- Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)
Room pressure controller (isolation room) · BACnet points list
Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The FMS-1655 holds and monitors room differential pressure by driving a damper, with four configurable analog inputs, two thermistor inputs, four analog outputs, four digital inputs and four relays. It talks BACnet MS/TP or Metasys N2. The BACnet table has 90 objects: I/O, setpoints, alarm and warning limits, network-written values, airflow and volumetric offset, output overrides, deadbands, isolation mode commands and alarm status.
This page lists 90 BACnet objects for the Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP) — 60 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.
- Manufacturer
- Johnson Controls
- Model
- Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)
- Equipment
- Room pressure controller (isolation room)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 90 (60 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 85000 + MAC address
- Also known as
- FMS-1655, FMS1655, Triatek FMS-1655, Triatek room pressure controller, JCI room pressure controller, LIT-12013120
Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.
BMS integration notes: Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)
Map the room isolation mode command, the room pressure setpoint, the measured room pressure, the damper output and the primary alarm status. Write network variables (AV 43-46) only if the BAS supplies those values.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MO 1 | Primary solation Mode | Isolation mode: 1 positive, 2 negative, 3 neutral | Write |
| AV 1 | AI-1 Setpoint (Room Pressure) | Room pressure setpoint | Write |
| AI 1 | Analog Input 1 (default: Isolation Pressure) | Room (isolation) pressure | Read |
| AO 1 | Analog Output 1 (default: Damper Position) | Damper position output | Read |
| BI 1 | Digital Input 1 (default: Door Switch) | Door switch | Read |
| MO 3 | Primary Alarm Status | Primary alarm: 1 normal, 2 warning, 3 alarm | Read |
Enable & remote start
Primary Isolation Mode (MSO 1) is writable: 1 positive, 2 negative, 3 neutral.
Sensors & values from the BMS
AV 43-46 are writable network variables for humidity, temperature, air changes and differential pressure sent from the BAS.
Network setup
- BACnet MS/TP is the default protocol; Metasys N2 is the alternative.
- Device instance = Device ID Offset (default 85,000, set in steps of 1,000) + MAC address, e.g. MAC 123 gives 85,123.
- MS/TP master MAC range 1-127; Max_Master default 127; baud rate chosen from four standard rates on the Network Setup menu.
Watch out for
- Alarm limits, deadbands and setpoints are setup values; don't write them cyclically.
- What each analog input measures depends on how it is configured; names give the default use.
Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Analog Input 1 (default: Isolation Pressure) | Read | |||
| AI | 2 | Analog Input 2 | Read | |||
| AI | 3 | Analog Input 3 | Read | |||
| AI | 4 | Analog Input 4 | Read | |||
| AI | 5 | Thermistor Input 1 | Read | |||
| AI | 6 | Thermistor Input 2 | Read | |||
| AOmin | 1 | Analog Output 1 (default: Damper Position) | Read | |||
| AO | 2 | Analog Output 2 (default: Anteroom Damper Control) | Read | |||
| AO | 3 | Analog Output 3 (spare control output) | Read | |||
| AO | 4 | Analog Output 4 (spare control output) | Read | |||
| BImin | 1 | Digital Input 1 (default: Door Switch) | Read | |||
| BI | 2 | Digital Input 2 (default: Anteroom Door Switch) | Read | |||
| BI | 3 | Digital Input 3 (spare digital input) | Read | |||
| BI | 4 | Digital Input 4 (spare digital input) | Read | |||
| BO | 1 | Relay Output 1 (default: Primary Alarm Relay Output) | Read | |||
| BO | 2 | Relay Output 2 (default: Spare Relay Output) | Read | |||
| BO | 3 | Relay Output 3 (spare relay output) | Read | |||
| BO | 4 | Not user-selectable | Read | |||
| AVmin | 1 | AI-1 Setpoint (Room Pressure) | Control setpoint | Write | ||
| AV | 2 | AI-2 Setpoint | Control setpoint | Write | ||
| AV | 3 | AI-3 Setpoint | Control setpoint | Write | ||
| AV | 4 | AI-4 Setpoint | Control setpoint | Write | ||
| AV | 5 | TI-1 Setpoint | Control setpoint | Write | ||
| AV | 6 | TI-2 Setpoint | Control setpoint | Write | ||
| AV | 7 | Air Change Rate based on Flow Input at AI-1 | Air change rate from flow input | Write | ||
| AV | 8 | Air Change Rate based on Flow Input at AI-2 | Air change rate from flow input | Write | ||
| AV | 9 | Air Change Rate based on Flow Input at AI-3 | Air change rate from flow input | Write | ||
| AV | 10 | Air Change Rate based on Flow Input at AI-4 | Air change rate from flow input | Write | ||
| AV | 11 | Alarm Relay 1 High Setpoint | Alarm relay trip limit | Write | ||
| AV | 12 | Alarm Relay 1 Low Setpoint | Alarm relay trip limit | Write | ||
| AV | 13 | Alarm Relay 2 High Setpoint | Alarm relay trip limit | Write | ||
| AV | 14 | Alarm Relay 2 Low Setpoint | Alarm relay trip limit | Write | ||
| AV | 15 | Alarm Relay 3 High Setpoint | Alarm relay trip limit | Write | ||
| AV | 16 | Alarm Relay 3 Low Setpoint | Alarm relay trip limit | Write | ||
| AV | 17 | Not user-selectable | Write | |||
| AV | 18 | Not user-selectable | Write | |||
| AV | 19 | AI-1 Low Alarm Setpoint (low pressure alarm) | Alarm / warning limit | Write | ||
| AV | 20 | AI-1 Low Warning Setpoint (low pressure warning) | Alarm / warning limit | Write | ||
| AV | 21 | AI-1 High Warning Setpoint (high pressure warning) | Alarm / warning limit | Write | ||
| AV | 22 | AI-1 High Alarm Setpoint (high pressure alarm) | Alarm / warning limit | Write | ||
| AV | 23 | AI-2 Low Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 24 | AI-2 Low Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 25 | AI-2 High Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 26 | AI-2 High Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 27 | AI-3 Low Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 28 | AI-3 Low Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 29 | AI-3 High Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 30 | AI-3 High Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 31 | AI-4 Low Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 32 | AI-4 Low Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 33 | AI-4 High Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 34 | AI-4 High Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 35 | TI-1 Low Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 36 | TI-1 Low Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 37 | TI-1 High Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 38 | TI-1 High Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 39 | TI-2 Low Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 40 | TI-2 Low Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 41 | TI-2 High Warning Setpoint | Alarm / warning limit | Write | ||
| AV | 42 | TI-2 High Alarm Setpoint | Alarm / warning limit | Write | ||
| AV | 43 | Writable Network Variable – Humidity | Value written by the BAS | Write | ||
| AV | 44 | Writable Network Variable – Temperature | Value written by the BAS | Write | ||
| AV | 45 | Writable Network Variable – Air Changes | Value written by the BAS | Write | ||
| AV | 46 | Writable Network Variable – Differential Pressure | Value written by the BAS | Write | ||
| AV | 47 | Device ID Offset (range: 0 – 4,194,000) | Device instance = offset + MAC | Write | ||
| AV | 48 | Duct Air Flow based on AI-1 flow input | Duct airflow from flow input | Read | ||
| AV | 49 | Duct Air Flow based on AI-2 flow input | Duct airflow from flow input | Read | ||
| AV | 50 | Duct Air Flow based on AI-3 flow input (Supply Flow) | Duct airflow from flow input | Read | ||
| AV | 51 | Duct Air Flow based on AI-4 flow input (Exhaust Flow) | Duct airflow from flow input | Read | ||
| AV | 52 | Volumetric Offset (Supply Flow – Exhaust Flow) | Supply minus exhaust flow | Read | ||
| AV | 53 | Volumetric Offset Setpoint | Control setpoint | Write | ||
| AV | 54 | AO-1 Override Level | Output override level | Write | ||
| AV | 55 | AO-2 Override Level | Output override level | Write | ||
| AV | 56 | AO-3 Override Level | Output override level | Write | ||
| AV | 57 | AO-4 Override Level | Output override level | Write | ||
| AV | 58 | AI-1 Deadband Setting | Control deadband | Write | ||
| AV | 59 | AI-2 Deadband Setting | Control deadband | Write | ||
| AV | 60 | AI-3 Deadband Setting | Control deadband | Write | ||
| AV | 61 | AI-4 Deadband Setting | Control deadband | Write | ||
| AV | 62 | TI-1 Deadband Setting | Control deadband | Write | ||
| AV | 63 | TI-2 Deadband Setting | Control deadband | Write | ||
| MOmin | 1 | Primary solation Mode | Room isolation mode | Write | 1=positive, 2=negative, 3=neutral | |
| MO | 2 | Secondary Isolation Mode | Room isolation mode | Write | 1=positive, 2=negative, 3=neutral | |
| MOmin | 3 | Primary Alarm Status | Alarm status | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 4 | Secondary Alarm Status | Alarm status | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 5 | AI-3 Alarm Status | Alarm status | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 6 | AI-4 Alarm Status | Alarm status | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 7 | TI-1 Alarm Status | Alarm status | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 8 | TI-2 Alarm Status | Alarm status | Read | 1=normal, 2=warning, 3=alarm | |
| MO | 9 | Offset Control Status | Volumetric offset control status | Read |
No points match these filters.
Object ID lookup: Johnson Controls FMS-1655 Room Pressure Controller point IDs by name
AI1Analog Input 1 (default: Isolation Pressure)AI2Analog Input 2AI3Analog Input 3AI4Analog Input 4AI5Thermistor Input 1AI6Thermistor Input 2AO1Analog Output 1 (default: Damper Position)AO2Analog Output 2 (default: Anteroom Damper Control)AO3Analog Output 3 (spare control output)AO4Analog Output 4 (spare control output)BI1Digital Input 1 (default: Door Switch)BI2Digital Input 2 (default: Anteroom Door Switch)BI3Digital Input 3 (spare digital input)BI4Digital Input 4 (spare digital input)BO1Relay Output 1 (default: Primary Alarm Relay Output)BO2Relay Output 2 (default: Spare Relay Output)BO3Relay Output 3 (spare relay output)BO4Not user-selectableAV1AI-1 Setpoint (Room Pressure)AV2AI-2 SetpointAV3AI-3 SetpointAV4AI-4 SetpointAV5TI-1 SetpointAV6TI-2 SetpointAV7Air Change Rate based on Flow Input at AI-1AV8Air Change Rate based on Flow Input at AI-2AV9Air Change Rate based on Flow Input at AI-3AV10Air Change Rate based on Flow Input at AI-4AV11Alarm Relay 1 High SetpointAV12Alarm Relay 1 Low SetpointAV13Alarm Relay 2 High SetpointAV14Alarm Relay 2 Low SetpointAV15Alarm Relay 3 High SetpointAV16Alarm Relay 3 Low SetpointAV17Not user-selectableAV18Not user-selectableAV19AI-1 Low Alarm Setpoint (low pressure alarm)AV20AI-1 Low Warning Setpoint (low pressure warning)AV21AI-1 High Warning Setpoint (high pressure warning)AV22AI-1 High Alarm Setpoint (high pressure alarm)AV23AI-2 Low Alarm SetpointAV24AI-2 Low Warning SetpointAV25AI-2 High Warning SetpointAV26AI-2 High Alarm SetpointAV27AI-3 Low Alarm SetpointAV28AI-3 Low Warning SetpointAV29AI-3 High Warning SetpointAV30AI-3 High Alarm SetpointAV31AI-4 Low Alarm SetpointAV32AI-4 Low Warning SetpointAV33AI-4 High Warning SetpointAV34AI-4 High Alarm SetpointAV35TI-1 Low Alarm SetpointAV36TI-1 Low Warning SetpointAV37TI-1 High Warning SetpointAV38TI-1 High Alarm SetpointAV39TI-2 Low Alarm SetpointAV40TI-2 Low Warning SetpointAV41TI-2 High Warning SetpointAV42TI-2 High Alarm SetpointAV43Writable Network Variable – HumidityAV44Writable Network Variable – TemperatureAV45Writable Network Variable – Air ChangesAV46Writable Network Variable – Differential PressureAV47Device ID Offset (range: 0 – 4,194,000)AV48Duct Air Flow based on AI-1 flow inputAV49Duct Air Flow based on AI-2 flow inputAV50Duct Air Flow based on AI-3 flow input (Supply Flow)AV51Duct Air Flow based on AI-4 flow input (Exhaust Flow)AV52Volumetric Offset (Supply Flow – Exhaust Flow)AV53Volumetric Offset SetpointAV54AO-1 Override LevelAV55AO-2 Override LevelAV56AO-3 Override LevelAV57AO-4 Override LevelAV58AI-1 Deadband SettingAV59AI-2 Deadband SettingAV60AI-3 Deadband SettingAV61AI-4 Deadband SettingAV62TI-1 Deadband SettingAV63TI-2 Deadband SettingMO1Primary solation ModeMO2Secondary Isolation ModeMO3Primary Alarm StatusMO4Secondary Alarm StatusMO5AI-3 Alarm StatusMO6AI-4 Alarm StatusMO7TI-1 Alarm StatusMO8TI-2 Alarm StatusMO9Offset Control Status
Integration notes
- Object names are the manual's functional descriptions. Multistate objects are printed as MSO (multistate output) and shown here as MO.
- MSO 1 is printed "Primary solation Mode" (sic).
- AV 17/18 and BO 4 are marked 'Not user-selectable'.
- Units are not printed in the BACnet table.
- The same manual also has a Metasys N2 object table (pages 64-65), not included here.
- Source: 'BACnet Objects' table, manual pages 62-63 (PDF pages 65-66), 90 objects.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)
How many BACnet points does the Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP) have?
This list has 90 BACnet objects: 6 analog inputs, 4 analog outputs, 63 analog values, 4 binary inputs, 4 binary outputs, 9 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP) BACnet points are writable?
60 of the 90 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP) BACnet documentation?
The source is FMS-1655 Room Pressure Controller Programming Manual (LIT-12013120 Rev. A), revision 2018-08, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/JIDP3G795sTe0t6ZnGsF2g/content.
What are the minimum BACnet points to integrate the Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)?
Start with MO 1 Primary solation Mode (Isolation mode: 1 positive, 2 negative, 3 neutral); AV 1 AI-1 Setpoint (Room Pressure) (Room pressure setpoint); AI 1 Analog Input 1 (default: Isolation Pressure) (Room (isolation) pressure); AO 1 Analog Output 1 (default: Damper Position) (Damper position output); BI 1 Digital Input 1 (default: Door Switch) (Door switch); MO 3 Primary Alarm Status (Primary alarm: 1 normal, 2 warning, 3 alarm).
How do I enable BMS control of the Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)?
Primary Isolation Mode (MSO 1) is writable: 1 positive, 2 negative, 3 neutral.
Can the BMS supply sensor values to the Johnson Controls Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)?
AV 43-46 are writable network variables for humidity, temperature, air changes and differential pressure sent from the BAS.
How do I check these points on the real Triatek FMS-1655 Room Pressure Controller (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Johnson Controls BACnet points lists
- Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2001.
Also known as: ATC1100, LC-ATC1100-0, Application #2001, ATC app 2001, ATC1100 2001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2002 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2002.
Also known as: ATC1100, LC-ATC1100-0, Application #2002, ATC app 2002, ATC1100 2002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2003 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2003.
Also known as: ATC1100, LC-ATC1100-0, Application #2003, ATC app 2003, ATC1100 2003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2004.
Also known as: ATC1100, LC-ATC1100-0, Application #2004, ATC app 2004, ATC1100 2004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2005.
Also known as: ATC1100, LC-ATC1100-0, Application #2005, ATC app 2005, ATC1100 2005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2006 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1100 with application #2006.
Also known as: ATC1100, LC-ATC1100-0, Application #2006, ATC app 2006, ATC1100 2006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2007 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2007.
Also known as: ATC1100, LC-ATC1100-0, Application #2007, ATC app 2007, ATC1100 2007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1100 Fan Coil Controller - Application #2008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan and an optional on/off fresh-air damper, run by the Johnson Controls ATC1100 with application #2008.
Also known as: ATC1100, LC-ATC1100-0, Application #2008, ATC app 2008, ATC1100 2008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3001 (Two-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3001.
Also known as: ATC1500, LC-ATC1500-0, Application #3001, ATC app 3001, ATC1500 3001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3002 (Two-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3002.
Also known as: ATC1500, LC-ATC1500-0, Application #3002, ATC app 3002, ATC1500 3002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3003 (Two-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3003.
Also known as: ATC1500, LC-ATC1500-0, Application #3003, ATC app 3003, ATC1500 3003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3004 (Two-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3004.
Also known as: ATC1500, LC-ATC1500-0, Application #3004, ATC app 3004, ATC1500 3004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3005 (Two-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3005.
Also known as: ATC1500, LC-ATC1500-0, Application #3005, ATC app 3005, ATC1500 3005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3006 (Two-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3006.
Also known as: ATC1500, LC-ATC1500-0, Application #3006, ATC app 3006, ATC1500 3006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3007 (Two-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #3007.
Also known as: ATC1500, LC-ATC1500-0, Application #3007, ATC app 3007, ATC1500 3007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #3008 (Two-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A two-pipe fan coil with one changeover heating/cooling valve (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #3008.
Also known as: ATC1500, LC-ATC1500-0, Application #3008, ATC app 3008, ATC1500 3008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4001 (Four-Pipe, On/Off Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4001.
Also known as: ATC1500, LC-ATC1500-0, Application #4001, ATC app 4001, ATC1500 4001, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4002 (Four-Pipe, On/Off Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4002.
Also known as: ATC1500, LC-ATC1500-0, Application #4002, ATC app 4002, ATC1500 4002, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4003 (Four-Pipe, 0-10V Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4003.
Also known as: ATC1500, LC-ATC1500-0, Application #4003, ATC app 4003, ATC1500 4003, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4004 (Four-Pipe, 0-10V Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4004.
Also known as: ATC1500, LC-ATC1500-0, Application #4004, ATC app 4004, ATC1500 4004, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4005 (Four-Pipe, Six-Way Valve, Staged Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4005.
Also known as: ATC1500, LC-ATC1500-0, Application #4005, ATC app 4005, ATC1500 4005, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4006 (Four-Pipe, Six-Way Valve, Staged Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a multi-speed (staged) fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4006.
Also known as: ATC1500, LC-ATC1500-0, Application #4006, ATC app 4006, ATC1500 4006, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4007 (Four-Pipe, On/Off Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4007.
Also known as: ATC1500, LC-ATC1500-0, Application #4007, ATC app 4007, ATC1500 4007, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4008 (Four-Pipe, On/Off Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (on/off), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4008.
Also known as: ATC1500, LC-ATC1500-0, Application #4008, ATC app 4008, ATC1500 4008, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4009 (Four-Pipe, 0-10V Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4009.
Also known as: ATC1500, LC-ATC1500-0, Application #4009, ATC app 4009, ATC1500 4009, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4010 (Four-Pipe, 0-10V Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with separate heating and cooling valves (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4010.
Also known as: ATC1500, LC-ATC1500-0, Application #4010, ATC app 4010, ATC1500 4010, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4011 (Four-Pipe, Six-Way Valve, Var-Speed Fan, Floating Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional floating fresh-air damper with position output, run by the Johnson Controls ATC1500 with application #4011.
Also known as: ATC1500, LC-ATC1500-0, Application #4011, ATC app 4011, ATC1500 4011, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Fan coil unit controller
Johnson Controls ATC1500 Fan Coil Controller - Application #4012 (Four-Pipe, Six-Way Valve, Var-Speed Fan, On/Off Damper)
A four-pipe fan coil with a six-way valve for heating and cooling (0-10 V proportional), a variable-speed fan, two-wire PWM heating and an optional on/off fresh-air damper, run by the Johnson Controls ATC1500 with application #4012.
Also known as: ATC1500, LC-ATC1500-0, Application #4012, ATC app 4012, ATC1500 4012, Advanced Terminal Unit Controller, ATC SMART Equipment Controller - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Load Device
Each configured load (virtual BACnet device) of the Johnson Controls EEM multi-circuit electric energy meter.
Also known as: EEM Multi-Circuit load, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (multi-circuit, BACnet MS/TP or BACnet IP)
Johnson Controls EEM Multi-Circuit Electric Energy Meter - Root Device
The root (panel) device of the Johnson Controls EEM multi-circuit electric energy meter in its 3, 12 and 48-load versions.
Also known as: EEM Multi-Circuit, EEM-MULTI-03, EEM-MULTI-12, EEM-MULTI-48, Electric Energy Meter Multi-Circuit, JCI EEM - Power and energy meter (3-phase, BACnet MS/TP)
Johnson Controls EM Series 3-Phase Energy Meter with EMCOMMS Module (BACnet MS/TP)
The Johnson Controls EM series three-phase energy meter: the EMCOMMS communication module with its CVT voltage/current sensors, one per phase.
Also known as: EMCOMMS, EM Series, EM 3 Phase Energy Meter, JCI EM meter, EMCOMMS BACnet - Evaporative condenser controller
Johnson Controls Frick XLP3b Evaporative Condenser Controller (BMS points)
Johnson Controls / Frick XLP3b evaporative condensers for industrial refrigeration with the factory PLC control panel (up to eight fans and a pump).
Also known as: XLP3b, Frick XLP3b, XLP3b evaporative condenser, 140.925-IOM - Laboratory VAV controller (fume hood)
Johnson Controls HMS-2000 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS-2000 touchscreen fume hood controller with face velocity, sash, pressure and airflow inputs.
Also known as: HMS-2000, HMS2000, LB-HMS2C, Hood Monitoring Station, JCI fume hood controller - Laboratory VAV controller (fume hood)
Johnson Controls HMS1655 Fume Hood Controller (BACnet MS/TP)
Fume hoods controlled and monitored by the Johnson Controls HMS1655 fume hood controller with face velocity, sash, pressure, airflow and temperature inputs.
Also known as: HMS1655, HMS-1655, Hood Monitoring Station, JCI fume hood controller - Water-to-water heat pump
Johnson Controls JMWL-Series 30-70 Ton Modular Water-to-Water Heat Pump
Johnson Controls JMWL-Series 30-70 ton modular water-to-water heat pump modules with the factory master controller.
Also known as: JMWL, JMWL-Series, JMWL360, JMWL600, JMWL840, JMW600, 14807-NOM1, 97B0090N02, JCI modular water-to-water heat pump - Water-source heat pump controller
Johnson Controls PEAK 18 SMART Equipment Controller - Water-Source Heat Pump (PK-OEM1820)
Water-source heat pumps with a factory PEAK OEM 18 (24 V) SMART Equipment controller linked over Modbus to one or two Aurora (ABC) unit boards.
Also known as: PEAK 18, PK-OEM1820-0, PK-OEM18x0-0, PEAK OEM 18, SMART Equipment controller, 147.00-EG1, Aurora ABC - Refrigerated display case controller
Johnson Controls PENN MR5 Series panel-mount refrigerated case controller (MR534, BACnet MS/TP)
PENN / Johnson Controls MR5 Series (MR534) panel-mount controllers for refrigerated display cases, with the ADPT-MR5-RS485 adapter for BACnet MS/TP or Verasys.
Also known as: MR5, MR534, MR534AFDV, MR534AFDN, PENN MR5, ADPT-MR5-RS485, LIT-12013019, JCI refrigeration case controller - Rooftop unit controller
Johnson Controls Premier Rooftop Units 25-50 Ton
Johnson Controls Premier 25-50 ton R-410A packaged rooftop units (MZVAV or SZVAV) with the Applied Smart Equipment controller.
Also known as: JCI Premier RTU, Premier 25-50 ton, Applied Smart Equipment controller, Smart Equipment rooftop, 5586996-JSG-A - Rooftop unit BACnet gateway
Johnson Controls Simplicity LINC Gateway (YORK / JCI Unitary Products rooftops)
Johnson Controls Unitary Products (YORK, Coleman, Luxaire) packaged rooftop units with Simplicity controls built after 4/2/2008, plus older Simplicity Elite and Simplicity with Intelli-Comfort controls, fitted with the Simplicity LINC gateway.
Also known as: Simplicity LINC, Simplicity-LINC, SimplicityLINC, YORK Simplicity LINC, 1031990-UAD-A-0313, YORK_RTU, Simplicity Elite, Intelli-Comfort, Sun-Line, Predator, YORK Simplicity BACnet - Fan coil unit controller (room thermostat)
Johnson Controls T8800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils with three-speed fans and on/off or modulating valves, using the T8800 touch screen thermostat (TF20, TB20, TB21).
Also known as: T8800, T8800-TF20, T8800-TB20, T8800-TB21 - Fan coil unit controller (room thermostat)
Johnson Controls T9800 Series Touch Screen Fan Coil Thermostat (BACnet MS/TP)
Two- and four-pipe fan coils (relay or 0-10 VDC valves, three-speed or ECM fans), fan coils with floor heating or TiO2/ESP, water source heat pumps, boilers and a basic AHU application, using the T9800 touch screen thermostat.
Also known as: T9800, T9800-TF20-9JS0, T9800-TF21-9JS0, T9800-TB21-9JS0, T9800-TF20-1JS0, T9800-TF21-1JS0, T9800-TB21-1JS0 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2601-4 and TEC2601-4+PIR Single-Stage Thermostat (BACnet MS/TP)
Single-stage heating and cooling equipment such as small rooftop units and split systems with 24 VAC G/Y1/W1 control, using the TEC2601-4 thermostat.
Also known as: TEC2601-4, TEC2601-4+PIR, TEC2601 - Rooftop unit controller (room thermostat for heat-pump units)
Johnson Controls TEC2602-4 and TEC2602-4+PIR Heat Pump Thermostat (BACnet MS/TP)
Single- or two-stage heat pumps with auxiliary heat and a reversing valve, using the TEC2602-4 thermostat.
Also known as: TEC2602-4, TEC2602-4+PIR, TEC2602 - Rooftop unit controller (room thermostat)
Johnson Controls TEC2603-4 and TEC2603-4+PIR Multi-Stage Thermostat (BACnet MS/TP)
Rooftop units and split systems with up to two heating and two cooling stages, using the TEC2603-4 thermostat.
Also known as: TEC2603-4, TEC2603-4+PIR, TEC2603 - Rooftop unit controller (room thermostat with economizer)
Johnson Controls TEC2604-4 and TEC2604-4+PIR Multi-Stage Economizer Thermostat (BACnet MS/TP)
Rooftop units with an economizer and up to two heating and two cooling stages, using the TEC2604-4 thermostat.
Also known as: TEC2604-4, TEC2604-4+PIR, TEC2604 - Rooftop unit controller (room thermostat with humidity control)
Johnson Controls TEC2613-4 and TEC2613-4+PIR Multi-Stage Temperature and Humidity Controller (BACnet MS/TP)
Multi-stage rooftop units and split systems that also dehumidify or drive a humidifier, using the TEC2613-4 controller.
Also known as: TEC2613-4, TEC2613-4+PIR, TEC2613 - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-2 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Johnson Controls TEC2645-2 BACnet MS/TP networked thermostats with one 0-10 VDC proportional output and one-speed fan control (the -2 generation; the newer TEC2645-4 is a separate entry with different instances).
Also known as: TEC2645-2, TEC2645, TEC2645-2 networked thermostat - Fan coil unit controller (room thermostat)
Johnson Controls TEC2645-4 Thermostat with Single Proportional Output and One-Speed Fan (BACnet MS/TP)
Fan coils, reheat valves and zoning equipment with one 0-10 VDC proportional output and a single-speed fan, using the TEC2645-4 thermostat.
Also known as: TEC2645-4, TEC2645 - VAV zone controller (room thermostat for TEC zoning)
Johnson Controls TEC2647Z-3 / TEC2647Z-3+PIR Zone Controller (TEC Zoning System, BACnet MS/TP)
Zone dampers in the Johnson Controls TEC zoning system, each run by a TEC2647Z-3 zone controller (optionally with PIR occupancy sensor) and served by a TEC2664Z-3 rooftop controller.
Also known as: TEC2647Z-3, TEC2647Z-3+PIR, TEC2647Z, TEC2647Z-2, TEC zoning zone controller - Rooftop unit controller (TEC zoning system)
Johnson Controls TEC2664Z-3 Rooftop Controller (TEC Zoning System, BACnet MS/TP)
Constant volume, pressure-dependent rooftop units with up to two heating and two cooling stages and a bypass damper, run by the TEC2664Z-3 rooftop controller of the Johnson Controls TEC zoning system.
Also known as: TEC2664Z-3, TEC2664Z, TEC2664Z-2, TEC zoning rooftop controller - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-2 Series Fan Coil Thermostat with Dehumidification and Three Fan Speeds (BACnet MS/TP)
Two- or four-pipe fan coils and cabinet unit heaters with three fan speeds, using the older TEC26x6(H)-2 thermostats.
Also known as: TEC2616-2, TEC2626-2, TEC2636-2, TEC2646-2, TEC2656-2, TEC2636H-2, TEC2656H-2, TEC26x6-2 - Fan coil unit controller (room thermostat)
Johnson Controls TEC26x6(H)-4 and TEC26x6H-4+PIR Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils with up to three fan speeds, controlled by the TEC26x6(H)-4 family (on/off, floating or proportional valve outputs, optional dehumidification and PIR occupancy sensing).
Also known as: TEC2616-4, TEC2626-4, TEC2636-4, TEC2646-4, TEC2656-4, TEC2616H-4, TEC2636H-4+PIR, TEC2656H-4+PIR, TEC26x6-4 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-2 Series Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the older TEC26x7-2 two-output thermostats.
Also known as: TEC2627-2, TEC2647-2, TEC26x7-2 - VAV zone controller (room thermostat)
Johnson Controls TEC26x7-4 and TEC26x7-4+PIR Thermostat with Two Outputs (BACnet MS/TP)
Hydronic reheat valves, pressure-dependent VAV boxes with or without reheat and other zoning equipment, using the two-output TEC26x7-4 thermostats (TEC2627 on/off or floating, TEC2647 proportional).
Also known as: TEC2627-4, TEC2647-4, TEC2627-4+PIR, TEC2647-4+PIR, TEC26x7-4 - VAV zone controller (room thermostat for VVT zoning)
Johnson Controls TEC26x7VVT-2 Series Thermostat with Two Outputs for VVT Systems (BACnet MS/TP)
Pressure-dependent VAV and VVT zone dampers with or without local reheat, using the TEC26x7VVT-2 thermostats with floating or 0-10 VDC outputs.
Also known as: TEC2627VVT-2, TEC2647VVT-2, TEC26x7VVT-2, TEC26x7VVT - Fan coil unit controller (room thermostat)
Johnson Controls TEC26xx-0+PIR Thermostat Controller (BACnet MS/TP)
Fan coils and zoning equipment controlled by the TEC26xx-0+PIR thermostats, which add remote input and heat/cool output configuration objects to the TEC26x6 object set.
Also known as: TEC26xx-0+PIR, TEC26xx-0 - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3610 / TEC3611 / TEC3612 / TEC3613 On/Off or Floating Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with on/off or floating outputs, using the networked TEC3610-TEC3613 thermostats.
Also known as: TEC3610, TEC3611, TEC3612, TEC3613, TEC361x, TEC3000 on/off floating, JCI TEC3000 fan coil - Fan coil unit controller (room thermostat)
Johnson Controls TEC3000 Series TEC3620 / TEC3621 / TEC3622 / TEC3623 Proportional Fan Coil Thermostat (BACnet MS/TP)
Two- or four-pipe fan coils, cabinet unit heaters, reheat valves and pressure-dependent VAV zones with 0-10 VDC proportional outputs, using the networked TEC3620-TEC3623 thermostats.
Also known as: TEC3620, TEC3621, TEC3622, TEC3623, TEC362x, TEC3000 proportional, JCI TEC3000 0-10V fan coil - Rooftop unit controller (room thermostat, conventional or heat-pump RTUs)
Johnson Controls TEC3000 Series TEC3630 / TEC3631 Single- or Two-Stage RTU / Heat Pump Thermostat with Economizer (BACnet MS/TP)
Single- or two-stage unitary rooftop units and heat-pump RTUs, with or without an economizer, using the networked TEC3630 and TEC3631 thermostats.
Also known as: TEC3630, TEC3631, TEC363x, TEC3000 economizer, JCI TEC3000 rooftop thermostat - Room pressure controller (critical environment)
Johnson Controls Triatek FMS-2000C Critical Environment Controller (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000C critical environment controllers for isolation rooms, labs and cleanrooms (successor of the FMS-1655).
Also known as: FMS-2000C, FMS2000C, FMS-2000, Triatek FMS-2000C, LIT-12013504, JCI critical environment controller - Room pressure monitor (critical environment)
Johnson Controls Triatek FMS-2000M Critical Environment Monitor (BACnet MS/TP)
Triatek / Johnson Controls FMS-2000M critical environment monitors with one to four differential pressure sensors (models FMS2M-Bx1x to Bx4x).
Also known as: FMS-2000M, FMS2000M, Triatek FMS-2000M, FMS2M, FMS2M-Bx1x, FMS2M-Bx2x, FMS2M-Bx3x, FMS2M-Bx4x, LIT-12013580 - Variable frequency drive (HVAC)
Johnson Controls Variable Speed Drive Series III (on-board BACnet MS/TP and BACnet IP)
Johnson Controls Variable Speed Drive Series III (VS3) HVAC drives using the on-board RS-485 port (BACnet MS/TP) or the RJ45 Ethernet port (BACnet IP).
Also known as: VSD Series III, Variable Speed Drive Series 3, JCI VSD3, VS3 drive, LIT-12013000 - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-1 (Cooling only)
A single-duct cooling-only VAV box controlled by the Johnson Controls VAV1717 with preloaded application 1717-1.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-1, VAV1717 Cooling only - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-10 (Elec Reheat 1 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-10.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-10, VAV1717 Elec Reheat 1 Stg On/Off Series Fan - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-2 (Elec Reheat 1-2 Stg)
A single-duct VAV box with one or two stages of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-2.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-2, VAV1717 Elec Reheat 1-2 Stg - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-3 (On/Off HW Reheat)
A single-duct VAV box with an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-3.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-3, VAV1717 On/Off HW Reheat - VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-4 (Incr HW Reheat)
A single-duct VAV box with an incremental (floating) hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-4.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-4, VAV1717 Incr HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-5 (On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-5.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-5, VAV1717 On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-6 (On/Off HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-6.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-6, VAV1717 On/Off HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-7 (Elec Reheat 1 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one stage of electric reheat controlled by the Johnson Controls VAV1717 with preloaded application 1717-7.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-7, VAV1717 Elec Reheat 1 Stg On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-8 (On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan controlled by the Johnson Controls VAV1717 with preloaded application 1717-8.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-8, VAV1717 On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1717 VAV Controller - Application 1717-9 (On/Off HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1717 with preloaded application 1717-9.
Also known as: VAV1717, JC-VAV1717-0, Application 1717-9, VAV1717 On/Off HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-1 (Elec Reheat 1-3 Stg On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-1.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-1, VAV1732 Elec Reheat 1-3 Stg On/Off Parallel Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-10 (Proportional HW Reheat)
A single-duct VAV box with a proportional (0-10 VDC) hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-10.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-10, VAV1732 Proportional HW Reheat - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-2 (Incr HW Reheat On/Off Parallel Fan)
A parallel fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-2.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-2, VAV1732 Incr HW Reheat On/Off Parallel Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-3 (Elec Reheat 1-3 Stg On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-3.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-3, VAV1732 Elec Reheat 1-3 Stg On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-4 (Incr HW Reheat On/Off Series Fan)
A series fan-powered VAV box with a single-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-4.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-4, VAV1732 Incr HW Reheat On/Off Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-5 (Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan controlled by the Johnson Controls VAV1732 with preloaded application 1732-5.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-5, VAV1732 Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-6 (Elec Reheat 1-3 Stg Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-6.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-6, VAV1732 Elec Reheat 1-3 Stg Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-7 (On/Off HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an on/off hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-7.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-7, VAV1732 On/Off HW Reheat Var Speed Series Fan - Fan-powered VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-8 (Incr HW Reheat Var Speed Series Fan)
A series fan-powered VAV box with a variable-speed fan and an incremental hot water reheat valve controlled by the Johnson Controls VAV1732 with preloaded application 1732-8.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-8, VAV1732 Incr HW Reheat Var Speed Series Fan - VAV terminal unit controller
Johnson Controls VAV1732 VAV Controller - Application 1732-9 (Elec Reheat 1-3 Stg)
A single-duct VAV box with one to three stages of electric reheat controlled by the Johnson Controls VAV1732 with preloaded application 1732-9.
Also known as: VAV1732, JC-VAV1732-0, Application 1732-9, VAV1732 Elec Reheat 1-3 Stg - Bypass damper controller (Verasys zoning)
Johnson Controls Verasys BYP200 Bypass Controller
Verasys BYP200 bypass damper controllers that hold duct static pressure in a zoning system.
Also known as: BYP200, Verasys bypass controller - General purpose I/O controller (Verasys)
Johnson Controls Verasys generic IO controller
Verasys generic IO controllers with digital and analog inputs, outputs, NetSensors and energy meters on the system bus.
Also known as: Verasys generic IO, Verasys IO controller, Verasys GIO - Rooftop unit controller (Smart Equipment)
Johnson Controls Verasys SSE system bus (Smart Equipment rooftop board)
Rooftop units with the Simplicity SE / Smart Equipment (SSE) control board connected to a Verasys system bus.
Also known as: SSE, Simplicity SE, Verasys SSE - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC1000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC1000 Constant Volume Controller.
Also known as: VAC1000, Verasys VAC1000, Verasys constant volume controller - Lighting controller (Verasys)
Johnson Controls Verasys VAC1001 Lighting Controller
Verasys VAC1001 lighting controllers with up to 9 lighting circuits grouped into zones.
Also known as: VAC1001, Verasys lighting controller - Rooftop / constant volume unit controller (Verasys)
Johnson Controls Verasys VAC3000 Constant Volume Controller
Constant volume rooftop and air handling units controlled by a Verasys VAC3000 Constant Volume Controller.
Also known as: VAC3000, Verasys VAC3000, Verasys constant volume controller, Verasys CV controller - VAV / zone damper controller (Verasys)
Johnson Controls Verasys Zone Equipment Controller (ZEC)
Verasys Zone Equipment Controllers serving zone dampers and VAV boxes in a Verasys zoning system.
Also known as: ZEC, Verasys ZEC, Zone Equipment Controller - Rooftop unit controller (Verasys zoning)
Johnson Controls Verasys Zoning RTU (rooftop unit on the Verasys system bus)
Rooftop units integrated as the air source of a Verasys zoning system.
Also known as: Verasys Zoning RTU, Verasys RTU, Verasys zoning rooftop - Variable frequency drive (HVAC)
Johnson Controls VSD Series II HVAC drive (BACnet MS/TP and BACnet IP)
Johnson Controls VSD Series II HVAC drives using the built-in RS-485 port (BACnet MS/TP) or the Ethernet port (BACnet IP).
Also known as: VSD Series II, Variable Speed Drive Series II, JCI VSD2, VSD Series 2, LIT-12011771 - Zoning system coordinator
Johnson Controls VZC100 Verasys Zone Coordinator
Verasys VZC100 zone coordinators that run a zoned rooftop system (zone voting, duct pressure and discharge air resets).
Also known as: VZC100, Verasys Zone Coordinator
Source: FMS-1655 Room Pressure Controller Programming Manual · LIT-12013120 Rev. A · rev. 2018-08. Object names, instances and units are reproduced as published; descriptions are our own.