  4. CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects

VRF branch controller monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Mitsubishi Electric CMB-WP V-GA1 and CMB-WM V-AA controllers over BACnet: refrigerant, bypass and water outlet temperatures of the heating-main and cooling-main heat exchangers, branch thermistors TH31a-TH31p, high and low pressure, superheat and subcooling, power failure, float switch, debris removal and air vent states, pump speeds, control signals to and from the outdoor unit, total capacities, liquid level controls and 3-way valve positions VB3a-VB3p (70 objects). Monitoring only.

This page lists 70 BACnet objects for the CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects
Equipment
VRF branch controller monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
70 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Mitsubishi Hybrid City Multi BACnet, CoolMasterNet Mitsubishi Electric, CMB-WP V-GA1, CMB-WM V-AA
Brands covered
Mitsubishi Electric
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 70 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects

Integration in brief

Use these objects to monitor Mitsubishi Electric branch controller equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend water outlet temperatures, pressures and the power-failure and float switch states.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 273TH32Heating-main HX water outlet temperatureRead
AI 274TH33Cooling-main HX water outlet temperatureRead
AI 277PS1High pressure, liquid sideRead
AI 278PS3Low pressureRead
IV 305QjCTotal cooling capacityRead
IV 306QjHTotal heating capacityRead
BI 291PSPower failure detectedRead
BI 292FloatFloat switchRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

70 of 70 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
AI257TH11Liquid-side refrigerant temp. of Heating-main heat exchangerRead
AI258TH12Liquid-side refrigerant temp. of Cooling-main heat exchangerRead
AI259TH13TH13Read
AI260TH14TH13Read
AI261TH15Bypass inlet temperatureRead
AI262TH16Bypass outlet temperatureRead
AI263TH31aTH31aRead
AI264TH31bTH31bRead
AI265TH31cTH31cRead
AI266TH31dTH31dRead
AI267TH31eTH31eRead
AI268TH31fTH31fRead
AI269TH31gTH31gRead
AI270TH31hTH31hRead
AI271TH31iTH31iRead
AI272TH31jTH31jRead
AImin273TH32Outlet water temp. of Heating-main heat exchangerRead
AImin274TH33Outlet water temp. of Cooling-main heat exchangerRead
AI275TH34TH34Read
AI276TH35TH35Read
AImin277PS1Detects the high pressure at the liquid side.Read
AImin278PS3Detects the low pressure.Read
AI279TH31kTH31kRead
AI280TH31lTH31lRead
AI281TH31mTH31mRead
AI282TH31nTH31nRead
AI283TH31oTH31oRead
AI284TH31pTH31pRead
AI285SH1Superheat at bypass exit area. TH13-TH11 (only HB)Read
AI286SH2BC SH2°CRead
AI287SC1BC SC1°CRead
AI288SC2Subcool at liquid entrance area. PT1-TH12 (only HB)Read
AI289PT1Average of saturation gas temperatureRead
AI290dPHMBC dPHMkg/cm2Read
BImin291PSPower failure detectionRead
BImin292FloatFloat SWRead
BI293FlConFloat SWRead
BI294DebrisDebris removal operationRead
BI295AirVentAir vent operationRead
BI296SVM1Solenoid valveRead
BI29721S4Ma21S4MaRead
BI29821S4Mb21S4MbRead
PIV299PumpI1number of rotationsRead
PIV300PumpI2number of rotationsRead
PIV301PumpO1variable for controlRead
PIV302PumpO2variable for controlRead
PIV303HBSigOutdoor unit operation control signal to OCRead
PIV304OCSigIndoor unit operation control signal from OCRead
IVmin305QjCTotal capacity CoolRead
IVmin306QjHTotal capacity HeatRead
PIV307L1BC L1 Liquid level controlRead
PIV308L2BC L2 Liquid level controlRead
PIV309L3BC L3 Liquid level controlRead
IV310VB3a3-way valve VB3aRead
IV311VB3b3-way valve VB3bRead
IV312VB3c3-way valve VB3cRead
IV313VB3d3-way valve VB3dRead
IV314VB3e3-way valve VB3eRead
IV315VB3f3-way valve VB3fRead
IV316VB3g3-way valve VB3gRead
IV317VB3h3-way valve VB3hRead
IV318VB3i3-way valve VB3iRead
IV319VB3j3-way valve VB3jRead
IV320VB3k3-way valve VB3kRead
IV321VB3l3-way valve VB3lRead
IV322VB3m3-way valve VB3mRead
IV323VB3n3-way valve VB3nRead
IV324VB3o3-way valve VB3oRead
IV325VB3p3-way valve VB3pRead
Object ID lookup: CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects have?

This list has 70 BACnet objects: 34 analog inputs, 8 binary inputs, 1 characterstring value, 18 integer values, 9 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects?

Start with AI 273 TH32 (Heating-main HX water outlet temperature); AI 274 TH33 (Cooling-main HX water outlet temperature); AI 277 PS1 (High pressure, liquid side); AI 278 PS3 (Low pressure); IV 305 QjC (Total cooling capacity); IV 306 QjH (Total heating capacity); BI 291 PS (Power failure detected); BI 292 Float (Float switch).

How do I enable BMS control of the CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.