VRF outdoor system monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish system-level service data for Daikin VRV-K (RSEYP8-10KJ) outdoor systems over BACnet: type, AirNet address, error code, ambient, heat exchanger, discharge, suction, oil, evaporating and condensing temperatures, inverter frequency, current and temperature, EV openings, operating states, compressor, valve and fan states and retry and drooping-control flags (49 objects). Monitoring only.

This page lists 49 BACnet objects for the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ)
Equipment
VRF outdoor system monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
49 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-K, RSEYP8-10KJ
Brands covered
Daikin
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 49 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ)

Integration in brief

Use these objects to monitor Daikin outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operating states, temperatures, compressor data and the error state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 274CoolCoolingRead
BI 275HeatHeatingRead
BI 278TstatOnThermostat onRead
BI 280DfrstDefrost activeRead
PIV 269InvFrqInverter frequency, HzRead
IV 259AmbTAmbient temperature, °CRead
AI 267EvTEvaporating temperature, °CRead
AI 268CndTCondensing temperature, °CRead
CSV 258ErrCodeSystem error codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

49 of 49 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) BACnet Points List
DescriptionStates
CSV256TypeOutdoor System Type NameRead
PIV257AirNetAirNet Addr.Read
CSVmin258ErrCodeError codeRead
IVmin259AmbTAmbient temperature°CRead
IV260HexT1Heat exchanger temp. 1°CRead
IV261HexT2Heat exchanger temp. 2°CRead
PIV262DschTInvDisch. temp.(INV)°CRead
PIV263DschTStdDisch. temp.(STD)°CRead
IV264SuctPipT1Suction pipe temp. 1°CRead
IV265SuctPipT2Suction pipe temp. 2°CRead
IV266OiTOil temp.°CRead
AImin267EvTEvaporating Temperature°CRead
AImin268CndTCondensing Temperature°CRead
PIVmin269InvFrqInverter frequencyHzRead
PIV270InvCurInverter currentARead
PIV271InvTInverter temp.°CRead
PIV272EVOp1EV opening 1plsRead
PIV273EVOp2EV opening 2plsRead
BImin274CoolCoolingRead
BImin275HeatHeatingRead
BI276VentVentilationRead
BI277CoolHeatPrllCool/Heat parallel ope.Read
BImin278TstatOnThermostat ONRead
BI279ResrtStbyRestart stand-byRead
BImin280DfrstDefrostRead
BI281SoftStrtSoft startRead
BI282OiRtrnOil returnRead
BI283OiEqOpOil equalizing ope.Read
BI284Comp1InvCompressor1(INV)Read
BI285Comp2StdCompressor2(STD)Read
BI286BypEqBypass for equalizerRead
BI287HotGasBypHot gas bypassRead
BI288Injct1Injection 1Read
BI289Injct2Injection 2Read
BI290DschGasDisch. gasRead
BI291LiqPLiquid pres.Read
BI2924WayVlv14 way valve 1Read
BI2934WayVlv24-way valve 2Read
BI294HiPRtryHigh pressure retryRead
BI295LoPRtryLow pressure retryRead
BI296DschPipRtryDisch. pipe retryRead
BI297InvStbyINV stand-byRead
BI298HiPDroCtlHigh pres. drooping cntl.Read
BI299LoPDroCtlLow pres. drooping cntl.Read
BI300DschDroCtlDisch. pipe drooping cntl.Read
BI301InvCurDroCtlINV current drooping cntl.Read
BI302Fan1HFAN-1HRead
BI303Fan1LFAN-1LRead
BI304Fan2FAN-2Read
Object ID lookup: CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ)

How many BACnet points does the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) have?

This list has 49 BACnet objects: 2 analog inputs, 31 binary inputs, 2 characterstring values, 6 integer values, 8 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ) BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ)?

Start with BI 274 Cool (Cooling); BI 275 Heat (Heating); BI 278 TstatOn (Thermostat on); BI 280 Dfrst (Defrost active); PIV 269 InvFrq (Inverter frequency, Hz); IV 259 AmbT (Ambient temperature, °C); AI 267 EvT (Evaporating temperature, °C); AI 268 CndT (Condensing temperature, °C); CSV 258 ErrCode (System error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ)?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.