VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects BACnet points list

Updated 11 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Gree GMV5 outdoor units over BACnet: rated capacity, master/slave status, outdoor temperature, compressor and fan frequencies, module high and low pressure, discharge, shell, defrost, subcooler and separator temperatures, EXV positions, compressor and valve states, and compressor and fan currents, bus voltages and IPM temperatures (42 objects). Monitoring only.

This page lists 42 BACnet objects for the CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Gree GMV5 outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
42 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Gree GMV5 BACnet, CoolMasterNet Gree, Gree outdoor unit BACnet, GMV5
Brands covered
Gree
Source document
BACnet Integration Guidelines - CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 0.5, 2019-04-29
Download CSV 42 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Gree outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend the key temperatures, pressures and compressor data (the guide lists no error object for Gree outdoor units).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 282Comp1StatCompressor 1 runningRead
PIV 265Comp1OpFreqCompressor 1 frequency, HzRead
IV 264OutTOutdoor temperature, °CRead
IV 269MdlHpModule high pressure valueRead
IV 270MdlLpModule low pressure valueRead
IV 271Comp1DisTCompressor 1 discharge temperature, °CRead
AI 286Comp1CurCompressor 1 current, ARead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

42 of 42 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor System Type NameRead
AI257RatedCapRated Capacity (value x 0.1)kWRead
PIV258MsSlStatMaster-Slave StatusRead
PIV259GenVerGeneral Protocol VersionRead
PIV260UnitVerUnit Protocol VersionRead
PIV261PwrTpPower TypeRead
PIV262FanTpFan TypeRead
PIV263FanEmergFan EmergencyRead
IVmin264OutTOutdoor Temp°CRead
PIVmin265Comp1OpFreqComp1 Operation FrequencyHzRead
PIV266Comp2OpFreqComp2 Operation FrequencyHzRead
PIV267Fan1OpFreqFan1 Operation FrequencyHzRead
PIV268Fan2OpFreqFan2 Operation FrequencyHzRead
IVmin269MdlHpModule HP°CRead
IVmin270MdlLpModule LP°CRead
IVmin271Comp1DisTComp1 Discharge Temp°CRead
IV272Comp1ShTComp1 Shell Temp°CRead
IV273Comp2DisTComp2 Discharge Temp°CRead
IV274Comp2ShTComp2 Shell Temp°CRead
IV275DfrsT1Defrosting Temp1°CRead
IV276SubClLiqTSubcooler Liq Temp°CRead
IV277SubClGsTSubcooler Gas Temp°CRead
IV278SepInTSeparator Inlet Temp°CRead
IV279SepOutTSeparator Outlet Temp°CRead
PIV280HtEXVHeating EXVpulsesRead
PIV281FanStcPrsHigh Static PressureRead
BImin282Comp1StatComp1 StatusRead
BI283Comp2StatComp2 StatusRead
BI2844wayVlv14-way Valve1Read
BI285LpMrsVlvLP Measure ValveRead
AImin286Comp1CurComp1 CurrentARead
PIV287Comp1BsbVComp1 Basbar VoltageVRead
IV288Comp1IpmTComp1 IPM Temp°CRead
AI289Fan1CurFan1 CurrentARead
PIV290Fan1BsbVFan1 Basbar VoltageVRead
IV291Fan1IpmTFan1 IPM Temp°CRead
AI292Comp2CurComp2 CurrentARead
PIV293Comp2BsbVComp2 Basbar VoltageVRead
IV294Comp2IpmTComp2 IPM Temp°CRead
AI295Fan2CurFan2 CurrentARead
PIV296Fan2BsbVFan2 Basbar VoltageVRead
IV297Fan2IpmTFan2 IPM Temp°CRead
Object ID lookup: CoolAutomation Gree GMV5 ODU point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Gree GMV5 outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects have?

This list has 42 BACnet objects: 5 analog inputs, 4 binary inputs, 1 characterstring value, 16 integer values, 16 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 0.5, 2019-04-29, published free by CoolAutomation at https://coolautomation.com/Lib/doc/CoolMasterNet/manual/CoolMasterNet-BACnet-guidelines.pdf.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects?

Start with BI 282 Comp1Stat (Compressor 1 running); PIV 265 Comp1OpFreq (Compressor 1 frequency, Hz); IV 264 OutT (Outdoor temperature, °C); IV 269 MdlHp (Module high pressure value); IV 270 MdlLp (Module low pressure value); IV 271 Comp1DisT (Compressor 1 discharge temperature, °C); AI 286 Comp1Cur (Compressor 1 current, A).

How do I enable BMS control of the CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Gree GMV5 outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 0.5, 2019-04-29. Object names, instances and units are reproduced as published; descriptions are our own.