VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Toshiba SMMSu outdoor units over BACnet: unit HP, compressor speeds, fan mode, high and low pressure, discharge, heat exchanger, liquid, suction, outdoor and oil and IGBT temperatures, compressor currents, PMV positions and valve states, plus model and serial number, check (text and number), pre-check and notice codes, release and defrost flags, run timers, switch settings and the 7-segment display text (83 objects). Monitoring only.

This page lists 83 BACnet objects for the CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
83 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Toshiba SMMSu BACnet, Toshiba SMMS-u BACnet, CoolMasterNet Toshiba, SMMSu
Brands covered
Toshiba
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 83 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Toshiba outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend pressures, compressor speed and check codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 277Comp1Compressor 1 speed, HzRead
AI 299TOOutdoor air temperature, °CRead
AI 280Pd[psi]High pressure, psiRead
AI 281Ps[psi]Low pressure, psiRead
AI 284TD1Discharge temperature 1, °CRead
CSV 268ChkCdCheck (error) code textRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

83 of 83 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
CSV257MdlModel NameRead
CSV258SNSerial No.Read
PIV259HPOutdoor Unit HPRead
PIV260StPriStarting PriorityRead
PIV261DfrstGrDefrost GrRead
BI262OilLvCk1Oil Level Check1Read
BI263OilLvCk2Oil Level Check2Read
BI264CFoStop1Comp Forced Stop1Read
BI265CFoStop2Comp Forced Stop2Read
BI266CompBUp1Comp BackUp1Read
BI267CompBUp2Comp BackUp2Read
CSVmin268ChkCdCheck codeRead
PIV269ChkCdChkCdRead
CSV270PreChkCdPre-Check codeRead
PIV271PreChkCdPreChkCdRead
PIV272NtcCd1Notice Code1Read
PIV273NtcCd2Notice Code2Read
PIV274NtcCd3Notice Code3Read
PIV275NtcCd4Notice Code4Read
PIV276NtcCd5Notice Code5Read
AImin277Comp1Comp(1) HzHzRead
AI278Comp2Comp(2) HzHzRead
PIV279FanModeOutdoor Unit FanModeRead
AImin280Pd[psi]Pd:High PressurepsiRead
AImin281Ps[psi]Ps:Low PressurepsiRead
AI282TGTG:High Pressure Temp°CRead
AI283TUTU Low Pressure Temp°CRead
AImin284TD1TD1 Discharge Temp°CRead
AI285TD2TD2 Discharge Temp°CRead
AI286TK1TK1:Oil Temp1°CRead
AI287TK2TK2:Oil Temp2°CRead
AI288TS1TS1:Suction Temp°CRead
AI289TS3TS3:Suction Temp°CRead
AI290TE1TE1:Heat Exchanger Temp°CRead
AI291TE2TE2:Heat Exchanger Temp°CRead
AI292TE3TE3°CRead
AI293TG1TG1:Gas.Temp°CRead
AI294TG2TG2:Gas.Temp°CRead
AI295TG3TG3°CRead
AI296TL1TL1:Liquid Pipe Temp°CRead
AI297TL2TL2:Liquid Pipe Temp°CRead
AI298TL3TL3:Liquid Pipe Temp°CRead
AImin299TOTO Outdoor Air Temp°CRead
AI300TH1TH1:Comp1 IGBT Temp°CRead
AI301TH2TH2:Comp2 IGBT Temp°CRead
AI302THF1THF1:Fan Motor1 IGBT Temp°CRead
AI303THF2THF2:Fan Motor1 IGBT Temp°CRead
AI304I1I1ARead
AI305I2I2ARead
PIV306PwrOnTmPower ON TimehrRead
PIV307PMV1Pulse Motor Valve1plsRead
PIV308PMV2Pulse Motor Valve2plsRead
PIV309PMV3Pulse Motor Valve3plsRead
PIV310PMV4Pulse Motor Valve4plsRead
BI3114wayVlv4way ValveRead
BI312SV41SV41:Comp Start AssistRead
BI313SV42SV42:Comp Start AssistRead
BI314SV3DSV3D:Separator OpenRead
BI315SV3FSV3FRead
BI316SV5BSV5BRead
BI317Co1HeatComp1 HeaterRead
BI318Co2HeatComp2 HeaterRead
BI319AccHeatAccumulator HeaterRead
BI320HiPrsRelHigh Pressure ReleaseRead
BI321DschTRelDischarge Temp ReleaseRead
BI322DfrstPrepHtDefrost preparation (Heating)Read
BI323DfrstCtrlClDuring Defrost control (Cooling)Read
BI324DfrstFinClDefrost finish action (Cooling)Read
BI325OilEqCtOil Equalizing ControlRead
AI326Inv1CurCtrlControl current INV1ARead
PIV327OnStrtHHOn Time From Start [hh]hrRead
PIV328OnStrtMMOn Time From Start [mm]minRead
PIV329StopKeepUnit Stop keep timerRead
PIV330RSW1RSW1Read
PIV331RSW2RSW2Read
PIV332RSW3RSW3Read
PIV333SW101SW101Read
PIV334SW102SW102Read
PIV335SW103SW103Read
PIV336SW104SW104Read
PIV337SW105SW105Read
CSV3387Seg7 segment displayRead
Object ID lookup: CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects have?

This list has 83 BACnet objects: 29 analog inputs, 21 binary inputs, 6 characterstring values, 27 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects?

Start with AI 277 Comp1 (Compressor 1 speed, Hz); AI 299 TO (Outdoor air temperature, °C); AI 280 Pd[psi] (High pressure, psi); AI 281 Ps[psi] (Low pressure, psi); AI 284 TD1 (Discharge temperature 1, °C); CSV 268 ChkCd (Check (error) code text).

How do I enable BMS control of the CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.