Short answer

The VZC100 coordinates a Verasys zoning system: it collects heating and cooling requests from the zones and resets the rooftop unit's discharge air and duct static pressure. Through the SBH it exposes 30 objects: changeover and reset settings, setpoints, enable and mode commands, request counts and the zoning system state.

This page lists 30 BACnet objects for the Johnson Controls VZC100 Verasys Zone Coordinator — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Johnson Controls’s own free documentation, linked below.

Manufacturer
Johnson Controls
Model
VZC100 Verasys Zone Coordinator
Equipment
Zoning system coordinator
Equipment type
Other equipment
BACnet objects
30 (23 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
VZC100, Verasys Zone Coordinator
Source document
Verasys BACnet over IP Integration User Guide · LIT-12013287 · rev. 2024-03-11
Download CSV 30 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Johnson Controls’s current documentation and the live device before use. Not official Johnson Controls information. Terms of use.

BMS integration notes: Johnson Controls VZC100 Verasys Zone Coordinator

Integration in brief

Integrate through the Verasys Smart Building Hub: enable BACnet routing on the SBH, and the supervisor then sees each system bus device behind the SBH's MS/TP network. Map the enable and occupancy commands, the main setpoints and the status and alarm points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 23475UNIT_ENUnit enableWrite
MV 23476CONTROL-MODEControl modeWrite
AV 23474DAT-SPDischarge air temperature setpointWrite
AV 23468DUCT-P-SPDuct static pressure setpointWrite
AV 23470CLGOCC-SPOccupied cooling setpointWrite
AV 23471HTGOCC-SPOccupied heating setpointWrite
AV 23488TOT-CLG-REQTotal cooling requests from zonesRead
AV 23487TOT-HEAT-REQTotal heating requests from zonesRead
MV 23492ZN-SYS-STATEZoning system stateRead

Network setup

Watch out for

Johnson Controls VZC100 Verasys Zone Coordinator BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

30 of 30 shown
Type
AnalogMulti-state
Access
Show
Johnson Controls VZC100 Verasys Zone Coordinator BACnet Points List
DescriptionStates
AV23464MINREQ-CHANGEWrite
AV23465MIN-URGREQ-CHANGEWrite
AV23466CHNGVR-MINTIMEWrite
AV23467MAX-DAT-SP-ADWrite
AVmin23468DUCT-P-SPWrite
AV23469REP-ZONEWrite
AVmin23470CLGOCC-SPWrite
AVmin23471HTGOCC-SPWrite
AV23472MAX-DUCT-SP-ADWrite
AV23473ECON-MIN-POSWrite
AVmin23474DAT-SPWrite
MVmin23475UNIT_ENWrite
MVmin23476CONTROL-MODEWrite
MV23477BAL-MODEWrite
MV23478CHNGVR-STATERead
MV23479DAT-RESETWrite
MV23480DUCT-SP-RESETWrite
MV23481TITLE24-TESTWrite
MV23482CONST-MODEWrite
MV23483UNOCC-HC-ENWrite
MV23484TEMP-OCCWrite
AV23485VFD-ECON-MINPOSWrite
AV23486URG-HEAT-REQRead
AVmin23487TOT-HEAT-REQRead
AVmin23488TOT-CLG-REQRead
AV23489URG-CLG-REQRead
MV23490SD-CMDWrite
MVmin23492ZN-SYS-STATERead
MV23493LS-CMDWrite
MV23494LS-SRead
Object ID lookup: Johnson Controls Verasys VZC100 Zone Coordinator point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VZC100 Verasys Zone Coordinator and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Johnson Controls VZC100 Verasys Zone Coordinator

How many BACnet points does the Johnson Controls VZC100 Verasys Zone Coordinator have?

This list has 30 BACnet objects: 16 analog values, 14 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Johnson Controls VZC100 Verasys Zone Coordinator BACnet points are writable?

23 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Johnson Controls VZC100 Verasys Zone Coordinator BACnet documentation?

The source is Verasys BACnet over IP Integration User Guide (LIT-12013287), revision 2024-03-11, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/maps/bQUUXbLn_sJI5F5XzKax0Q/attachments/ETDjFYqCzPvla4mPr0wdlw-bQUUXbLn_sJI5F5XzKax0Q/content.

What are the minimum BACnet points to integrate the Johnson Controls VZC100 Verasys Zone Coordinator?

Start with MV 23475 UNIT_EN (Unit enable); MV 23476 CONTROL-MODE (Control mode); AV 23474 DAT-SP (Discharge air temperature setpoint); AV 23468 DUCT-P-SP (Duct static pressure setpoint); AV 23470 CLGOCC-SP (Occupied cooling setpoint); AV 23471 HTGOCC-SP (Occupied heating setpoint); AV 23488 TOT-CLG-REQ (Total cooling requests from zones); AV 23487 TOT-HEAT-REQ (Total heating requests from zones); MV 23492 ZN-SYS-STATE (Zoning system state).

How do I check these points on the real VZC100 Verasys Zone Coordinator?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Johnson Controls BACnet points lists

Source: Verasys BACnet over IP Integration User Guide · LIT-12013287 · rev. 2024-03-11. Object names, instances and units are reproduced as published; descriptions are our own.