- PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)
Refrigerated display case controller · BACnet points list
Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP) BACnet points list
Updated 12 November 2026
The MR5 controls one refrigerated case: compressor, defrost, evaporator fan and alarm relays from up to three temperature sensors, with optional QREV/PSHC superheat sensor. Through the ADPT-MR5-RS485 adapter it joins a BACnet MS/TP or Verasys network and exposes 51 objects: case temperatures, relay states, QREV/PSHC readings, binary inputs, the setpoint and differential, defrost settings and defrost times, and leak/door/QREV alarms.
This page lists 51 BACnet objects for the Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)
- Equipment
- Refrigerated display case controller
- Equipment type
- Other equipment
- BACnet objects
- 51 (15 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1
- Also known as
- MR5, MR534, MR534AFDV, MR534AFDN, PENN MR5, ADPT-MR5-RS485, LIT-12013019, JCI refrigeration case controller
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)
Fit the ADPT-MR5-RS485 adapter (included on MR534AFDV), set MS/TP connectivity to BACnet and a unique device address and device ID, then read case temperature, relay states and alarms. The BMS can adjust the setpoint and differential and defrost settings.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 10321 | SetPoint | Case temperature setpoint | Write |
| AV 10329 | Differential | Control differential | Write |
| AI 10218 | Average Case Temperature | Average case temperature | Read |
| AI 10005 | Sensor 1 : Temperature | Sensor 1 (case) temperature | Read |
| BO 10446 | Compressor Relay | Compressor relay state | Read |
| BO 10449 | Defrost Relay | Defrost relay state | Read |
| BO 10452 | Fan Relay | Evaporator fan relay state | Read |
| BI 10434 | Alarm Refrigeration Leak | Refrigerant leak alarm | Read |
| BI 10437 | Alarm Door Open | Door open alarm | Read |
| BO 10440 | Alarm Relay | Alarm relay state | Read |
Network setup
- Network needs the ADPT-MR5-RS485 adapter; MR534AFDN models need it bought separately.
- Set MS/TP CONNECTIVITY to BAC-NET (or Verasys) in the BACNET setup menu.
- Default BACnet device address (MAC) 07 and device ID 1; change both on the BACNET setup screens.
- Baud rates 9.6k, 19.2k and 38.4k. The adapter has no EOL switch; fit a 220 ohm resistor across + and - at the trunk ends.
Watch out for
- Change the default device ID 1 before adding several MR5s to one site.
- Defrost times (TV objects) are read-only over BACnet.
Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | 1 | MR5 Case Controller | Device object | Read | ||
| AImin | 10005 | Sensor 1 : Temperature | Case sensor 1, -45 to 140 °F; trended | °F | Read | |
| AI | 10008 | Sensor 2 : Temperature | Sensor 2, -45 to 140 °F | °F | Read | |
| AI | 10011 | Sensor 3 : Temperature | Sensor 3, -45 to 140 °F | °F | Read | |
| AImin | 10218 | Average Case Temperature | Average case temperature | °F | Read | |
| AI | 10428 | Average Defrost Temperature | Average defrost temperature | °F | Read | |
| BOmin | 10446 | Compressor Relay | Compressor relay state | Read | 0=Inactive, 1=Active | |
| BOmin | 10449 | Defrost Relay | Defrost relay state | Read | 0=Inactive, 1=Active | |
| BOmin | 10452 | Fan Relay | Evaporator fan relay state | Read | 0=Inactive, 1=Active | |
| BOmin | 10440 | Alarm Relay | Alarm relay state | Read | 0=Inactive, 1=Active | |
| BO | 10443 | Auxiliary Relay | Auxiliary relay state | Read | 0=Inactive, 1=Active | |
| AI | 10197 | QREV/PSHC : Superheat | Superheat from QREV/PSHC sensor, -40 to 212 °F | °F | Read | |
| AI | 10200 | QREV/PSHC : Temperature | QREV/PSHC temperature, -40 to 212 °F | °F | Read | |
| AI | 10212 | QREV/PSHC : Pressure | QREV/PSHC pressure, 100-3445 kPa (14.5-500 psi) | kPa | Read | |
| AI | 10215 | QREV/PSHC : Current State | QREV/PSHC notification code 0000-9999 | Read | ||
| MV | 10290 | QREV/PSHC : Refrigerant | Refrigerant type set in the QREV/PSHC | Read | 1=R410A, 2=R404, 3=R407A, 4=R134A, 5=Reserved, 6=R22, 7=R407C, 8=R_407F, 9=R_417A, 10=R_422A, 11=R_422D, 12=R_427A, 13=R_438A, 14=R_448A, 15=R_449A, 16=R_450A, 17=R_507A, 18=R_513A, 19-21=Unknown | |
| BI | 10020 | Binary Input 1 : State | Binary input 1 contact | Read | 0=Open, 1=Close | |
| BI | 10416 | Binary Input 2 : State | Binary input 2 contact | Read | 0=Open, 1=Close | |
| MV | 10461 | Binary Input 1 : Mode | Binary input 1 function | Read | 1=None, 2=Refrigerant Leak, 3=Door Open | |
| MV | 10455 | Binary Input 2 : Mode | Binary input 2 function | Read | 1=None, 2=Refrigerant Leak, 3=Door Open | |
| MV | 10389 | Auto DST | Automatic daylight saving time | Read | 1=No, 2=Yes | |
| MV | 10371 | Relay Selection | Use of the shared relay | Read | 1=Fan, 2=Auxiliary | |
| AVmin | 10321 | SetPoint | Case temperature setpoint, -40 to 122 °F | °F | Write | |
| AVmin | 10329 | Differential | Control differential, 1-15 °F | °F | Write | |
| MV | 10272 | Case Sensor : Failure Mode | Compressor action on case sensor failure | Write | 1=On, 2=Off, 3=Average | |
| AV | 10327 | Anti-Short Cycle Delay | Compressor anti-short-cycle delay, 0-12 min | min | Write | |
| MV | 10386 | Fan State : Compressor OFF | Evaporator fan state while compressor is off | Write | 1=Off, 2=On | |
| AV | 10330 | Max Defrost Duration | Maximum defrost duration, 0-99 min | min | Write | |
| MV | 10380 | Defrost Schedule Type | Defrost schedule type | Write | 1=Schedule, 2=Adaptive | |
| AV | 10331 | Adaptive Interval | Adaptive defrost interval, 1-48 h | h | Write | |
| AV | 10322 | Adaptive Defrost Duration | Adaptive defrost duration, 0-99 min | min | Write | |
| AV | 10323 | Max Time Between Defrost | Maximum time between defrosts, 3-48 h | h | Write | |
| AV | 10324 | Min Time Between Defrost | Minimum time between defrosts, 3-24 h | h | Write | |
| AV | 10325 | Blackout Duration | Defrost blackout duration, 0-240 min | min | Write | |
| MV | 10412 | Reset History | Reset history | Write | 1=No, 2=Yes | |
| MV | 10383 | Defrost Schedule | Defrost schedule mode | Write | 1=Automatic, 2=Manual | |
| AV | 10326 | Defrost Scheduled Per Day | Number of defrosts per day, 0-8 | Write | ||
| Other | 10821 | Next Defrost time | Time Value object (TV) | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10820 | Blackout Start Time | Time Value object (TV) | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10812 | First Defrost | Time Value object (TV): defrost time 1 | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10813 | Second Defrost | Time Value object (TV): defrost time 2 | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10814 | Third Defrost | Time Value object (TV): defrost time 3 | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10815 | Fourth Defrost | Time Value object (TV): defrost time 4 | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10816 | Fifth Defrost | Time Value object (TV): defrost time 5 | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10817 | Sixth Defrost | Time Value object (TV): defrost time 6 | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10818 | Seventh Defrost | Time Value object (TV): defrost time 7 | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| Other | 10819 | Eighth Defrost | Time Value object (TV): defrost time 8 | Read | 00:00:00 to 23:59:59 (Hr:Min:Sec) | |
| BI | 10368 | QREV/PSHC Alarm Status | QREV/PSHC alarm | Read | 0=Normal, 1=Alarm | |
| BI | 10365 | QREV/PSHC Communication Loss | Lost communication with QREV/PSHC | Read | 0=Normal, 1=Alarm | |
| BImin | 10434 | Alarm Refrigeration Leak | Refrigerant leak alarm | Read | 0=Normal, 1=Alarm | |
| BImin | 10437 | Alarm Door Open | Door open alarm | Read | 0=Normal, 1=Alarm |
No points match these filters.
Object ID lookup: Johnson Controls PENN MR5 Case Controller point IDs by name
AI10005Sensor 1 : TemperatureAI10008Sensor 2 : TemperatureAI10011Sensor 3 : TemperatureAI10218Average Case TemperatureAI10428Average Defrost TemperatureBO10446Compressor RelayBO10449Defrost RelayBO10452Fan RelayBO10440Alarm RelayBO10443Auxiliary RelayAI10197QREV/PSHC : SuperheatAI10200QREV/PSHC : TemperatureAI10212QREV/PSHC : PressureAI10215QREV/PSHC : Current StateMV10290QREV/PSHC : RefrigerantBI10020Binary Input 1 : StateBI10416Binary Input 2 : StateMV10461Binary Input 1 : ModeMV10455Binary Input 2 : ModeMV10389Auto DSTMV10371Relay SelectionAV10321SetPointAV10329DifferentialMV10272Case Sensor : Failure ModeAV10327Anti-Short Cycle DelayMV10386Fan State : Compressor OFFAV10330Max Defrost DurationMV10380Defrost Schedule TypeAV10331Adaptive IntervalAV10322Adaptive Defrost DurationAV10323Max Time Between DefrostAV10324Min Time Between DefrostAV10325Blackout DurationMV10412Reset HistoryMV10383Defrost ScheduleAV10326Defrost Scheduled Per DayBI10368QREV/PSHC Alarm StatusBI10365QREV/PSHC Communication LossBI10434Alarm Refrigeration LeakBI10437Alarm Door Open
Integration notes
- Time objects are printed as TV (Time Value) and shown here as type Other with the same instance.
- The bulletin is marked Discontinued.
- Sensor 1 : Temperature (AI 10005) is the only object that supports trending (144 samples, every 10 min or on COV).
- The table also marks which objects support BACnet alarms (sensor temperatures and the four alarm BIs).
- Units for temperatures follow the controller setting; the table prints ranges in °F and °C.
- Source: Table 29 'MR5 BACnet objects available on Verasys or standard BACnet', pages 61-64 (51 objects).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)
How many BACnet points does the Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP) have?
This list has 51 BACnet objects: 9 analog inputs, 10 analog values, 6 binary inputs, 5 binary outputs, 1 device, 10 multi-state values, 10 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP) BACnet points are writable?
15 of the 51 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP) BACnet documentation?
The source is MR5 Series Panel Mount Case Controller Technical Bulletin (LIT-12013019), revision 2019-08-13, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/PFZ9MbhezH_qtq06OykSww/content.
What are the minimum BACnet points to integrate the Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)?
Start with AV 10321 SetPoint (Case temperature setpoint); AV 10329 Differential (Control differential); AI 10218 Average Case Temperature (Average case temperature); AI 10005 Sensor 1 : Temperature (Sensor 1 (case) temperature); BO 10446 Compressor Relay (Compressor relay state); BO 10449 Defrost Relay (Defrost relay state); BO 10452 Fan Relay (Evaporator fan relay state); BI 10434 Alarm Refrigeration Leak (Refrigerant leak alarm); BI 10437 Alarm Door Open (Door open alarm); BO 10440 Alarm Relay (Alarm relay state).
How do I check these points on the real PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Room pressure controller (isolation room)
Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-1655 room pressure controllers for isolation rooms, labs and cleanrooms, with optional anteroom and flow inputs.
Also known as: FMS-1655, FMS1655, Triatek FMS-1655, Triatek room pressure controller, JCI room pressure controller, LIT-12013120 - Room pressure controller (critical environment)
Johnson Controls Triatek FMS-2000C Critical Environment Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000C critical environment controllers for isolation rooms, labs and cleanrooms (successor of the FMS-1655).
Also known as: FMS-2000C, FMS2000C, FMS-2000, Triatek FMS-2000C, LIT-12013504, JCI critical environment controller - Room pressure monitor (critical environment)
Johnson Controls Triatek FMS-2000M Critical Environment Monitor (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000M critical environment monitors with one to four differential pressure sensors (models FMS2M-Bx1x to Bx4x).
Also known as: FMS-2000M, FMS2000M, Triatek FMS-2000M, FMS2M, FMS2M-Bx1x, FMS2M-Bx2x, FMS2M-Bx3x, FMS2M-Bx4x, LIT-12013580 - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Bypass damper controller (Verasys zoning)
Johnson Controls Verasys BYP200 Bypass Controller
Verasys BYP200 bypass damper controllers that hold duct static pressure in a zoning system.
Also known as: BYP200, Verasys bypass controller - General purpose I/O controller (Verasys)
Johnson Controls Verasys generic IO controller
Verasys generic IO controllers with digital and analog inputs, outputs, NetSensors and energy meters on the system bus.
Also known as: Verasys generic IO, Verasys IO controller, Verasys GIO - Rooftop unit controller (Smart Equipment)
Johnson Controls Verasys SSE system bus (Smart Equipment rooftop board)
Rooftop units with the Simplicity SE / Smart Equipment (SSE) control board connected to a Verasys system bus.
Also known as: SSE, Simplicity SE, Verasys SSE - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC1000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC1000 Constant Volume Controller.
Also known as: VAC1000, Verasys VAC1000, Verasys constant volume controller - Lighting controller (Verasys)
Johnson Controls Verasys VAC1001 Lighting Controller
Verasys VAC1001 lighting controllers with up to 9 lighting circuits grouped into zones.
Also known as: VAC1001, Verasys lighting controller - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC3000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC3000 Constant Volume Controller.
Also known as: VAC3000, Verasys VAC3000, Verasys constant volume controller, Verasys CV controller - VAV / zone damper controller (Verasys)
Johnson Controls Verasys Zone Equipment Controller (ZEC)
Verasys Zone Equipment Controllers serving zone dampers and VAV boxes in a Verasys zoning system.
Also known as: ZEC, Verasys ZEC, Zone Equipment Controller - Rooftop unit controller (Verasys zoning)
Johnson Controls Verasys Zoning RTU (rooftop unit on the Verasys system bus)
Rooftop units integrated as the air source of a Verasys zoning system.
Also known as: Verasys Zoning RTU, Verasys RTU, Verasys zoning rooftop - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771 - Zoning system coordinator
Johnson Controls VZC100 Verasys Zone Coordinator
Verasys VZC100 zone coordinators that run a zoned rooftop system (zone voting, duct pressure and discharge air resets).
Also known as: VZC100, Verasys Zone Coordinator
Source: MR5 Series Panel Mount Case Controller Technical Bulletin · LIT-12013019 · rev. 2019-08-13. Object names, instances and units are reproduced as published; descriptions are our own.