VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from LG Multi V III HR master outdoor units over BACnet: type, operation mode, error code, target and current high and low pressure, compression ratio, superheat and subcooling, compressor and fan speeds, EEV positions, refrigerant and outdoor temperatures, inverter currents, voltages and IPM temperatures, and valve and compressor states, plus constant-speed compressor and oil supply temperatures (69 objects). Monitoring only.

This page lists 69 BACnet objects for the CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
69 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
LG Multi V III heat recovery BACnet, CoolMasterNet LG, MultiV III HR Master, LGMV
Brands covered
LG
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 69 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor LG outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the master outdoor unit's VA and trend pressures, compressor speed and error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
CSV 257ModeOperation mode textRead
PIV 271InvTrcFrqInverter compressor frequency, HzRead
AI 280AirTOutdoor air temperature, °CRead
PIV 263HiPrsTrcHigh pressure, kPaRead
PIV 264LoPrsTrcLow pressure, kPaRead
AI 284InvDisTInverter compressor discharge temp, °CRead
PIV 258ErrError codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

69 of 69 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
CSVmin257ModeOperation ModeRead
PIVmin258ErrError CodeRead
AI259AvgTAverage indoor temperature°CRead
PIV260HiPrsTrgTarget high pressurekPaRead
PIV261LoPrsTrgTarget low pressurekPaRead
AI262SCSHTrgTarget degree of subcooling and super heat°CRead
PIVmin263HiPrsTrcCurrent high pressurekPaRead
PIVmin264LoPrsTrcCurrent low pressurekPaRead
AI265ComprRatioCompression ratioRead
AI266SHTrgTarget degree of super heat°CRead
AI267SHTrcCurrent degree of super heat°CRead
AI268SCTrcCurrent degree of subcooling°CRead
AI269SCSCTrcCurrent degree of subcooling and super heat°CRead
PIV270InvTrgFrqInverter target frequencyHzRead
PIVmin271InvTrcFrqInverter current frequencyHzRead
PIV272Fan1TrgFAN1 target RPMrpmRead
PIV273Fan1TrcFAN1 current RPMrpmRead
PIV274Fan2TrgFAN2 target RPMrpmRead
PIV275Fan2TrcFAN2 current RPMrpmRead
PIV276MainEEVMain EEVplsRead
PIV277SubEEVSub EEVplsRead
PIV278ScEEVSubcooling EEVplsRead
PIV279EqEEVOil supply EEVplsRead
AImin280AirTOutdoor air temperature°CRead
AI281SuctTCompressor suction temperature°CRead
AI282BubTCondenser temperature°CRead
AI283DewTEvaporator temperature°CRead
AImin284InvDisTInverter discharge temperature°CRead
AI285Comp1DisTConstant compressor1 discharge temperature°CRead
AI286Comp2DisTConstant compressor2 discharge temperature°CRead
AI287HexTHeat exchanger pipe temperature°CRead
AI288UpHexTTop/Upper heat exchanger pipe temperature°CRead
AI289LoHexTBottom/Down/Lower heat exchanger pipe temperature°CRead
AI290ScInTSubcooling inlet temperature°CRead
AI291ScOutTSubcooling outlet temperature°CRead
AI292LiqTLiquid pipe temperature°CRead
AI293InvOilTInverter oil supply temperature°CRead
AI294Comp1OilTCompressor1 oil supply temperature°CRead
AI295Comp2OilTCompressor2 oil supply temperature°CRead
AI296InvCTInverter current valueARead
AI297Comp1CTCompressor1 current valueARead
AI298Comp2CTCompressor2 current valueARead
PIV299InvVInverter voltageVRead
PIV300InvPwrFrqInverter power frequencyHzRead
AI301InvPhsCTInverter phase currentARead
AI302Fan1PhsCTFan1 phase currentARead
AI303Fan2PhsCTFan2 phase currentARead
PIV304InvDcLnkInverter DC LINK voltageVRead
AI305InvIpmTInverter IPM temperature°CRead
AI306FanHtSnkTOutdoor fan heat sink temperature°CRead
PIV307Fan1VFan1 voltageVRead
PIV308Fan2VFan2 voltageVRead
BI309AccumOil return valveRead
BI3104wayUp4 WAY up valveRead
BI3114wayDn4 WAY down valveRead
BI312Comp1Compressor1Read
BI313Comp2Compressor2Read
BI314HotGasHot gasRead
BI315InvHtVlvInverter heater valveRead
BI316Comp1HtVlvCompressor1 heater valveRead
BI317Comp2HtVlvCompressor2 heater valveRead
BI318HexUpVlvHeat exchanger top valveRead
BI319HexDnVlvHeat exchanger bottom valveRead
BI320InvIjtInverter injection valveRead
BI321Comp1IjtCompressor1 injection valveRead
BI322Comp2IjtCompressor2 injection valveRead
BI323ScIjtSC injection valveRead
PIV324EEPVerEEP versionRead
Object ID lookup: CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects have?

This list has 69 BACnet objects: 31 analog inputs, 15 binary inputs, 2 characterstring values, 21 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects?

Start with CSV 257 Mode (Operation mode text); PIV 271 InvTrcFrq (Inverter compressor frequency, Hz); AI 280 AirT (Outdoor air temperature, °C); PIV 263 HiPrsTrc (High pressure, kPa); PIV 264 LoPrsTrc (Low pressure, kPa); AI 284 InvDisT (Inverter compressor discharge temp, °C); PIV 258 Err (Error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.