, Lisbon, London, 3=(UTC+01:00) Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna, 4=(UTC+01:00) Belgrade, Bratislava, Budapest, Ljubljana, Prague, ... (list cut short in the doc)
MV28018UnitsWrite0=IP, 1=SI
MV28019Relearn SystemWrite0=False, 1=True
MV28020Provider NameWrite0=Automatic, 1=Manual
MV28027Heating Control StatusRead0=Normal, 1=Low, 2=Timing Low, 3=High, ... (list cut short in the doc)
MV280282 Pipe Valve BORead0=Off, 1=On, 2=Hold
AV28005Heating SetpointRange 0 to 100°C (32 to 212°F)°C/°FRead
AV28006Htg Minimum On TimeRange 0 to 1200 secondssWrite
AV28007Htg Minimum Off TimeRange 0 to 1200 secondssWrite
AV28008Limited Max Heating ValueRange 10 to 100%%Write
MV28029Heating ModeRead0=Off, 1=Max, 2=Limited Max, 3=Hold, ... (list cut short in the doc)
MV28030Heating Adaptive Tuning EnableWrite0=Disable, 1=Enable
MV28031Heating Manual TuningWrite0=Yes, 1=No
AV28009Heat Prop BandRange 1 to 200Write
AV28010Heat Integral TimeRange 0 to 1800 secondssWrite
AV28011Heat Saturation TimeRange 1 to 1800 secondssWrite
AV28012Heat Process RangeRange 0 to 1800Write
AV28013Heat Time ConstantRange 1 to 1800 secondssWrite
AV28014Heat Process Dead TimeRange 0 to 1800 secondssWrite
AV28015Heat PeriodRange 0 to 1800 secondssWrite
MV28032Heating Process IDWrite0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, ... (list cut short in the doc)
MV28033Two Position PolarityWrite0=Normal, 1=Reverse, 2=Hold
AV28016Control BandRange 0 to 5 delta °C (0 to 5 delta °F)delta °C/°FWrite
AV28018Cooling SetpointRange 0 to 100°C (32 to 212°F)°C/°FRead
MV28034Cooling Control StatusRead0=Normal, 1=Low, 2=Timing Low, 3=High, ... (list cut short in the doc)
AV28019Clg Minimum On TimeRange 0 to 1200 secondssWrite
AV28020Clg Minimum Off TimeRange 0 to 1200 secondssWrite
AV28021Limited Max Cooling ValueRange 10 to 100%%Write
MV28036Cooling ModeRead0=Off, 1=Max, 2=Limited Max, 3=Hold, ... (list cut short in the doc)
MV28037Cooling Adaptive Tuning EnableWrite0=Disable, 1=Enable
MV28038Cooling Manual TuningWrite0=Yes, 1=No
AV28022Cool Prop BandRange 1 to 200Write
AV28023Cool Integral TimeRange 0 to 1800 secondssWrite
AV28024Cool Saturation TimeRange 1 to 1800 secondssWrite
AV28025Cool Process RangeRange 0 to 1800Write
AV28026Cool Time ConstantRange 1 to 1800 secondssWrite
AV28027Cool Process Dead TimeRange 1 to 1800 secondssWrite
AV28028Cool PeriodRange 0 to 1800 secondssWrite
MV28039Cool Process IDWrite0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, ... (list cut short in the doc)
MV28040Damper StateRead0=Off, 1=On, 2=Max
AV28029Damper Maximum PositionRange 0 to 100%%Write
AV28030Damper Minimum PositionRange 0 to 100%%Write
AV28134Damper Stroke TimeRange 1 to 240 secondssWrite
AV28031Damper Percent CmdRange 0 to 100%%Read
MV28041Damper OpenCloseRead0=Close, 1=Open
AV28032CO2 Prop BandRange 0 to 10000 ppmppmWrite
MV28042OA Damper BORead0=Close, 1=Open, 2=Hold
MV28044Damper PolarityWrite0=Normal, 1=Reverse, 2=Hold
MV28045IAQRead0=Unreliable, 1=Low Priority, 2=Medium Priority, 3=High Priority, ... (list cut short in the doc)
MV28047Occupancy OverrideWrite0=Occupied, 1=UnOccupied, 2=Bypass, 3=Standby, 4=Not Set
MVmin28048Occupancy ScheduleWrite0=Occupied, 1=UnOccupied, 2=Standby, 3=Not Set
MVmin28049Effective OccupancyRead0=Occupied, 1=UnOccupied, 2=Bypass, 3=Standby
AV28034Bypass TimeRange 0 to 7200 secondssWrite
AV28035Off DelayRange 0 to 600 secondssWrite
MV28050Temporary OccupancyWrite0=Normal, 1=Trigger
MV28051FDD EnableWrite0=Disable, 1=Enable
AV28036Start DelayRange 0 to 86400 secondssWrite
AV28037Insufficient Htg Cap Sat DelayRange 0 to 86400 secondssWrite
AV28038Insufficient Htg Cap Zone Max ErrorRange 0 to 55 delta °C (0 to 99 delta °F)delta °C/°FWrite
AV28039Insufficient Clg Cap Zone Max ErrorRange 0 to 55 delta °C (0 to 99 delta °F)delta °C/°FWrite
AV28040Low Zone Temp Zone Max ErrorRange 0 to 55 delta °C (0 to 99 delta °F)delta °C/°FWrite
AV28041High Zone Temp Zone Max ErrorRange 0 to 55 delta °C (0 to 99 delta °F)delta °C/°FWrite
AV28042ZN Spt Out Of Comfort Lim Min T SptRange -20 to 40°C (-4 to 104°F)°C/°FWrite
AV28043ZN Spt Out Of Comfort Lim Max T SptRange -20 to 40°C (-4 to 104°F)°C/°FWrite
AV28044Changeover Setting Zone Max ErrorRange 0 to 55 delta °C (0 to 99 delta °F)delta °C/°FWrite
AV28045Setpoint Compensation Winter Max DiffRange 0 to 55 delta °C (0 to 99 delta °F)delta °C/°FWrite
AV28046Setpoint Compensation Summer Max DiffRange 0 to 55 delta °C (0 to 99 delta °F)delta °C/°FWrite
AV28048Insufficient Clg Cap Sat DelayRange 0 to 86400 secondssWrite
MV28052FDDRead0=Disable, 1=Enable
MV28053Window Open While Occupied FaultRead0=Normal, 1=Alarm
MV28054Window Open While Unoccupied FaultRead0=Normal, 1=Alarm
MV28055Insufficient Cooling Capacity FaultRead0=Normal, 1=Alarm
MV28056Insufficient Heating Capacity FaultRead0=Normal, 1=Alarm
MV28057Zone Spt Outside Comfort Limits FaultRead0=Normal, 1=Alarm
MV28058High Zone Temp FaultRead0=Normal, 1=Alarm
MV28059Low Zone Temp FaultRead0=Normal, 1=Alarm
MV28060Incorrect Changeover Setting FaultRead0=Normal, 1=Alarm
MV28061Incorrect Setpoint Compensation FaultRead0=Normal, 1=Alarm
AV28049Window Open In Occ In Fault TimeRange 0 to 86400 secondssWrite
AV28050Window Open In Unocc In Fault TimeRange 0 to 86400 secondssWrite
AV28051Low Zone Temp In Fault TimeRange 0 to 86400 secondssWrite
AV28052High Zone Temp In Fault TimeRange 0 to 86400 secondssWrite
AV28054Changeover Setting In Fault TimeRange 0 to 86400 secondssWrite
MV28063Window Open In Occ Fault EnableWrite0=Disable, 1=Enable
MV28064Window Open In Unocc Fault EnableWrite0=Disable, 1=Enable
MV28065Insufficient Htg Cap Fault EnableWrite0=Disable, 1=Enable
MV28066Insufficient Clg Cap Fault EnableWrite0=Disable, 1=Enable
MV28067Low Zone Temp Fault EnableWrite0=Disable, 1=Enable
MV28068High Zone Temp Fault EnableWrite0=Disable, 1=Enable
MV28069Changeover Setting Fault EnableWrite0=Disable, 1=Enable
MV28070Setpoint Compensation Fault EnableWrite0=Disable, 1=Enable
MV28071ZN Spt Out Of Comfort Lim Fault EnableWrite0=Disable, 1=Enable
AV28055ecoClgSetpointRange 20 to 30°C (68 to 86°F)°C/°FWrite
MV28073Energy IndicatorRead0=Off, 1=Red, 2=Green
AV28056ecoHtgSetpointRange 15 to 25°C (59 to 77°F)°C/°FWrite
MV28074Energy Indication EnableWrite0=Disable, 1=Enable
MV28075Energy Indicator ResetWrite0=False, 1=True
AV28057ecoHtgSetpoint DiffRange 0 to 10 delta °C (0 to 10 delta °F)delta °C/°FWrite
AV28058ecoClgSetpoint DiffRange 0 to 10 delta °C (0 to 10 delta °F)delta °C/°FWrite
AV28059CO2 SetpointRange 0 to 10000 ppmppmWrite
AV28060Effective Zone Temperature SetpointRange 10 to 30°C (50 to 86°F)°C/°FRead
AV28061Unocc Cooling SetpointRange 15 to 30°C (59 to 86°F)°C/°FWrite
AV28062Unocc Heating SetpointRange 10 to 25°C (50 to 77°F)°C/°FWrite
AVmin28063Network SetpointRange 12 to 28°C (53.6 to 82.4°F)°C/°FWrite
AV28064Standby Cooling SetpointRange 10 to 30°C (50 to 86°F)°C/°FWrite
AV28065Standby Heating SetpointRange 10 to 30°C (50 to 86°F)°C/°FWrite
AV28066Freeze Stat SetpointRange -20 to 10°C (-4 to 50°F)°C/°FWrite
AV28067Frost Protect DifferentialRange 0 to 15 delta °C (0 to 27 delta °F)delta °C/°FWrite
MV28076Spt SourceWrite0=Network Input, 1=Sensor Input, 2=Multiple Inputs
MV29990Space VoteRead0=Urgent Heat, 1=Heat, 2=Satisfied, 3=Cool, 4=Urgent Cool
AV28068Low RangeRange 0 to 100%%Write
AV28069High RangeRange 0 to 100%%Write
AV28070Low Range DiffRange 0 to 100%%Write
AV28071High Range DiffRange 0 to 100%%Write
MV28078Fan BORead0=Off, 1=On, 2=Hold
AVmin28072Fan Speed AORange 0 to 100%%Read
AV28073Percent CmdRange 0 to 100%%Read
MV28079Fan ModeRead0=Off, 1=On, 2=Max
AV28074Minimum SpeedRange 0 to 100%%Write
AV28075Max Speed CoolingRange 0 to 100%%Write
AV28076Max Speed HeatingRange 0 to 100%%Write
AV28077Supply Fan LowRange 0 to 100%%Write
AV28078Supply Fan MediumRange 0 to 100%%Write
AV28079Fan Min Out ValueRange 0 to 100%%Write
MV28080Fan BO PolarityWrite0=Normal, 1=Reverse, 2=Hold
AV28080Fan Max Out ValueRange 0 to 100%%Write
AV28081Network Override Indoor Air QualityRange 0 to 10000 ppmppmWrite
AV28082Operational Indoor Air QualityRange 0 to 10000 ppmppmRead
AV28083Network Override Outdoor Air TemperatureRange -46 to 94°C (-50.8 to 201.2°F)°C/°FWrite
AV28084Network Override Zone TemperatureRange -18 to 38°C (-0.4 to 100.4°F)°C/°FWrite
AVmin28085Operational Zone TemperatureRange -18 to 38°C (-0.4 to 100.4°F)°C/°FRead
AV28086Operational Outdoor Air TemperatureRange -18 to 38°C (-0.4 to 100.4°F)°C/°FRead
MVmin28081Condensate Alarm BIRead0=Normal, 1=Alarm, 2=Hold
MV28082SummerWinter BIRead0=Summer, 1=Winter, 2=Hold
MV28083Window Status BIRead0=Close, 1=Open, 2=Hold
MV28084Occupancy Sensor BIRead0=Occupied, 1=Unoccupied, 2=Hold
MV28085Occupancy Sensor PolarityWrite0=Normal, 1=Reverse, 2=Hold
MV28086Window Contact PolarityWrite0=Normal, 1=Reverse, 2=Hold
MV28087Dew Point Contact PolarityWrite0=Normal, 1=Reverse, 2=Hold
MV28088Summer Winter PolarityWrite0=Normal, 1=Reverse, 2=Hold
AV28087Effective Cooling ShiftRange -20 to 40°C (-4 to 104°F)°C/°FRead
AV28088Effective Heating ShiftRange -20 to 40°C (-4 to 104°F)°C/°FRead
AV28089Winter SetpointRange -40 to 20°C (-40 to 68°F)°C/°FWrite
AV28090Summer SetpointRange 10 to 60°C (50 to 140°F)°C/°FWrite
AV28091Summer Change LimitRange -10 to 10 delta °C (-18 to 18 delta °F)delta °C/°FWrite
AV28092Winter Change LimitRange -10 to 10 delta °C (-18 to 18 delta °F)delta °C/°FWrite
AV28093Summer GainRange 0 to 10Write
AV28094Winter GainRange -10 to 10Write
MV28089SummerWinterRead0=Summer, 1=Winter
MV28090Start CommissionWrite0=Normal, 1=Trigger
MV28091HC-C OvrdWrite0=Off, 1=On
AV28095HC-O OvrdRange 0 to 100%%Write
AV28096SF-O OvrdRange 0 to 100%%Write
MV28092OAD-C OvrdWrite0=Off, 1=On
MV28093SFL-C OvrdWrite0=Off, 1=On
MV28094SFM-C OvrdWrite0=Off, 1=On
MV28095SFH-C OvrdWrite0=Off, 1=On
AV28097OAD-O OvrdRange 0 to 100%%Write
MV28096SF-C OvrdWrite0=Off, 1=On
MV28097Fan StatusRead0=Off, 1=On
AV28098Zone TemperatureRange -20 to 40°C (-4 to 104°F)°C/°FRead
AV28099CO2Range 0 to 10000 ppmppmRead
MV28098Zone Occupancy RequestRead0=Occupied, 1=UnOccupied, 2=Not Set
AV28100Warmer/Cooler AdjustRange -100 to 100 delta °C (-100 to 100 delta °F)delta °C/°FRead
AV28101Setpoint OffsetRange 0.01 to 10 delta °C (0.02 to 18 delta °F)delta °C/°FWrite
MV28099Indoor Air Quality Sensor InstalledRead0=Reliable, 1=No Input, 2=Out of range high, 3=Out of range low, ... (list cut short in the doc)
MV28100Occupancy Status DisplayRead0=Occupied, 1=UnOccupied, 2=Standby, 3=Not Set
MV28101Fan Speed RequestRead0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
AV28102Network/Zone Sensor SetpointRange 10 to 40°C (50 to 104°F)°C/°FRead
AV28103Active SetpointRange 12 to 28°C (53.6 to 82.4°F)°C/°FWrite
AV28104Zone Temperature Setpoint AlternateRange 12 to 28°C (53.6 to 82.4°F)°C/°FRead
AV28105Heating Percent CmdRange 0 to 100%%Read
AV28118Cooling Percent CmdRange 0 to 100%%Read
MV28114DamperRead0=On/Off, 1=Floating
MV28115Fan TypeRead0=Constant Volume Fan, 1=Fixed Variable Fan
MV28116ValveRead0=Staged, 1=Proportional
AV28129Application DetailsRange 0 to 1000000000Read
AV28130Application NameRange 0 to 10000Read
MV28117Fan CyclingWrite0=No, 1=Yes
AV28131Fan On ThresholdRange 0 to 100%%Write
AV28132Fan Off ThresholdRange 0 to 100%%Write
AV28133Heating Purge DurationRange 0 to 1800 secondssWrite
MV28118Fan StateRead0=Off, 1=On
MV28119Off During UnoccupiedWrite0=False, 1=True, 2=Hold
MV28120Cooling Fan RequiredWrite0=No, 1=Yes
MV28121Heating Fan RequiredWrite0=No, 1=Yes
MV28122Fan Speed OverrideWrite0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
MV28123Eff Fan Speed CmdRead0=Auto, 1=Off, 2=Low, 3=Medium, 4=High
Object ID lookup: Johnson Controls ATC1100 App #2007 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)

How many BACnet points does the Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper) have?

This list has 208 BACnet objects: 108 analog values, 100 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper) BACnet points are writable?

140 of the 208 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper) BACnet documentation?

The source is Advanced Terminal Unit Controller Application Note - Application #2007 (LIT-12013077), revision April 2023, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/WBodpWe4CKKyHt9FNh41yA/content.

What are the minimum BACnet points to integrate the Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)?

Start with MV 28002 Unit Enable Mode (Unit on/off: 0=Shutdown, 1=Enable); MV 28048 Occupancy Schedule (Occupancy from the BAS schedule); MV 28006 System Mode Determination (Mode command (cool only, heat only, fan only...)); AV 28063 Network Setpoint (Zone setpoint written by the BAS, °C/°F); MV 28000 Unit Status (Heat, cool, fan only, satisfied or off); MV 28049 Effective Occupancy (Occupancy in effect); AV 28085 Operational Zone Temperature (Zone temperature in use, °C/°F); AV 28072 Fan Speed AO (Fan speed output, %); MV 28081 Condensate Alarm BI (Condensate alarm input: 0=Normal, 1=Alarm).

How do I enable BMS control of the Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)?

Unit Enable Mode (Shutdown or Enable, default Enable) turns the unit off or on. Effective occupancy follows Occupancy Override first, then the bypass timer, Occupancy Schedule and the occupancy sensor. System Mode Determination is the writable mode command (cool only, heat only, fan only and others). The note says a network mode command takes priority over the summer-winter changeover input.

Can the BMS supply sensor values to the Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)?

With Spt Source at Network Input (the default) the zone setpoint comes from Network Setpoint (default 22 °C). Network Override Zone Temperature, Network Override Outdoor Air Temperature and Network Override Indoor Air Quality are writable network inputs; a network CO2 value takes priority over the local sensor, and summer-winter setpoint compensation only works with a reliable network outdoor air temperature.

How do I check these points on the real ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.