VRF outdoor system monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish system-level service data for Daikin VRV PLUS (RSEYP16-30KJY1) outdoor systems over BACnet: type, AirNet address, error code, ambient, discharge, suction, evaporating, condensing, coil, header and liquid temperatures, inverter frequency, current and temperature, EV openings, operating states, three compressors, valve and fan states, heating-overload and low-ambient flags and HP (70 objects). Monitoring only.

This page lists 70 BACnet objects for the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1)
Equipment
VRF outdoor system monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
70 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV_PLUS, VRV Plus, RSEYP16-30KJY1
Brands covered
Daikin
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 70 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1)

Integration in brief

Use these objects to monitor Daikin outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operating states, temperatures, compressor data and the error state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 271CoolCoolingRead
BI 272HeatHeatingRead
BI 275TstatOnThermostat onRead
BI 277DfrstDefrost activeRead
PIV 266InvFrqInverter frequency, HzRead
IV 259AmbTAmbient temperature, °CRead
IV 264EvTEvaporating temperature, °CRead
IV 265CndTCondensing temperature, °CRead
CSV 258ErrCodeSystem error codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

70 of 70 shown
Type
Binary
Show
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) BACnet Points List
DescriptionStates
CSV256TypeOutdoor System Type NameRead
PIV257AirNetAirNet Addr.Read
CSVmin258ErrCodeError codeRead
IVmin259AmbTAmbient temperature°CRead
PIV260DschTInvDisch. temp.(INV)°CRead
PIV261DschTStd1Disch. temp.(STD1)°CRead
PIV262DschTStd2Disch. temp.(STD2)°CRead
IV263SuctTSuction Temperature°CRead
IVmin264EvTEvaporating Temperature°CRead
IVmin265CndTCondensing Temperature°CRead
PIVmin266InvFrqInverter frequencyHzRead
PIV267InvCurInverter currentARead
PIV268InvTInverter temp.°CRead
PIV269EVOp1EV opening 1plsRead
PIV270EVOp2EV opening 2plsRead
BImin271CoolCoolingRead
BImin272HeatHeatingRead
BI273VentVentilationRead
BI274CoolHeatPrllCool/Heat parallel ope.Read
BImin275TstatOnThermostat ONRead
BI276ResrtStbyRestart stand-byRead
BImin277DfrstDefrostRead
BI278SoftStrtSoft startRead
BI279OiRtrnOil returnRead
BI280OiEqOpOil equalizing ope.Read
BI281CcHCrankcase HeaterRead
BI282AuxCondAux CondensersRead
BI283RcvrReceiversRead
BI284Comp1InvCompressor1(INV)Read
BI285Comp2Std1Compressor2(STD1)Read
BI286Comp3Std2Compressor3(STD2)Read
BI287HotGasBypHot gas bypassRead
BI288InjctInvInjection(INV)Read
BI289InjctStd1Injection(STD1)Read
BI290InjctStd2Injection(STD2)Read
BI291LiqPLiquid pres.Read
BI2924WayVlv14 way valve 1Read
BI2934WayVlv24-way valve 2Read
BI2944WayVlv34-way valve 3Read
BI295HiPRtryHigh pressure retryRead
BI296LoPRtryLow pressure retryRead
BI297DschPipRtryDisch. pipe retryRead
BI298InvStbyINV stand-byRead
BI299HiPDroCtlHigh pres. drooping cntl.Read
BI300LoPDroCtlLow pres. drooping cntl.Read
BI301DschDroCtlDisch. pipe drooping cntl.Read
BI302InvCurDroCtlINV current drooping cntl.Read
BI303Fan11LFAN-11LRead
BI304Fan11HFAN-11HRead
BI305Fan12FAN-12Read
BI306Fan21FAN-21Read
BI307Fan22FAN-22Read
BI308Fan3FAN-3Read
BI309Fan4FAN-4Read
BI310HtOvld1Heating overload 1Read
BI311HtOvld2Heating overload 2Read
BI312HtOvld3Heating overload 3Read
BI313HtOvld4Heating overload 4Read
BI314ClLwAmbT1Cooling low ambient temp 1Read
BI315ClLwAmbT2Cooling low ambient temp 2Read
BI316ClLwAmbT3Cooling low ambient temp 3Read
BI317ClLwAmbT4Cooling low ambient temp 4Read
IV318Cil1TCoil 1 temp°CRead
IV319Cil2TCoil 2 temp°CRead
IV320Cil3TCoil 3 temp°CRead
IV321Hdr1THeader 1 temp°CRead
IV322Hdr2THeader 2 temp°CRead
IV323Hdr3THeader 3 temp°CRead
IV324LiqTLiquid temp°CRead
PIV325HPHPhpRead
Object ID lookup: CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1)

How many BACnet points does the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) have?

This list has 70 BACnet objects: 47 binary inputs, 2 characterstring values, 11 integer values, 10 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1) BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1)?

Start with BI 271 Cool (Cooling); BI 272 Heat (Heating); BI 275 TstatOn (Thermostat on); BI 277 Dfrst (Defrost active); PIV 266 InvFrq (Inverter frequency, Hz); IV 259 AmbT (Ambient temperature, °C); IV 264 EvT (Evaporating temperature, °C); IV 265 CndT (Condensing temperature, °C); CSV 258 ErrCode (System error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1)?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.