Short answer

With PRO functionality, CoolAutomation gateways publish service data from Mitsubishi Electric City Multi PURY-M YNW-A/A1 outdoor units over BACnet: type, control and operation mode, compressor and fan frequencies, total cooling and heating capacity, LEV positions, compressor currents and bus voltage, 63HS/63LS pressures, thermistor, condensing and evaporating temperatures, operation status and OC/OS attribute, plus current, maintenance and preliminary error codes with detail and source address (65 objects). Monitoring only.

This page lists 65 BACnet objects for the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
65 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PURY-M YNW-A, PURY-M YNW-A1
Brands covered
Mitsubishi Electric
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 65 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Mitsubishi Electric equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operation mode, compressor frequency, pressures and error codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 258OpeMOperation mode codeRead
PIV 285OpeSOperation status codeRead
BI 309CompOnCompressor onRead
PIV 260F1Compressor 1 frequency, HzRead
AI 27663HS1High pressure, kg/cm2Read
AI 27763LSLow pressure, kg/cm2Read
AI 289TcCondensing temperature, °CRead
AI 290TeEvaporating temperature, °CRead
PIV 311ErrError codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

65 of 65 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIV257CtrlMControl ModeRead
PIVmin258OpeMOperation ModeRead
IV259F(Hz)All temporary frequenciesHzRead
PIVmin260F1Temporary frequency of No.1 COMPHzRead
PIV261FocTemporary frequencyHzRead
PIV262FANFan outputHzRead
IV263QjCTotal capacity CoolRead
IV264QjHTotal capacity HeatRead
PIV265LEV2LEV2 Linear expansion valveplsRead
PIV266LEV2bLEV2bplsRead
PIV267LEV2dLEV2dRead
PIV268LEV4Linear expansion valveplsRead
AI269IuU-Phase current effective valueARead
AI270IwW-Phase current effective valueARead
PIV271ALALRead
AI272LXLXRead
PIV273FAN(rpm)FAN(rpm)rpmRead
IV274VdcBus voltageVRead
PIV275LEV9LEV9plsRead
AImin27663HS163HS1 Pressure sensorkg/cm2Read
AImin27763LS63LS Pressure sensorkg/cm2Read
AI278TH3Thermistor 3°CRead
AI279TH4Thermistor 4°CRead
AI280TH5Thermistor 5°CRead
AI281TH7Thermistor 7°CRead
AI282TH15Thermistor 15°CRead
AI283FAN-VerFan1 SW versionRead
PIV284SaveCapacity save signal%Read
PIVmin285OpeSOperation StatusRead
PIV286AttrAttribute (OC/OS identification)Read
PIV287M-NetSupUnM-NET supply unitRead
PIV288StrtUpUnStart-up unitRead
AImin289TcCondensing temperature°CRead
AImin290TeEvaporating temperature°CRead
AI291THHSThermistor 9°CRead
BI292DmndDemandRead
BI293SV1aSV1(A)/SV1aRead
BI294Dmnd2Demand2Read
BI295SnowSnowRead
BI296NgtNightRead
BI297Ngt2Night2Read
BI29821S4a21S4aRead
BI29921S4b21S4bRead
BI300SV2SV2Read
IV301AKHeat exchanger capacityRead
AI302THHS(FAN1)THHS(FAN1)°CRead
AI303RotTmRotation timerRead
BI304IHIHRead
PIV305FAN-FrFan1 run statusRead
BI306WMWMRead
BI307RepRepeater outputRead
BI30872C72CRead
BImin309CompOnComp ONRead
BI310M-NetSupM-NET supplyRead
PIVmin311ErrError codeRead
PIV312ErrDetError detail codeRead
PIV313ErrSrcError source addressRead
PIV314MntErrMaintenance error codeRead
PIV315MntErrDetMaintenance error detail codeRead
PIV316MntErrSrcMaintenance error source addressRead
PIV317PrelErrPreliminary error codeRead
PIV318PrelErrDetPreliminary error detail codeRead
PIV319PrelErrSrcPreliminary error source addressRead
PIV320DtaCollData collectionRead
Object ID lookup: CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects have?

This list has 65 BACnet objects: 16 analog inputs, 15 binary inputs, 1 characterstring value, 5 integer values, 28 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects?

Start with PIV 258 OpeM (Operation mode code); PIV 285 OpeS (Operation status code); BI 309 CompOn (Compressor on); PIV 260 F1 (Compressor 1 frequency, Hz); AI 276 63HS1 (High pressure, kg/cm2); AI 277 63LS (Low pressure, kg/cm2); AI 289 Tc (Condensing temperature, °C); AI 290 Te (Evaporating temperature, °C); PIV 311 Err (Error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.