VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Toshiba SMMS-Mini outdoor units over BACnet: unit HP, compressor speed, fan mode, high and low pressure, discharge, heat exchanger, liquid, suction, outdoor, oil and heat sink temperatures, check codes, compressor current, MCU version, PMV positions and valve states (28 objects). Monitoring only.

This page lists 28 BACnet objects for the CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
28 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Toshiba SMMS Mini BACnet, Toshiba Mini-SMMS BACnet, CoolMasterNet Toshiba, SMMS-Mini
Brands covered
Toshiba
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 28 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Toshiba outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend pressures, compressor speed and check codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 258Comp(1)Compressor speed, HzRead
AI 269TOOutdoor air temperature, °CRead
AI 261Pd[psi]High pressure, psiRead
AI 262Ps[psi]Low pressure, psiRead
AI 263TD1Discharge temperature, °CRead
PIV 270CheckCd1Check (error) code 1Read

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

28 of 28 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIV257HPOutdoor Unit HPRead
AImin258Comp(1)Comp(1) HzHzRead
IV259FanModeOutdoor Unit FanModeRead
BI2604wayVlv4way ValveRead
AImin261Pd[psi]Pd:High PressurepsiRead
AImin262Ps[psi]Ps:Low PressurepsiRead
AImin263TD1TD1 Discharge Temp°CRead
AI264TETE:Heat Exchanger Temp°CRead
AI265TLTL:Liquid Pipe Temp°CRead
AI266TGTG:High Pressure Temp°CRead
AI267TSTS Suction Temp°CRead
AI268TUTU Low Pressure Temp°CRead
AImin269TOTO Outdoor Air Temp°CRead
PIVmin270CheckCd1Check Code1Read
PIV271CheckCd2Check Code2Read
AI272MCUverMCU VersionRead
AI273I1I1ARead
IV274PMV1Pulse Motor Valve1plsRead
BI275SV2SV2:Hot Gas BypassRead
BI276SV3ASV3A:Oil Supply ON/OFFRead
BI277SV5SV5 ON/OFFRead
BI278SV4SV4 Comp Start AssistRead
AI279THTH Heat Sink Temperature°CRead
AI280TL3TL3:Liquid Pipe Temp°CRead
AI281TS3TS3:Suction Temp°CRead
AI282TK1TK1:Oil Temp1°CRead
IV283PMV4Pulse Motor Valve4plsRead
Object ID lookup: CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects have?

This list has 28 BACnet objects: 16 analog inputs, 5 binary inputs, 1 characterstring value, 3 integer values, 3 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects?

Start with AI 258 Comp(1) (Compressor speed, Hz); AI 269 TO (Outdoor air temperature, °C); AI 261 Pd[psi] (High pressure, psi); AI 262 Ps[psi] (Low pressure, psi); AI 263 TD1 (Discharge temperature, °C); PIV 270 CheckCd1 (Check (error) code 1).

How do I enable BMS control of the CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists