- Home
- BACnet points lists
- Johnson Controls
- EEM Multi-Circuit Electric Energy Meter - Root Device
Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP) · BACnet points list
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device BACnet points list
Updated 11 November 2026
The EEM multi-circuit meter measures up to two voltage references and many CT loads and talks BACnet MS/TP or BACnet IP. Its root device carries the panel-level values for both voltage inputs (Vin1 and Vin2): line-neutral and line-line voltages, phase angles, harmonic distortion, frequency and total energy, plus the service type of each input and the two pulse inputs.
This page lists 33 BACnet objects for the Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- EEM Multi-Circuit Electric Energy Meter - Root Device
- Equipment
- Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 33 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM
- Source document
- EEM Multi-Circuit BACnet Object List · LIT-12013610
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
Choose BACnet MS/TP or BACnet IP in the meter web portal, set the base device instance, then discover the root device and the per-load virtual devices. On the root device read the Vin1/Vin2 voltages, frequency and total energy.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Vin1 Line 1 Measured Line-Neutral Voltage (L1-N) | Vin1 L1-N voltage, V | Read |
| AI 2 | Vin1 Line 2 Measured Line-Neutral Voltage (L2-N) | Vin1 L2-N voltage, V | Read |
| AI 3 | Vin1 Line 3 Measured Line-Neutral Voltage (L3-N) | Vin1 L3-N voltage, V | Read |
| AI 13 | Vin1 Frequency | Vin1 frequency, Hz | Read |
| AI 14 | Vin1 Total Energy Usage | Vin1 total energy, kWh | Read |
| AI 34 | Vin2 Total Energy Usage | Vin2 total energy, kWh | Read |
Network setup
- Protocol is chosen in the meter's web portal: BACnet MS/TP, BACnet IP, Modbus RTU or Modbus TCP.
- BACnet settings: base device instance (0 to 4194328 per the manual), base device name, virtual network number; BACnet IP adds UDP port and BBMD address/TTL; BACnet MS/TP adds MAC 0 to 127, Max Master and Max Info Frames.
- MS/TP baud rates 9600, 19200, 38400 (default), 57600 and 76800; 8 data bits, no parity, 1 stop bit.
- Each configured load gets its own virtual device instance (VDI); the manual says to give every load a unique VDI.
Watch out for
- Load measurements (kW, kWh, amps) are on the per-load virtual devices, not on the root device.
- Root and load devices reuse the same AI instance numbers; map them by device.
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Vin1 Line 1 Measured Line-Neutral Voltage (L1-N) | Voltage input 1; range 0 to 100000 | V | Read | |
| AImin | 2 | Vin1 Line 2 Measured Line-Neutral Voltage (L2-N) | Voltage input 1; range 0 to 100000 | V | Read | |
| AImin | 3 | Vin1 Line 3 Measured Line-Neutral Voltage (L3-N) | Voltage input 1; range 0 to 100000 | V | Read | |
| AI | 4 | Vin1 Line 1 - Line 2 Measured Voltage (L1-L2) | Voltage input 1; range 0 to 100000 | V | Read | |
| AI | 5 | Vin1 Line 2 - Line 3 Measured Voltage (L2-L3) | Voltage input 1; range 0 to 100000 | V | Read | |
| AI | 6 | Vin1 Line 3 - Line 1 Measured Voltage (L3-L1) | Voltage input 1; range 0 to 100000 | V | Read | |
| AI | 7 | Vin1 Line 1 Phase Angle | Voltage input 1; range -360 to 360; units can be changed to radians | ° | Read | |
| AI | 8 | Vin1 Line 2 Phase Angle | Voltage input 1; range -360 to 360; units can be changed to radians | ° | Read | |
| AI | 9 | Vin1 Line 3 Phase Angle | Voltage input 1; range -360 to 360; units can be changed to radians | ° | Read | |
| AI | 10 | Vin1 Line 1 Harmonic Distortion | Voltage input 1; range 0 to 100 | % | Read | |
| AI | 11 | Vin1 Line 2 Harmonic Distortion | Voltage input 1; range 0 to 100 | % | Read | |
| AI | 12 | Vin1 Line 3 Harmonic Distortion | Voltage input 1; range 0 to 100 | % | Read | |
| AImin | 13 | Vin1 Frequency | Voltage input 1; range 45 to 65 | Hz | Read | |
| AImin | 14 | Vin1 Total Energy Usage | Voltage input 1; range 0 to 100000 | kWh | Read | |
| AI | 21 | Vin2 Line 1 Measured Line-Neutral Voltage (L1-N) | Voltage input 2; range 0 to 100000 | V | Read | |
| AI | 22 | Vin2 Line 2 Measured Line-Neutral Voltage (L2-N) | Voltage input 2; range 0 to 100000 | V | Read | |
| AI | 23 | Vin2 Line 3 Measured Line-Neutral Voltage (L3-N) | Voltage input 2; range 0 to 100000 | V | Read | |
| AI | 24 | Vin2 Line 1 - Line 2 Measured Voltage (L1-L2) | Voltage input 2; range 0 to 100000 | V | Read | |
| AI | 25 | Vin2 Line 2 - Line 3 Measured Voltage (L2-L3) | Voltage input 2; range 0 to 100000 | V | Read | |
| AI | 26 | Vin2 Line 3 - Line 1 Measured Voltage (L3-L1) | Voltage input 2; range 0 to 100000 | V | Read | |
| AI | 27 | Vin2 Line 1 Phase Angle | Voltage input 2; range -360 to 360; units can be changed to radians | ° | Read | |
| AI | 28 | Vin2 Line 2 Phase Angle | Voltage input 2; range -360 to 360; units can be changed to radians | ° | Read | |
| AI | 29 | Vin2 Line 3 Phase Angle | Voltage input 2; range -360 to 360; units can be changed to radians | ° | Read | |
| AI | 30 | Vin2 Line 1 Harmonic Distortion | Voltage input 2; range 0 to 100 | % | Read | |
| AI | 31 | Vin2 Line 2 Harmonic Distortion | Voltage input 2; range 0 to 100 | % | Read | |
| AI | 32 | Vin2 Line 3 Harmonic Distortion | Voltage input 2; range 0 to 100 | % | Read | |
| AI | 33 | Vin2 Frequency | Voltage input 2; range 45 to 65 | Hz | Read | |
| AImin | 34 | Vin2 Total Energy Usage | Voltage input 2 | kWh | Read | |
| NC | 1 | Event Notification Class | Notification class | Read | ||
| MV | 1 | Vin1 Service Type | Electrical service wiring on voltage input 1 | Read | 1=4-Wire wye, 2=3-Wire delta, 3=Reserved, 4=3-Wire single phase (split-phase), 5=2-Wire single phase | |
| MV | 2 | Vin2 Service Type | Electrical service wiring on voltage input 2 | Read | 1=4-Wire wye, 2=3-Wire delta, 3=Reserved, 4=3-Wire single phase (split-phase), 5=2-Wire single phase | |
| Other | 1 | Pulse Input #1 | Pulse Converter object for pulse input 1; units user-configurable | Read | ||
| Other | 2 | Pulse Input #2 | Pulse Converter object for pulse input 2; units user-configurable | Read |
No points match these filters.
Object ID lookup: Johnson Controls EEM Meter Root Device point IDs by name
AI1Vin1 Line 1 Measured Line-Neutral Voltage (L1-N)AI2Vin1 Line 2 Measured Line-Neutral Voltage (L2-N)AI3Vin1 Line 3 Measured Line-Neutral Voltage (L3-N)AI4Vin1 Line 1 - Line 2 Measured Voltage (L1-L2)AI5Vin1 Line 2 - Line 3 Measured Voltage (L2-L3)AI6Vin1 Line 3 - Line 1 Measured Voltage (L3-L1)AI7Vin1 Line 1 Phase AngleAI8Vin1 Line 2 Phase AngleAI9Vin1 Line 3 Phase AngleAI10Vin1 Line 1 Harmonic DistortionAI11Vin1 Line 2 Harmonic DistortionAI12Vin1 Line 3 Harmonic DistortionAI13Vin1 FrequencyAI14Vin1 Total Energy UsageAI21Vin2 Line 1 Measured Line-Neutral Voltage (L1-N)AI22Vin2 Line 2 Measured Line-Neutral Voltage (L2-N)AI23Vin2 Line 3 Measured Line-Neutral Voltage (L3-N)AI24Vin2 Line 1 - Line 2 Measured Voltage (L1-L2)AI25Vin2 Line 2 - Line 3 Measured Voltage (L2-L3)AI26Vin2 Line 3 - Line 1 Measured Voltage (L3-L1)AI27Vin2 Line 1 Phase AngleAI28Vin2 Line 2 Phase AngleAI29Vin2 Line 3 Phase AngleAI30Vin2 Line 1 Harmonic DistortionAI31Vin2 Line 2 Harmonic DistortionAI32Vin2 Line 3 Harmonic DistortionAI33Vin2 FrequencyAI34Vin2 Total Energy UsageNC1Event Notification ClassMV1Vin1 Service TypeMV2Vin2 Service Type
Integration notes
- Objects from the Root Device Object List, page 1 of LIT-12013610.
- The meter shows up as a root device plus one virtual BACnet device per configured load; the two object lists are separate library entries.
- The object list has no access column. Access is inferred: measurements read-only; the guide notes the phase angle units can be written (radians or degrees-phase).
- Network settings in the integration notes come from the EEM Multi-Circuit Installation and Operation Manual (LIT-12013609) on the same portal.
- The pulse inputs are Pulse Converter objects, listed here with type Other.
- The device object name defaults to "No Panel Name".
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EEM Multi-Circuit Electric Energy Meter - Root Device and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
How many BACnet points does the Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device have?
This list has 33 BACnet objects: 28 analog inputs, 1 notification class, 2 multi-state values, 2 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device BACnet documentation?
The source is EEM Multi-Circuit BACnet Object List (LIT-12013610), published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/Yuwx93g3eOD6h4sNaatLFA/content.
What are the minimum BACnet points to integrate the Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device?
Start with AI 1 Vin1 Line 1 Measured Line-Neutral Voltage (L1-N) (Vin1 L1-N voltage, V); AI 2 Vin1 Line 2 Measured Line-Neutral Voltage (L2-N) (Vin1 L2-N voltage, V); AI 3 Vin1 Line 3 Measured Line-Neutral Voltage (L3-N) (Vin1 L3-N voltage, V); AI 13 Vin1 Frequency (Vin1 frequency, Hz); AI 14 Vin1 Total Energy Usage (Vin1 total energy, kWh); AI 34 Vin2 Total Energy Usage (Vin2 total energy, kWh).
How do I check these points on the real EEM Multi-Circuit Electric Energy Meter - Root Device?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771
Source: EEM Multi-Circuit BACnet Object List · LIT-12013610. Object names, instances and units are reproduced as published; descriptions are our own.