Short answer

With PRO functionality, CoolAutomation gateways publish service data from Gree VRF6 HR outdoor units over BACnet: rated capacity, protocol versions, outdoor temperature, compressor and fan frequencies, module high and low pressure, discharge, defrost, subcooler and separator temperatures, EXV positions, compressor and valve states and drive currents, voltages and module temperatures, including R410A module pressures in psi (59 objects). Monitoring only.

This page lists 59 BACnet objects for the CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
59 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Gree VRF6 HR BACnet, Gree VRF6 heat recovery BACnet, CoolMasterNet Gree, VRF6 HR
Brands covered
Gree
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 59 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Gree outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend compressor, pressure and temperature data.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 283Comp1Compressor 1 runningRead
PIV 265Comp1OpFreqCompressor 1 frequency, HzRead
IV 264AmbTOutdoor temperature, °CRead
IV 269MdlHiPrsModule high pressure valueRead
IV 270MdlLoPrsModule low pressure valueRead
IV 271Comp1DisTCompressor 1 discharge temperature, °CRead
AI 299Comp1CurCompressor 1 current, ARead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

59 of 59 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
AI257RatedCapRated capacitykWRead
PIV258MsSlMaster-Slave statusRead
PIV259GenVerGeneral protocol versionRead
PIV260UnitVerUnit protocol versionRead
PIV261PwrTpPower typeRead
PIV262FanTpFan typeRead
PIV263FanEmergFan emergency statusRead
IVmin264AmbTOutdoor ambient temperature°CRead
PIVmin265Comp1OpFreqCompressor 1 operation frequencyHzRead
PIV266Comp2OpFreqCompressor 2 operation frequencyHzRead
PIV267Fan1OpFreqFan1 operation frequencyHzRead
PIV268Fan2OpFreqFan2 operation frequencyHzRead
IVmin269MdlHiPrsModule high pressure°CRead
IVmin270MdlLoPrsModule low pressure°CRead
IVmin271Comp1DisTCompressor 1 discharge temperature°CRead
IV272Comp1TpCvrTCompressor 1 top cover temperature°CRead
IV273Comp2DisTCompressor 2 discharge temperature°CRead
IV274Comp2TpCvrTCompressor 2 top cover temperature°CRead
IV275DfrsT1Defrosting temperature 1°CRead
IV276DfrsT2Defrosting temperature 2°CRead
IV277SbclLiqOutTSubcooler liquid outlet temperature°CRead
IV278SbclGsOutTSubcooler gas outlet temperature°CRead
IV279GsSepInTubTGas separator inlet tube temperature°CRead
IV280GsSepOutTubTGas separator outlet tube temperature°CRead
PIV281HtEXVODU heating EXVPlsRead
PIV282FanStcPrsMdOutdoor fan static pressure modeRead
BImin283Comp1Compressor 1 statusRead
BI284Comp2Compressor 2 statusRead
BI2854WayVlv14-way valve1 statusRead
BI2864WayVlv24-way valve2 statusRead
BI287OiRtVlv1Oil return valve 1Read
BI288OiRtVlv2Oil return valve 2Read
BI289HiPrsSolVlvHigh pressure solenoid valveRead
BI290LoPrsSolVlvLow pressure solenoid valveRead
BI291LPBpsSolVlvODU low pressure by-pass solenoid valveRead
BI292LiqInVlvLiquid inlet valveRead
BI293GsBlncVlvGas balance valveRead
BI294PrsVlvPressure valveRead
BI295HiPrsBpsVlvHP-bypass valve statusRead
BI296AuxOiRtVlv1Auxiliary oil return valve 1Read
BI297SbclSolVlvSubcooler solenoid valveRead
BI298HtGsBpsVlvHot-gas by-pass valveRead
AImin299Comp1CurCompressor 1 currentARead
PIV300Comp1BsbVCompressor 1 busbar voltageVRead
IV301Comp1MdlTCompressor 1 module temperature°CRead
AI302Fan1CurFan1 currentARead
PIV303Fan1BsbVFan1 busbar voltageVRead
IV304Fan1MdlTFan1 module temperature°CRead
AI305Comp2CurCompressor 2 currentARead
PIV306Comp2BsbVCompressor 2 busbar voltageVRead
IV307Comp2MdlTCompressor 2 module temperature°CRead
AI308Fan2CurFan2 currentARead
PIV309Fan2BsbVFan2 busbar voltageVRead
IV310Fan2MdlTFan2 module temperature°CRead
PIV311SbclEXVSubcooler EXVPlsRead
IV312SbclGsInTSubcooler gas inlet temperature°CRead
PIV313MdlHiPrsR410AModule high pressure (R410A)psiRead
PIV314MdlLoPrsR410AModule low pressure (R410A)psiRead
Object ID lookup: CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects have?

This list has 59 BACnet objects: 5 analog inputs, 16 binary inputs, 1 characterstring value, 18 integer values, 19 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects?

Start with BI 283 Comp1 (Compressor 1 running); PIV 265 Comp1OpFreq (Compressor 1 frequency, Hz); IV 264 AmbT (Outdoor temperature, °C); IV 269 MdlHiPrs (Module high pressure value); IV 270 MdlLoPrs (Module low pressure value); IV 271 Comp1DisT (Compressor 1 discharge temperature, °C); AI 299 Comp1Cur (Compressor 1 current, A).

How do I enable BMS control of the CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.