- ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
Fan coil unit controller · BACnet points list
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper) BACnet points list
Updated 6 November 2026
Application #2008 is one of the fan coil applications for the Johnson Controls ATC1100 (2 UI, 2 BI, 2 BO, 3 RO, 2 CO) Advanced Terminal Unit Controller, which connects over BACnet MS/TP (it can also run N2 or Modbus). It drives a two-pipe fan coil with 0-10 V proportional valve control, a variable-speed fan and an optional on/off fresh-air damper. Points cover unit enable, occupancy and mode commands, network setpoint and network sensor overrides, fan, valve and damper status, PID tuning, fault detection flags and the controller's network settings.
This page lists 204 BACnet objects for the Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper) — 136 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
- Equipment
- Fan coil unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 204 (136 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
Set the controller to BACnet MS/TP (FC Comm Mode Wired Field Bus) with an MS/TP address of 4-127, then enable the unit with Unit Enable Mode, drive occupancy through Occupancy Schedule and write Network Setpoint (Spt Source defaults to Network Input). Read unit status, effective occupancy, zone temperature and the fan state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 28002 | Unit Enable Mode | Unit on/off: 0=Shutdown, 1=Enable | Write |
| MV 28048 | Occupancy Schedule | Occupancy from the BAS schedule | Write |
| MV 28006 | System Mode Determination | Mode command (cool only, heat only, fan only...) | Write |
| AV 28063 | Network Setpoint | Zone setpoint written by the BAS, °C/°F | Write |
| MV 28000 | Unit Status | Heat, cool, fan only, satisfied or off | Read |
| MV 28049 | Effective Occupancy | Occupancy in effect | Read |
| AV 28085 | Operational Zone Temperature | Zone temperature in use, °C/°F | Read |
| AV 28072 | Fan Speed AO | Fan speed output, % | Read |
| MV 28081 | Condensate Alarm BI | Condensate alarm input: 0=Normal, 1=Alarm | Read |
Enable & remote start
Unit Enable Mode (Shutdown or Enable, default Enable) turns the unit off or on. Effective occupancy follows Occupancy Override first, then the bypass timer, Occupancy Schedule and the occupancy sensor. System Mode Determination is the writable mode command (cool only, heat only, fan only and others). The note says a network mode command takes priority over the summer-winter changeover input.
Sensors & values from the BMS
With Spt Source at Network Input (the default) the zone setpoint comes from Network Setpoint (default 22 °C). Network Override Zone Temperature, Network Override Outdoor Air Temperature and Network Override Indoor Air Quality are writable network inputs; a network CO2 value takes priority over the local sensor, and summer-winter setpoint compensation only works with a reliable network outdoor air temperature.
Network setup
- FC Comm Mode picks the field bus (Wired Field Bus for BACnet MS/TP, N2 or Modbus). MSTP Device Address is 4-127 and Device Object ID 0-4194302.
- FCB Baud Rate defaults to Auto; Operating Baud Rate shows the rate in use and Communication Status the MS/TP state.
- Units (MV 28018) selects IP or SI; the default is SI.
Watch out for
- BACnet IDs (AV 280xx / MV 280xx) are reused across the ATC applications but do not always mean the same point; map each application from its own list.
- Occupancy Override and Occupancy Schedule read Not Set after a reset until written again; with both Not Set and no occupancy sensor the unit falls back to Default Occupancy (Occupied unless changed).
- PID tuning, minimum on/off times and fault delays are commissioning values; don't write them cyclically.
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 28000 | Unit Status | Read | 0=Heat, 1=Cool, 2=Fan Only, 3=Balancing, 4=Satisfied, 5=Off | ||
| MV | 28001 | Application Tuning Reset | Write | 0=False, 1=True, 2=Hold | ||
| MVmin | 28002 | Unit Enable Mode | Write | 0=Shutdown, 1=Enable | ||
| MV | 28003 | Occupied State | Read | 0=Heating, 1=Satisfied, 2=Cooling, 3=Supp Htg, 4=Temperature Unreliable | ||
| MV | 28004 | Unoccupied State | Read | 0=Not Unoccupied, 1=Temperature Unreliable, 2=Unocc Htg/Clg Check, 3=Unoccupied Off | ||
| MVmin | 28006 | System Mode Determination | Write | 0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, ... (list cut short in the doc) | ||
| MV | 28007 | System Mode | Read | 0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, ... (list cut short in the doc) | ||
| MV | 28008 | Heat Cool Mode Destination | Write | 0=Cool Only, 1=Heat Only, 2=Fan Only, 3=Water Flush, ... (list cut short in the doc) | ||
| MV | 28009 | Effective HVAC Mode | Read | 0=Not In Use, 1=Off, 2=Heat, 3=Cool, 4=Fan Only | ||
| MV | 28010 | Device Status | Read | 0=Main Download Req, 1=Code Download, 2=Class Code Download, 3=Subclass Download, ... (list cut short in the doc) | ||
| MV | 28011 | Firmware Status | Read | 0=Firmware Versions OK, 1=Firmware Versions Do Not Match the Package | ||
| AV | 28000 | N2 Address | Range 1 to 253 | Write | ||
| AV | 28001 | Modbus Address | Range 1 to 247 | Write | ||
| AV | 28002 | MSTP Device Address | Range 4 to 127 | Write | ||
| AV | 28003 | Device Object ID | Range 0 to 4194302 | Write | ||
| MV | 28012 | FC Comm Mode | Write | 0=Wired Field Bus, 1=Wireless Field Bus, 2=N2 Field Bus, 3=Modbus Field Bus, ... (list cut short in the doc) | ||
| MV | 28013 | Communication Status | Read | 0=Not Configured, 1=Active, 2=Waiting For Poll For Master, 3=Not Received Token For Long, ... (list cut short in the doc) | ||
| MV | 28014 | FCB Baud Rate | Write | 0=Auto, 1=1200, 2=9600, 3=19200, ... (list cut short in the doc) | ||
| MV | 28015 | Operating Baud Rate | Read | 0=Auto, 1=1200, 2=9600, 3=19200, ... (list cut short in the doc) | ||
| MV | 28016 | BACnet Encoding Type | Write | 0=ISO 10646 (UCS-2), 1=ANSI X3.4 (US-ASCII), 2=Microsoft DBCS code page 932 (Japanese Shift JIS), 3=ISO 10646 (UTF-8) | ||
| MV | 28017 | Time Zone | Write | 1=(UTC+00:00) Monrovia, Reykjavik, 2=(UTC+00:00) Greenwich Mean Time : Dublin, Edinburgh, Lisbon, London, 3=(UTC+01:00) Amsterdam, Berlin, Bern, Rome, Stockholm, Vienna, 4=(UTC+01:00) Belgrade, Bratislava, Budapest, Ljubljana, Prague, ... (list cut short in the doc) | ||
| MV | 28018 | Units | Write | 0=IP, 1=SI | ||
| MV | 28019 | Relearn System | Write | 0=False, 1=True | ||
| MV | 28020 | Provider Name | Write | 0=Automatic, 1=Manual | ||
| MV | 28040 | Damper State | Read | 0=Off, 1=On, 2=Max | ||
| AV | 28029 | Damper Maximum Position | Range 0 to 100% | % | Write | |
| AV | 28030 | Damper Minimum Position | Range 0 to 100% | % | Write | |
| AV | 28134 | Damper Stroke Time | Range 1 to 240 seconds | s | Write | |
| AV | 28031 | Damper Percent Cmd | Range 0 to 100% | % | Read | |
| MV | 28041 | Damper OpenClose | Read | 0=Close, 1=Open | ||
| AV | 28032 | CO2 Prop Band | Range 0 to 10000 ppm | ppm | Write | |
| MV | 28042 | OA Damper BO | Read | 0=Close, 1=Open, 2=Hold | ||
| MV | 28044 | Damper Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28045 | IAQ | Read | 0=Unreliable, 1=Low Priority, 2=Medium Priority, 3=High Priority, ... (list cut short in the doc) | ||
| MV | 28047 | Occupancy Override | Write | 0=Occupied, 1=UnOccupied, 2=Bypass, 3=Standby, 4=Not Set | ||
| MVmin | 28048 | Occupancy Schedule | Write | 0=Occupied, 1=UnOccupied, 2=Standby, 3=Not Set | ||
| MVmin | 28049 | Effective Occupancy | Read | 0=Occupied, 1=UnOccupied, 2=Bypass, 3=Standby | ||
| AV | 28034 | Bypass Time | Range 0 to 7200 seconds | s | Write | |
| AV | 28035 | Off Delay | Range 0 to 600 seconds | s | Write | |
| MV | 28050 | Temporary Occupancy | Write | 0=Normal, 1=Trigger | ||
| MV | 28051 | FDD Enable | Write | 0=Disable, 1=Enable | ||
| AV | 28036 | Start Delay | Range 0 to 86400 seconds | s | Write | |
| AV | 28037 | Insufficient Htg Cap Sat Delay | Range 0 to 86400 seconds | s | Write | |
| AV | 28038 | Insufficient Htg Cap Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28039 | Insufficient Clg Cap Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28040 | Low Zone Temp Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28041 | High Zone Temp Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28042 | ZN Spt Out Of Comfort Lim Min T Spt | Range -20 to 40°C (-4 to 104°F) | °C/°F | Write | |
| AV | 28043 | ZN Spt Out Of Comfort Lim Max T Spt | Range -20 to 40°C (-4 to 104°F) | °C/°F | Write | |
| AV | 28044 | Changeover Setting Zone Max Error | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28045 | Setpoint Compensation Winter Max Diff | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28046 | Setpoint Compensation Summer Max Diff | Range 0 to 55 delta °C (0 to 99 delta °F) | delta °C/°F | Write | |
| AV | 28048 | Insufficient Clg Cap Sat Delay | Range 0 to 86400 seconds | s | Write | |
| MV | 28052 | FDD | Read | 0=Disable, 1=Enable | ||
| MV | 28053 | Window Open While Occupied Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28054 | Window Open While Unoccupied Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28055 | Insufficient Cooling Capacity Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28056 | Insufficient Heating Capacity Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28057 | Zone Spt Outside Comfort Limits Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28058 | High Zone Temp Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28059 | Low Zone Temp Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28060 | Incorrect Changeover Setting Fault | Read | 0=Normal, 1=Alarm | ||
| MV | 28061 | Incorrect Setpoint Compensation Fault | Read | 0=Normal, 1=Alarm | ||
| AV | 28049 | Window Open In Occ In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28050 | Window Open In Unocc In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28051 | Low Zone Temp In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28052 | High Zone Temp In Fault Time | Range 0 to 86400 seconds | s | Write | |
| AV | 28054 | Changeover Setting In Fault Time | Range 0 to 86400 seconds | s | Write | |
| MV | 28063 | Window Open In Occ Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28064 | Window Open In Unocc Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28065 | Insufficient Htg Cap Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28066 | Insufficient Clg Cap Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28067 | Low Zone Temp Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28068 | High Zone Temp Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28069 | Changeover Setting Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28070 | Setpoint Compensation Fault Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28071 | ZN Spt Out Of Comfort Lim Fault Enable | Write | 0=Disable, 1=Enable | ||
| AV | 28055 | ecoClgSetpoint | Range 20 to 30°C (68 to 86°F) | °C/°F | Write | |
| MV | 28073 | Energy Indicator | Read | 0=Off, 1=Red, 2=Green | ||
| AV | 28056 | ecoHtgSetpoint | Range 15 to 25°C (59 to 77°F) | °C/°F | Write | |
| MV | 28074 | Energy Indication Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28075 | Energy Indicator Reset | Write | 0=False, 1=True | ||
| AV | 28057 | ecoHtgSetpoint Diff | Range 0 to 10 delta °C (0 to 10 delta °F) | delta °C/°F | Write | |
| AV | 28058 | ecoClgSetpoint Diff | Range 0 to 10 delta °C (0 to 10 delta °F) | delta °C/°F | Write | |
| AV | 28059 | CO2 Setpoint | Range 0 to 10000 ppm | ppm | Write | |
| AV | 28060 | Effective Zone Temperature Setpoint | Range 10 to 30°C (50 to 86°F) | °C/°F | Read | |
| AV | 28061 | Unocc Cooling Setpoint | Range 15 to 30°C (59 to 86°F) | °C/°F | Write | |
| AV | 28062 | Unocc Heating Setpoint | Range 10 to 25°C (50 to 77°F) | °C/°F | Write | |
| AVmin | 28063 | Network Setpoint | Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Write | |
| AV | 28064 | Standby Cooling Setpoint | Range 10 to 30°C (50 to 86°F) | °C/°F | Write | |
| AV | 28065 | Standby Heating Setpoint | Range 10 to 30°C (50 to 86°F) | °C/°F | Write | |
| AV | 28066 | Freeze Stat Setpoint | Range -20 to 10°C (-4 to 50°F) | °C/°F | Write | |
| AV | 28067 | Frost Protect Differential | Range 0 to 15 delta °C (0 to 27 delta °F) | delta °C/°F | Write | |
| MV | 28076 | Spt Source | Write | 0=Network Input, 1=Sensor Input, 2=Multiple Inputs | ||
| MV | 29990 | Space Vote | Read | 0=Urgent Heat, 1=Heat, 2=Satisfied, 3=Cool, 4=Urgent Cool | ||
| AV | 28068 | Low Range | Range 0 to 100% | % | Write | |
| AV | 28069 | High Range | Range 0 to 100% | % | Write | |
| AV | 28070 | Low Range Diff | Range 0 to 100% | % | Write | |
| AV | 28071 | High Range Diff | Range 0 to 100% | % | Write | |
| MV | 28078 | Fan BO | Read | 0=Off, 1=On, 2=Hold | ||
| AVmin | 28072 | Fan Speed AO | Range 0 to 100% | % | Read | |
| AV | 28073 | Percent Cmd | Range 0 to 100% | % | Read | |
| MV | 28079 | Fan Mode | Read | 0=Off, 1=On, 2=Max | ||
| AV | 28074 | Minimum Speed | Range 0 to 100% | % | Write | |
| AV | 28075 | Max Speed Cooling | Range 0 to 100% | % | Write | |
| AV | 28076 | Max Speed Heating | Range 0 to 100% | % | Write | |
| AV | 28077 | Supply Fan Low | Range 0 to 100% | % | Write | |
| AV | 28078 | Supply Fan Medium | Range 0 to 100% | % | Write | |
| AV | 28079 | Fan Min Out Value | Range 0 to 100% | % | Write | |
| MV | 28080 | Fan BO Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| AV | 28080 | Fan Max Out Value | Range 0 to 100% | % | Write | |
| AV | 28081 | Network Override Indoor Air Quality | Range 0 to 10000 ppm | ppm | Write | |
| AV | 28082 | Operational Indoor Air Quality | Range 0 to 10000 ppm | ppm | Read | |
| AV | 28083 | Network Override Outdoor Air Temperature | Range -46 to 94°C (-50.8 to 201.2°F) | °C/°F | Write | |
| AV | 28084 | Network Override Zone Temperature | Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Write | |
| AVmin | 28085 | Operational Zone Temperature | Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Read | |
| AV | 28086 | Operational Outdoor Air Temperature | Range -18 to 38°C (-0.4 to 100.4°F) | °C/°F | Read | |
| MVmin | 28081 | Condensate Alarm BI | Read | 0=Normal, 1=Alarm, 2=Hold | ||
| MV | 28082 | SummerWinter BI | Read | 0=Summer, 1=Winter, 2=Hold | ||
| MV | 28083 | Window Status BI | Read | 0=Close, 1=Open, 2=Hold | ||
| MV | 28084 | Occupancy Sensor BI | Read | 0=Occupied, 1=Unoccupied, 2=Hold | ||
| MV | 28085 | Occupancy Sensor Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28086 | Window Contact Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28087 | Dew Point Contact Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| MV | 28088 | Summer Winter Polarity | Write | 0=Normal, 1=Reverse, 2=Hold | ||
| AV | 28087 | Effective Cooling Shift | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28088 | Effective Heating Shift | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28089 | Winter Setpoint | Range -40 to 20°C (-40 to 68°F) | °C/°F | Write | |
| AV | 28090 | Summer Setpoint | Range 10 to 60°C (50 to 140°F) | °C/°F | Write | |
| AV | 28091 | Summer Change Limit | Range -10 to 10 delta °C (-18 to 18 delta °F) | delta °C/°F | Write | |
| AV | 28092 | Winter Change Limit | Range -10 to 10 delta °C (-18 to 18 delta °F) | delta °C/°F | Write | |
| AV | 28093 | Summer Gain | Range 0 to 10 | Write | ||
| AV | 28094 | Winter Gain | Range -10 to 10 | Write | ||
| MV | 28089 | SummerWinter | Read | 0=Summer, 1=Winter | ||
| MV | 28090 | Start Commission | Write | 0=Normal, 1=Trigger | ||
| MV | 28091 | HC-C Ovrd | Write | 0=Off, 1=On | ||
| AV | 28095 | HC-O Ovrd | Range 0 to 100% | % | Write | |
| AV | 28096 | SF-O Ovrd | Range 0 to 100% | % | Write | |
| MV | 28092 | OAD-C Ovrd | Write | 0=Off, 1=On | ||
| MV | 28093 | SFL-C Ovrd | Write | 0=Off, 1=On | ||
| MV | 28094 | SFM-C Ovrd | Write | 0=Off, 1=On | ||
| MV | 28095 | SFH-C Ovrd | Write | 0=Off, 1=On | ||
| AV | 28097 | OAD-O Ovrd | Range 0 to 100% | % | Write | |
| MV | 28096 | SF-C Ovrd | Write | 0=Off, 1=On | ||
| MV | 28097 | Fan Status | Read | 0=Off, 1=On | ||
| AV | 28098 | Zone Temperature | Range -20 to 40°C (-4 to 104°F) | °C/°F | Read | |
| AV | 28099 | CO2 | Range 0 to 10000 ppm | ppm | Read | |
| MV | 28098 | Zone Occupancy Request | Read | 0=Occupied, 1=UnOccupied, 2=Not Set | ||
| AV | 28100 | Warmer/Cooler Adjust | Range -100 to 100 delta °C (-100 to 100 delta °F) | delta °C/°F | Read | |
| AV | 28101 | Setpoint Offset | Range 0.01 to 10 delta °C (0.02 to 18 delta °F) | delta °C/°F | Write | |
| MV | 28099 | Indoor Air Quality Sensor Installed | Read | 0=Reliable, 1=No Input, 2=Out of range high, 3=Out of range low, ... (list cut short in the doc) | ||
| MV | 28100 | Occupancy Status Display | Read | 0=Occupied, 1=UnOccupied, 2=Standby, 3=Not Set | ||
| MV | 28101 | Fan Speed Request | Read | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High | ||
| AV | 28102 | Network/Zone Sensor Setpoint | Range 10 to 40°C (50 to 104°F) | °C/°F | Read | |
| AV | 28103 | Active Setpoint | Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Write | |
| AV | 28104 | Zone Temperature Setpoint Alternate | Range 12 to 28°C (53.6 to 82.4°F) | °C/°F | Read | |
| AV | 28105 | Heating Percent Cmd | Range 0 to 100% | % | Read | |
| AV | 28118 | Cooling Percent Cmd | Range 0 to 100% | % | Read | |
| MV | 28102 | Heating Control Status | Read | 0=Normal, 1=Low, 2=Timing Low, 3=High, ... (list cut short in the doc) | ||
| AV | 28106 | Limited Max Heating Value | Range 0 to 100% | % | Write | |
| MV | 28103 | Heating Mode | Read | 0=Off, 1=Max, 2=Limited Max, 3=Hold, ... (list cut short in the doc) | ||
| AV | 28107 | 2 Pipe Valve AO | Range 0 to 100% | % | Read | |
| AV | 28108 | Heating Setpoint | Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| MV | 28104 | Heating Adaptive Tuning Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28105 | Heating Manual Tuning | Write | 0=Yes, 1=No | ||
| AV | 28109 | Heat Prop Band | Range 1 to 200 | Write | ||
| AV | 28110 | Heat Integral Time | Range 0 to 1800 seconds | s | Write | |
| AV | 28111 | Heat Saturation Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28112 | Heat Process Range | Range 0 to 1800 | Write | ||
| AV | 28113 | Heat Time Constant | Range 1 to 1800 seconds | s | Write | |
| AV | 28114 | Heat Period | Range 0 to 1800 seconds | s | Write | |
| MV | 28106 | Heating Process ID | Write | 0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, ... (list cut short in the doc) | ||
| AV | 28115 | Heat Process Dead Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28116 | Proportional Min Out Value | Range 0 to 100% | % | Write | |
| AV | 28117 | Proportional Max Out Value | Range 0 to 100% | % | Write | |
| MV | 28107 | Cooling Control Status | Read | 0=Normal, 1=Low, 2=Timing Low, 3=High, ... (list cut short in the doc) | ||
| AV | 28119 | Cooling Setpoint | Range 0 to 100°C (32 to 212°F) | °C/°F | Read | |
| AV | 28120 | Limited Max Cooling Value | Range 0 to 100% | % | Write | |
| MV | 28108 | Cooling Mode | Read | 0=Off, 1=Max, 2=Limited Max, 3=Hold, ... (list cut short in the doc) | ||
| MV | 28109 | Cooling Adaptive Tuning Enable | Write | 0=Disable, 1=Enable | ||
| MV | 28110 | Cooling Manual Tuning | Write | 0=Yes, 1=No | ||
| AV | 28122 | Cool Prop Band | Range 1 to 200 | Write | ||
| AV | 28123 | Cool Integral Time | Range 0 to 1800 seconds | s | Write | |
| AV | 28124 | Cool Saturation Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28125 | Cool Process Range | Range 0 to 1800 | Write | ||
| AV | 28126 | Cool Time Constant | Range 1 to 1800 seconds | s | Write | |
| AV | 28127 | Cool Process Dead Time | Range 1 to 1800 seconds | s | Write | |
| AV | 28128 | Cool Period | Range 0 to 1800 seconds | s | Write | |
| MV | 28111 | Cool Process ID | Write | 0=Airflow, 1=Airflow %, 2=Airflow Diff, 3=Bldg Static, ... (list cut short in the doc) | ||
| MV | 28114 | Damper | Read | 0=On/Off, 1=Floating | ||
| MV | 28115 | Fan Type | Read | 0=Constant Volume Fan, 1=Fixed Variable Fan | ||
| MV | 28116 | Valve | Read | 0=Staged, 1=Proportional | ||
| AV | 28129 | Application Details | Range 0 to 1000000000 | Read | ||
| AV | 28130 | Application Name | Range 0 to 10000 | Read | ||
| MV | 28117 | Fan Cycling | Write | 0=No, 1=Yes | ||
| AV | 28131 | Fan On Threshold | Range 0 to 100% | % | Write | |
| AV | 28132 | Fan Off Threshold | Range 0 to 100% | % | Write | |
| AV | 28133 | Heating Purge Duration | Range 0 to 1800 seconds | s | Write | |
| MV | 28118 | Fan State | Read | 0=Off, 1=On | ||
| MV | 28119 | Off During Unoccupied | Write | 0=False, 1=True, 2=Hold | ||
| MV | 28120 | Cooling Fan Required | Write | 0=No, 1=Yes | ||
| MV | 28121 | Heating Fan Required | Write | 0=No, 1=Yes | ||
| MV | 28122 | Fan Speed Override | Write | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High | ||
| MV | 28123 | Eff Fan Speed Cmd | Read | 0=Auto, 1=Off, 2=Low, 3=Medium, 4=High |
No points match these filters.
Object ID lookup: Johnson Controls ATC1100 App #2008 point IDs by name
MV28000Unit StatusMV28001Application Tuning ResetMV28002Unit Enable ModeMV28003Occupied StateMV28004Unoccupied StateMV28006System Mode DeterminationMV28007System ModeMV28008Heat Cool Mode DestinationMV28009Effective HVAC ModeMV28010Device StatusMV28011Firmware StatusAV28000N2 AddressAV28001Modbus AddressAV28002MSTP Device AddressAV28003Device Object IDMV28012FC Comm ModeMV28013Communication StatusMV28014FCB Baud RateMV28015Operating Baud RateMV28016BACnet Encoding TypeMV28017Time ZoneMV28018UnitsMV28019Relearn SystemMV28020Provider NameMV28040Damper StateAV28029Damper Maximum PositionAV28030Damper Minimum PositionAV28134Damper Stroke TimeAV28031Damper Percent CmdMV28041Damper OpenCloseAV28032CO2 Prop BandMV28042OA Damper BOMV28044Damper PolarityMV28045IAQMV28047Occupancy OverrideMV28048Occupancy ScheduleMV28049Effective OccupancyAV28034Bypass TimeAV28035Off DelayMV28050Temporary OccupancyMV28051FDD EnableAV28036Start DelayAV28037Insufficient Htg Cap Sat DelayAV28038Insufficient Htg Cap Zone Max ErrorAV28039Insufficient Clg Cap Zone Max ErrorAV28040Low Zone Temp Zone Max ErrorAV28041High Zone Temp Zone Max ErrorAV28042ZN Spt Out Of Comfort Lim Min T SptAV28043ZN Spt Out Of Comfort Lim Max T SptAV28044Changeover Setting Zone Max ErrorAV28045Setpoint Compensation Winter Max DiffAV28046Setpoint Compensation Summer Max DiffAV28048Insufficient Clg Cap Sat DelayMV28052FDDMV28053Window Open While Occupied FaultMV28054Window Open While Unoccupied FaultMV28055Insufficient Cooling Capacity FaultMV28056Insufficient Heating Capacity FaultMV28057Zone Spt Outside Comfort Limits FaultMV28058High Zone Temp FaultMV28059Low Zone Temp FaultMV28060Incorrect Changeover Setting FaultMV28061Incorrect Setpoint Compensation FaultAV28049Window Open In Occ In Fault TimeAV28050Window Open In Unocc In Fault TimeAV28051Low Zone Temp In Fault TimeAV28052High Zone Temp In Fault TimeAV28054Changeover Setting In Fault TimeMV28063Window Open In Occ Fault EnableMV28064Window Open In Unocc Fault EnableMV28065Insufficient Htg Cap Fault EnableMV28066Insufficient Clg Cap Fault EnableMV28067Low Zone Temp Fault EnableMV28068High Zone Temp Fault EnableMV28069Changeover Setting Fault EnableMV28070Setpoint Compensation Fault EnableMV28071ZN Spt Out Of Comfort Lim Fault EnableAV28055ecoClgSetpointMV28073Energy IndicatorAV28056ecoHtgSetpointMV28074Energy Indication EnableMV28075Energy Indicator ResetAV28057ecoHtgSetpoint DiffAV28058ecoClgSetpoint DiffAV28059CO2 SetpointAV28060Effective Zone Temperature SetpointAV28061Unocc Cooling SetpointAV28062Unocc Heating SetpointAV28063Network SetpointAV28064Standby Cooling SetpointAV28065Standby Heating SetpointAV28066Freeze Stat SetpointAV28067Frost Protect DifferentialMV28076Spt SourceMV29990Space VoteAV28068Low RangeAV28069High RangeAV28070Low Range DiffAV28071High Range DiffMV28078Fan BOAV28072Fan Speed AOAV28073Percent CmdMV28079Fan ModeAV28074Minimum SpeedAV28075Max Speed CoolingAV28076Max Speed HeatingAV28077Supply Fan LowAV28078Supply Fan MediumAV28079Fan Min Out ValueMV28080Fan BO PolarityAV28080Fan Max Out ValueAV28081Network Override Indoor Air QualityAV28082Operational Indoor Air QualityAV28083Network Override Outdoor Air TemperatureAV28084Network Override Zone TemperatureAV28085Operational Zone TemperatureAV28086Operational Outdoor Air TemperatureMV28081Condensate Alarm BIMV28082SummerWinter BIMV28083Window Status BIMV28084Occupancy Sensor BIMV28085Occupancy Sensor PolarityMV28086Window Contact PolarityMV28087Dew Point Contact PolarityMV28088Summer Winter PolarityAV28087Effective Cooling ShiftAV28088Effective Heating ShiftAV28089Winter SetpointAV28090Summer SetpointAV28091Summer Change LimitAV28092Winter Change LimitAV28093Summer GainAV28094Winter GainMV28089SummerWinterMV28090Start CommissionMV28091HC-C OvrdAV28095HC-O OvrdAV28096SF-O OvrdMV28092OAD-C OvrdMV28093SFL-C OvrdMV28094SFM-C OvrdMV28095SFH-C OvrdAV28097OAD-O OvrdMV28096SF-C OvrdMV28097Fan StatusAV28098Zone TemperatureAV28099CO2MV28098Zone Occupancy RequestAV28100Warmer/Cooler AdjustAV28101Setpoint OffsetMV28099Indoor Air Quality Sensor InstalledMV28100Occupancy Status DisplayMV28101Fan Speed RequestAV28102Network/Zone Sensor SetpointAV28103Active SetpointAV28104Zone Temperature Setpoint AlternateAV28105Heating Percent CmdAV28118Cooling Percent CmdMV28102Heating Control StatusAV28106Limited Max Heating ValueMV28103Heating ModeAV281072 Pipe Valve AOAV28108Heating SetpointMV28104Heating Adaptive Tuning EnableMV28105Heating Manual TuningAV28109Heat Prop BandAV28110Heat Integral TimeAV28111Heat Saturation TimeAV28112Heat Process RangeAV28113Heat Time ConstantAV28114Heat PeriodMV28106Heating Process IDAV28115Heat Process Dead TimeAV28116Proportional Min Out ValueAV28117Proportional Max Out ValueMV28107Cooling Control StatusAV28119Cooling SetpointAV28120Limited Max Cooling ValueMV28108Cooling ModeMV28109Cooling Adaptive Tuning EnableMV28110Cooling Manual TuningAV28122Cool Prop BandAV28123Cool Integral TimeAV28124Cool Saturation TimeAV28125Cool Process RangeAV28126Cool Time ConstantAV28127Cool Process Dead TimeAV28128Cool PeriodMV28111Cool Process IDMV28114DamperMV28115Fan TypeMV28116ValveAV28129Application DetailsAV28130Application NameMV28117Fan CyclingAV28131Fan On ThresholdAV28132Fan Off ThresholdAV28133Heating Purge DurationMV28118Fan StateMV28119Off During UnoccupiedMV28120Cooling Fan RequiredMV28121Heating Fan RequiredMV28122Fan Speed OverrideMV28123Eff Fan Speed Cmd
Integration notes
- Objects from the BACnet and N2 bus points table on pages 44-54 of the application note (LIT-12013078).
- All objects are analog values (AV) or multistate values (MV); physical inputs and outputs show up as MV/AV status points. Access W means the table marks the object Writeable; multistate states keep the 0-based numbers printed in the note.
- For 17 multistate objects the note prints only the first states and then '...'; the full sets are in Metasys System Enumeration Sets (LIT-12011361).
- Application #2006 prints the same table except for the damper output: this one has MV 28042 OA Damper BO, MV 28044 Damper Polarity; #2006 has AV 28033 OA Damper PAO, MV 28043 Damper Polarity.
- Units come from the range column: temperatures follow the controller Units setting (MV 28018, default SI so °C).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
How many BACnet points does the Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper) have?
This list has 204 BACnet objects: 106 analog values, 98 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper) BACnet points are writable?
136 of the 204 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper) BACnet documentation?
The source is Advanced Terminal Unit Controller Application Note - Application #2008 (LIT-12013078), revision April 2023, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/5Zb0hVV91TOG34a6WUDLBw/content.
What are the minimum BACnet points to integrate the Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)?
Start with MV 28002 Unit Enable Mode (Unit on/off: 0=Shutdown, 1=Enable); MV 28048 Occupancy Schedule (Occupancy from the BAS schedule); MV 28006 System Mode Determination (Mode command (cool only, heat only, fan only...)); AV 28063 Network Setpoint (Zone setpoint written by the BAS, °C/°F); MV 28000 Unit Status (Heat, cool, fan only, satisfied or off); MV 28049 Effective Occupancy (Occupancy in effect); AV 28085 Operational Zone Temperature (Zone temperature in use, °C/°F); AV 28072 Fan Speed AO (Fan speed output, %); MV 28081 Condensate Alarm BI (Condensate alarm input: 0=Normal, 1=Alarm).
How do I enable BMS control of the Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)?
Unit Enable Mode (Shutdown or Enable, default Enable) turns the unit off or on. Effective occupancy follows Occupancy Override first, then the bypass timer, Occupancy Schedule and the occupancy sensor. System Mode Determination is the writable mode command (cool only, heat only, fan only and others). The note says a network mode command takes priority over the summer-winter changeover input.
Can the BMS supply sensor values to the Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)?
With Spt Source at Network Input (the default) the zone setpoint comes from Network Setpoint (default 22 °C). Network Override Zone Temperature, Network Override Outdoor Air Temperature and Network Override Indoor Air Quality are writable network inputs; a network CO2 value takes priority over the local sensor, and summer-winter setpoint compensation only works with a reliable network outdoor air temperature.
How do I check these points on the real ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: Advanced Terminal Unit Controller Application Note - Application #2008 · LIT-12013078 · rev. April 2023. Object names, instances and units are reproduced as published; descriptions are our own.