VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Mitsubishi Electric City Multi PURY-P ZKMU-A outdoor units over BACnet: type, control and operation mode, compressor and fan frequencies, total cooling and heating capacity, LEV positions, compressor currents and bus voltage, 63HS/63LS pressures, thermistor, condensing and evaporating temperatures, operation status and OC/OS attribute, plus dual fan data and solenoid valve states (67 objects). Monitoring only.

This page lists 67 BACnet objects for the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
67 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PURY-P ZKMU-A
Brands covered
Mitsubishi Electric
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 67 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Mitsubishi Electric equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operation mode, compressor frequency and pressures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 258OpeMOperation mode codeRead
PIV 289OpeSOperation status codeRead
BI 314CompOnCompressor onRead
PIV 260F1Compressor 1 frequency, HzRead
AI 27563HS1High pressure, kg/cm2Read
AI 27663LSLow pressure, kg/cm2Read
AI 293TcCondensing temperature, °CRead
AI 294TeEvaporating temperature, °CRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

67 of 67 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIV257CtrlMControl ModeRead
PIVmin258OpeMOperation ModeRead
IV259F(Hz)All temporary frequenciesHzRead
PIVmin260F1Temporary frequency of No.1 COMPHzRead
PIV261FocTemporary frequencyHzRead
PIV262FANFan outputHzRead
IV263QjCTotal capacity CoolRead
IV264QjHTotal capacity HeatRead
PIV265LEV5aLEV5aplsRead
PIV266LEV5bLEV5bplsRead
AI267IdcDirect currentARead
AI268IuU-Phase current effective valueARead
AI269IwW-Phase current effective valueARead
PIV270ALALRead
PIV271FAN(rpm)FAN(rpm)rpmRead
PIV272FAN2(rpm)FAN2(rpm)rpmRead
PIV273FAN2FAN2Read
IV274VdcBus voltageVRead
AImin27563HS163HS1 Pressure sensorkg/cm2Read
AImin27663LS63LS Pressure sensorkg/cm2Read
AI277TH3Thermistor 3°CRead
AI278TH4Thermistor 4°CRead
AI279TH5Thermistor 5°CRead
AI280TH6Inlet pipe temperature of the heat exchanger°CRead
AI281TH7Thermistor 7°CRead
AI282TH15Thermistor 15°CRead
AI283TH16Thermistor 16°CRead
AI284TH17TH17Read
AI285TH18Thermistor 18°CRead
AI286FAN-VerFan1 SW versionRead
AI287FAN2-VerFan2 SW versionRead
PIV288SaveCapacity save signal%Read
PIVmin289OpeSOperation StatusRead
PIV290AttrAttribute (OC/OS identification)Read
PIV291M-NetSupUnM-NET supply unitRead
PIV292StrtUpUnStart-up unitRead
AImin293TcCondensing temperature°CRead
AImin294TeEvaporating temperature°CRead
AI295THHSThermistor 9°CRead
AI296LXLXRead
IV297AKHeat exchanger capacityRead
AI298RotTmRotation timerRead
BI299DmndDemandRead
BI30052C52CRead
BI301SV1aSV1(A)/SV1aRead
BI302Dmnd2Demand2Read
BI303SnowSnowRead
BI304NgtNightRead
BI305Ngt2Night2Read
BI30621S4a21S4aRead
BI30721S4b21S4bRead
BI308SV5bSV5bRead
BI309IHIHRead
PIV310FAN-FrFan1 run statusRead
PIV311FAN2-FrFan2 run statusRead
BI312WMWMRead
BI313RepRepeater outputRead
BImin314CompOnComp ONRead
BI315M-NetSupM-NET supplyRead
BI316SV9SV9Read
BI317SV4aSV4aRead
BI318SV4bSV4bRead
BI319SV4cSV4cRead
BI320SV4dSV4dRead
BI321CH21CH21Read
PIV322ALhALhRead
Object ID lookup: CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects have?

This list has 67 BACnet objects: 21 analog inputs, 21 binary inputs, 1 characterstring value, 5 integer values, 19 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects?

Start with PIV 258 OpeM (Operation mode code); PIV 289 OpeS (Operation status code); BI 314 CompOn (Compressor on); PIV 260 F1 (Compressor 1 frequency, Hz); AI 275 63HS1 (High pressure, kg/cm2); AI 276 63LS (Low pressure, kg/cm2); AI 293 Tc (Condensing temperature, °C); AI 294 Te (Evaporating temperature, °C).

How do I enable BMS control of the CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.