VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Midea V6 master outdoor units over BACnet: mode, preheat, oil return and defrost states, system demand, HP, fan steps, high pressure, temperatures, compressor frequencies and currents, discharge temperatures, EXV positions, valve states, error code and superheat (40 objects). Monitoring only.

This page lists 40 BACnet objects for the CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Midea V6 master outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
40 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Midea V6 VRF BACnet, CoolMasterNet Midea, V6 Master
Brands covered
Midea
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 40 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Midea outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the master outdoor unit's VA and trend pressure, compressor frequency and error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 257MdOperating mode codeRead
PIV 274INV1Compressor 1 speed, rpsRead
AI 270T4Outdoor ambient temperature, °CRead
AI 267HiPrsHigh pressure, MPaRead
PIV 278T7C1Discharge temperature 1, °CRead
CSV 293ErrError codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

40 of 40 shown
Type
Analog
Show
CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIVmin257MdModeRead
PIV258PreHtPreheatRead
PIV259OiRetOil ReturnRead
PIV260DfrstDefrostingRead
PIV261MdOpPriMode operation priorityRead
AI262T2BAvgT2B Average°CRead
PIV263SysDmndSystem DemandRead
PIV264HPHPhpRead
PIV265Fan1Fan1Read
PIV266Fan2Fan2Read
AImin267HiPrsHigh pressureMPaRead
AI268T6AT6A°CRead
AI269T6BT6B°CRead
AImin270T4T4 (outdoor ambient temperature)°CRead
AI271T3T3 (condenser temperature)°CRead
PIV272Tf1Tf1°CRead
PIV273Tf2Tf2°CRead
PIVmin274INV1INV1 (compressor 1 frequency)rpsRead
PIV275INV2INV2 (compressor 2 frequency)rpsRead
PIV276CUR1CUR1 (current 1)ARead
PIV277CUR2CUR2 (current 2)ARead
PIVmin278T7C1T7C1 (discharge 1)°CRead
PIV279T7C2T7C2 (discharge 2)°CRead
PIV280EXVAEXVA (electronic expansion valve A)Read
PIV281EXVBEXVB (electronic expansion valve B)Read
PIV282EXVCEXVC (electronic expansion valve C)Read
PIV283CRANK1CRANK1Read
PIV284CRANK2CRANK2Read
PIV285SV4SV4Read
PIV286SV5SV5Read
PIV287SV6SV6Read
PIV288SV7SV7Read
PIV289SV8ASV8ARead
PIV290SV8BSV8BRead
PIV291SV9SV9Read
PIV292ST1ST1Read
CSVmin293ErrError CodeRead
PIV294DmndDemandRead
PIV295SprHtSuperheat°CRead
Object ID lookup: CoolAutomation CoolMasterNet Midea V6 master outdoor unit objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Midea V6 master outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects have?

This list has 40 BACnet objects: 6 analog inputs, 2 characterstring values, 32 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects?

Start with PIV 257 Md (Operating mode code); PIV 274 INV1 (Compressor 1 speed, rps); AI 270 T4 (Outdoor ambient temperature, °C); AI 267 HiPrs (High pressure, MPa); PIV 278 T7C1 (Discharge temperature 1, °C); CSV 293 Err (Error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Midea V6 master outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.