 "equipment_type": "Room pressure controller (isolation room)",
 "applies_to": "Triatek / Johnson Controls FMS-1655 room pressure controllers for isolation rooms, labs and cleanrooms, with optional anteroom and flow inputs.",
 "summary": "The FMS-1655 holds and monitors room differential pressure by driving a damper, with four configurable analog inputs, two thermistor inputs, four analog outputs, four digital inputs and four relays. It talks BACnet MS/TP or Metasys N2. The BACnet table has 90 objects: I/O, setpoints, alarm and warning limits, network-written values, airflow and volumetric offset, output overrides, deadbands, isolation mode commands and alarm status.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": "85000 + MAC address",
 "access_inferred": false,
 "notes": [
  "Object names are the manual's functional descriptions. Multistate objects are printed as MSO (multistate output) and shown here as MO.",
  "MSO 1 is printed \"Primary solation Mode\" (sic).",
  "AV 17/18 and BO 4 are marked 'Not user-selectable'.",
  "Units are not printed in the BACnet table.",
  "The same manual also has a Metasys N2 object table (pages 64-65), not included here.",
  "Source: 'BACnet Objects' table, manual pages 62-63 (PDF pages 65-66), 90 objects."
 ],
 "source": {
  "title": "FMS-1655 Room Pressure Controller Programming Manual",
  "doc_number": "LIT-12013120 Rev. A",
  "revision_date": "2018-08",
  "url": "https://docs.johnsoncontrols.com/bas/api/khub/documents/JIDP3G795sTe0t6ZnGsF2g/content"
 },
 "integration": {
  "summary": "Map the room isolation mode command, the room pressure setpoint, the measured room pressure, the damper output and the primary alarm status. Write network variables (AV 43-46) only if the BAS supplies those values.",
  "minimum_points": [
   {
    "ref": "MO 1",
    "name": "Primary solation Mode",
    "why": "Isolation mode: 1 positive, 2 negative, 3 neutral"
   },
   {
    "ref": "AV 1",
    "name": "AI-1 Setpoint (Room Pressure)",
    "why": "Room pressure setpoint"
   },
   {
    "ref": "AI 1",
    "name": "Analog Input 1 (default: Isolation Pressure)",
    "why": "Room (isolation) pressure"
   },
   {
    "ref": "AO 1",
    "name": "Analog Output 1 (default: Damper Position)",
    "why": "Damper position output"
   },
   {
    "ref": "BI 1",
    "name": "Digital Input 1 (default: Door Switch)",
    "why": "Door switch"
   },
   {
    "ref": "MO 3",
    "name": "Primary Alarm Status",
    "why": "Primary alarm: 1 normal, 2 warning, 3 alarm"
   }
  ],
  "enable": "Primary Isolation Mode (MSO 1) is writable: 1 positive, 2 negative, 3 neutral.",
  "heartbeat": null,
  "remote_sensors": "AV 43-46 are writable network variables for humidity, temperature, air changes and differential pressure sent from the BAS.",
  "setup": [
   "BACnet MS/TP is the default protocol; Metasys N2 is the alternative.",
   "Device instance = Device ID Offset (default 85,000, set in steps of 1,000) + MAC address, e.g. MAC 123 gives 85,123.",
   "MS/TP master MAC range 1-127; Max_Master default 127; baud rate chosen from four standard rates on the Network Setup menu."
  ],
  "gotchas": [
   "Alarm limits, deadbands and setpoints are setup values; don't write them cyclically.",
   "What each analog input measures depends on how it is configured; names give the default use."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Analog Input 1 (default: Isolation Pressure)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Analog Input 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Analog Input 3",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Analog Input 4",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Thermistor Input 1",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Thermistor Input 2",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Analog Output 1 (default: Damper Position)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "Analog Output 2 (default: Anteroom Damper Control)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "Analog Output 3 (spare control output)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "Analog Output 4 (spare control output)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Digital Input 1 (default: Door Switch)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Digital Input 2 (default: Anteroom Door Switch)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Digital Input 3 (spare digital input)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Digital Input 4 (spare digital input)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Relay Output 1 (default: Primary Alarm Relay Output)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Relay Output 2 (default: Spare Relay Output)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "Relay Output 3 (spare relay output)",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "Not user-selectable",
   "description": "",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "AI-1 Setpoint (Room Pressure)",
   "description": "Control setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "AI-2 Setpoint",
   "description": "Control setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "AI-3 Setpoint",
   "description": "Control setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "AI-4 Setpoint",
   "description": "Control setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "TI-1 Setpoint",
   "description": "Control setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "TI-2 Setpoint",
   "description": "Control setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Air Change Rate based on Flow Input at AI-1",
   "description": "Air change rate from flow input",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Air Change Rate based on Flow Input at AI-2",
   "description": "Air change rate from flow input",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Air Change Rate based on Flow Input at AI-3",
   "description": "Air change rate from flow input",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Air Change Rate based on Flow Input at AI-4",
   "description": "Air change rate from flow input",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Alarm Relay 1 High Setpoint",
   "description": "Alarm relay trip limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Alarm Relay 1 Low Setpoint",
   "description": "Alarm relay trip limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Alarm Relay 2 High Setpoint",
   "description": "Alarm relay trip limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Alarm Relay 2 Low Setpoint",
   "description": "Alarm relay trip limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Alarm Relay 3 High Setpoint",
   "description": "Alarm relay trip limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Alarm Relay 3 Low Setpoint",
   "description": "Alarm relay trip limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Not user-selectable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Not user-selectable",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "AI-1 Low Alarm Setpoint (low pressure alarm)",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "AI-1 Low Warning Setpoint (low pressure warning)",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "AI-1 High Warning Setpoint (high pressure warning)",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "AI-1 High Alarm Setpoint (high pressure alarm)",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "AI-2 Low Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "AI-2 Low Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "AI-2 High Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "AI-2 High Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "AI-3 Low Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "AI-3 Low Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "AI-3 High Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "AI-3 High Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "AI-4 Low Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "AI-4 Low Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "AI-4 High Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "AI-4 High Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "TI-1 Low Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "TI-1 Low Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "TI-1 High Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "TI-1 High Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "TI-2 Low Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "TI-2 Low Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "TI-2 High Warning Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "TI-2 High Alarm Setpoint",
   "description": "Alarm / warning limit",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Writable Network Variable – Humidity",
   "description": "Value written by the BAS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Writable Network Variable – Temperature",
   "description": "Value written by the BAS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "Writable Network Variable – Air Changes",
   "description": "Value written by the BAS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "Writable Network Variable – Differential Pressure",
   "description": "Value written by the BAS",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "Device ID Offset (range: 0 – 4,194,000)",
   "description": "Device instance = offset + MAC",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "Duct Air Flow based on AI-1 flow input",
   "description": "Duct airflow from flow input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "Duct Air Flow based on AI-2 flow input",
   "description": "Duct airflow from flow input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Duct Air Flow based on AI-3 flow input (Supply Flow)",
   "description": "Duct airflow from flow input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "Duct Air Flow based on AI-4 flow input (Exhaust Flow)",
   "description": "Duct airflow from flow input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "Volumetric Offset (Supply Flow – Exhaust Flow)",
   "description": "Supply minus exhaust flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "Volumetric Offset Setpoint",
   "description": "Control setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "AO-1 Override Level",
   "description": "Output override level",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "AO-2 Override Level",
   "description": "Output override level",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "AO-3 Override Level",
   "description": "Output override level",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "AO-4 Override Level",
   "description": "Output override level",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "AI-1 Deadband Setting",
   "description": "Control deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "AI-2 Deadband Setting",
   "description": "Control deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "AI-3 Deadband Setting",
   "description": "Control deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "AI-4 Deadband Setting",
   "description": "Control deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "TI-1 Deadband Setting",
   "description": "Control deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "TI-2 Deadband Setting",
   "description": "Control deadband",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "Primary solation Mode",
   "description": "Room isolation mode",
   "units": "",
   "access": "W",
   "states": "1=positive, 2=negative, 3=neutral"
  },
  {
   "type": "MO",
   "instance": 2,
   "name": "Secondary Isolation Mode",
   "description": "Room isolation mode",
   "units": "",
   "access": "W",
   "states": "1=positive, 2=negative, 3=neutral"
  },
  {
   "type": "MO",
   "instance": 3,
   "name": "Primary Alarm Status",
   "description": "Alarm status",
   "units": "",
   "access": "R",
   "states": "1=normal, 2=warning, 3=alarm"
  },
  {
   "type": "MO",
   "instance": 4,
   "name": "Secondary Alarm Status",
   "description": "Alarm status",
   "units": "",
   "access": "R",
   "states": "1=normal, 2=warning, 3=alarm"
  },
  {
   "type": "MO",
   "instance": 5,
   "name": "AI-3 Alarm Status",
   "description": "Alarm status",
   "units": "",
   "access": "R",
   "states": "1=normal, 2=warning, 3=alarm"
  },
  {
   "type": "MO",
   "instance": 6,
   "name": "AI-4 Alarm Status",
   "description": "Alarm status",
   "units": "",
   "access": "R",
   "states": "1=normal, 2=warning, 3=alarm"
  },
  {
   "type": "MO",
   "instance": 7,
   "name": "TI-1 Alarm Status",
   "description": "Alarm status",
   "units": "",
   "access": "R",
   "states": "1=normal, 2=warning, 3=alarm"
  },
  {
   "type": "MO",
   "instance": 8,
   "name": "TI-2 Alarm Status",
   "description": "Alarm status",
   "units": "",
   "access": "R",
   "states": "1=normal, 2=warning, 3=alarm"
  },
  {
   "type": "MO",
   "instance": 9,
   "name": "Offset Control Status",
   "description": "Volumetric offset control status",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/johnson-controls/fms-1655-room-pressure-controller",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}