VAV / zone damper controller (Verasys) · BACnet points list

Johnson Controls Verasys Zone Equipment Controller (ZEC) BACnet points list

Updated 12 November 2026

Short answer

The Zone Equipment Controller runs one zone of a Verasys zoning system (zone damper or VAV box, optional reheat). Through the SBH it exposes 57 objects in the 90,000 range: zone and discharge temperatures, occupied/unoccupied/standby setpoints, airflow limits, damper limits, DCV settings, enables, occupancy mode and zone vote.

This page lists 57 BACnet objects for the Johnson Controls Verasys Zone Equipment Controller (ZEC) — 38 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.

Manufacturer
Johnson Controls
Model
Verasys Zone Equipment Controller (ZEC)
Equipment
VAV / zone damper controller (Verasys)
Equipment type
VAV boxes & fan coils
BACnet objects
57 (38 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
ZEC, Verasys ZEC, Zone Equipment Controller
Source document
Verasys BACnet over IP Integration User Guide · LIT-12013287 · rev. 2024-03-11
Download CSV 57 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.

BMS integration notes: Johnson Controls Verasys Zone Equipment Controller (ZEC)

Integration in brief

Integrate through the Verasys Smart Building Hub: enable BACnet routing on the SBH, and the supervisor then sees each system bus device behind the SBH's MS/TP network. Map the enable and occupancy commands, the main setpoints and the status and alarm points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 90032UNIT-ENUnit enableWrite
MV 90037OCC-MODEOccupancy modeWrite
AV 90006CLGOCC-SPOccupied cooling setpointWrite
AV 90007HTGOCC-SPOccupied heating setpointWrite
AV 90000ZN-TZone temperatureRead
AV 90051FLOWAirflowRead
AV 90052FLOW-SPAirflow setpointRead
AV 90003DA-TDischarge air temperatureRead
MV 90062HTGCLG-MODEHeating/cooling modeRead
MV 90060ZN-VOTEZone voteRead

Network setup

Watch out for

Johnson Controls Verasys Zone Equipment Controller (ZEC) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

57 of 57 shown
Type
AnalogMulti-state
Access
Show
Johnson Controls Verasys Zone Equipment Controller (ZEC) BACnet Points List
DescriptionStates
AVmin90000ZN-TZone TemperatureRead
AV90001IAQIndoor Air QualityRead
AV90002WC-ADJLIMWarmer/Cooler AdjustRead
AVmin90003DA-TDischarge Air TemperatureRead
MV90004TEMP-OCCTemp OccRead
AVmin90006CLGOCC-SPOccupied Cooling SetpointWrite
AVmin90007HTGOCC-SPOccupied Heating SetpointWrite
AV90008CLGUNOCC-SUnoccupied Cooling SetpointWrite
AV90009HTGUNOCC-SUnoccupied Heating SetpointWrite
AV90011CLGUNOCC-FLOWUnoccupied Cooling Min FlowWrite
AV90012HTGUNOCC-FLOWUnoccupied Heating Min FlowWrite
AV90013WARM-FLOWWarmup Min FlowWrite
AV90014RHT-FLOWStaged Reheat Min FlowWrite
AV90015DAT-SPSupply Air Temperature SetpointWrite
AV90016DCVMAX-FLOWDCV Max FlowWrite
AV90017DCVCLGOCC-FLOWDCV Occupied Cooling Min FlowWrite
AV90018DCVHTGOCC-FLOWDCV Occupied Heating Min FlowWrite
AV90019DATMAXHTG-SPDCV Max FlowWrite
AV90020SBY-CLG-SPStandby Cooling SetpointWrite
AV90021SBY-HTG-SPStandby Heating SetpointWrite
AV90022LS-ADJLoad Shed AdjustWrite
AV90023LS-RATELIMLoad Shed Rate LimitWrite
AV90024DMPRCLGMIN-POSDamper Cooling Min PositionWrite
AV90025DMPRHTGMIN-POSDamper Heating Min PositionWrite
AV90026DMPRMAX-POSDamper Max PositionWrite
AV90027DCVCLGMIN-POSDCV Cooling Min ValueWrite
AV90028DCVHTGMIN-POSDCV Heating Min ValueWrite
AV90029DCVMAX-POSDCV Max Vent PositionWrite
AV90030DVENTIAQ-SPDemand Ventilation Indoor Air Quality SetpointWrite
MVmin90032UNIT-ENUnit EnableWrite
MV90034WC-ENWarmer/Cooler Adjust EnableWrite
MV90035DUALMAX-ENDual Max EnableWrite
MV90036DCV-ENDCV EnableWrite
MVmin90037OCC-MODEOccupancy ModeWrite
MV90039VOTE-ALLOWEDZone Vote AllowedWrite
MV90040HTG-CHeating Stage 1 CommandRead
MV90041DPR-ODamper PositionRead
MV90042SUPHTG1-CSupplemental Heating Stage 1 CommandRead
MV90043HTG-STG1-CHeating Stage 1 CommandRead
AV90044ZCU-SATHeating Stage 2 CommandRead
MV90045SF-CFan CommandRead
AV90046SUPHTG-STSupplemental Heating Stroke TimeWrite
AV90048CLGMAX-FLOWCooling Max FlowWrite
AV90049CLGOCCMIN-FLOWOccupied Cooling Min FlowWrite
AV90050HTGOCCMIN-FLOWOccupied Heating Min FlowWrite
AVmin90051FLOWSupply FlowRead
AVmin90052FLOW-SPSupply Flow SetpointRead
AV90053HTGDAT-SPBox Heating Supply Temp SetpointRead
AV90054EFF-SPActive SetpointRead
MVmin90060ZN-VOTEZone VoteRead
MVmin90062HTGCLG-MODEActive ModeRead
MV90066VENT-SVentilation RequestRead
MV90067EFF-OCCEffective OccupancyRead
MV90068AUTOTUNE-ENAuto Tuning EnableWrite
MV90069ZONE-WEIGHTZone WeightWrite
MV90070LS-ALLOWEDLoad Shed AllowedWrite
MV90072TEMP-OCC-ENTemp Occ EnableWrite
Object ID lookup: Johnson Controls Verasys Zone Equipment Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Verasys Zone Equipment Controller (ZEC) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Johnson Controls Verasys Zone Equipment Controller (ZEC)

How many BACnet points does the Johnson Controls Verasys Zone Equipment Controller (ZEC) have?

This list has 57 BACnet objects: 37 analog values, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Johnson Controls Verasys Zone Equipment Controller (ZEC) BACnet points are writable?

38 of the 57 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Johnson Controls Verasys Zone Equipment Controller (ZEC) BACnet documentation?

The source is Verasys BACnet over IP Integration User Guide (LIT-12013287), revision 2024-03-11, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/maps/bQUUXbLn_sJI5F5XzKax0Q/attachments/ETDjFYqCzPvla4mPr0wdlw-bQUUXbLn_sJI5F5XzKax0Q/content.

What are the minimum BACnet points to integrate the Johnson Controls Verasys Zone Equipment Controller (ZEC)?

Start with MV 90032 UNIT-EN (Unit enable); MV 90037 OCC-MODE (Occupancy mode); AV 90006 CLGOCC-SP (Occupied cooling setpoint); AV 90007 HTGOCC-SP (Occupied heating setpoint); AV 90000 ZN-T (Zone temperature); AV 90051 FLOW (Airflow); AV 90052 FLOW-SP (Airflow setpoint); AV 90003 DA-T (Discharge air temperature); MV 90062 HTGCLG-MODE (Heating/cooling mode); MV 90060 ZN-VOTE (Zone vote).

How do I check these points on the real Verasys Zone Equipment Controller (ZEC)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Johnson Controls BACnet points lists