VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Samsung DVM S Eco 7/8/9 HP outdoor units over BACnet: type, operation mode and status, error code, capacity, compressor target, order and current frequencies, temperatures, compressor current, EEV positions and compressor and valve states, plus high and low pressure and EVI data (33 objects). Monitoring only.

This page lists 33 BACnet objects for the CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
33 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Samsung DVM S Eco BACnet, CoolMasterNet Samsung, DVM-S Eco 7/8/9HP
Brands covered
Samsung
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 33 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Samsung outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend pressures, compressor frequency and error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 257OpModeOperation mode codeRead
PIV 258OpStatOperation status codeRead
PIV 263CurFreq1Compressor 1 current frequency, HzRead
AI 271OutTOutdoor temperature, °CRead
AI 264HiPrsHigh pressure, kg/cm2Read
AI 266LoPrsLow pressure, kg/cm2Read
AI 268DisT1Compressor 1 discharge temperature, °CRead
PIV 259ErrCodeError codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

33 of 33 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIVmin257OpModeOperation ModeRead
PIVmin258OpStatOperation StatusRead
PIVmin259ErrCodeError CodeRead
PIV260CapCapacityhpRead
PIV261TrgFreq1Target Frequency1HzRead
PIV262OrdFreq1Order Frequency1HzRead
PIVmin263CurFreq1Current Frequency1HzRead
AImin264HiPrsHigh Pressurekg/cm2Read
IV265SatTPdSaturated T_Pd°CRead
AImin266LoPrsLow Pressurekg/cm2Read
IV267SatTPsSaturated T_Ps°CRead
AImin268DisT1Discharge1°CRead
PIV269TstOpTest Operation(UP)Read
AI270CompTop1Comp Top1°CRead
AImin271OutTOutdoor temperature°CRead
AI272CompCur1Compressor current1ARead
AI273IPM1TIPM1 temperature°CRead
AI274CondOutTCondOut temperature°CRead
AI275LiqTubTLiquid tube temperature°CRead
AI276Suct1TSuction1 temperature°CRead
PIV277MainEEVMain EEVRead
PIV278EviEEVEVI EEVRead
AI279EviInEVI IN°CRead
AI280EviOutEVI OUT°CRead
PIV281OutFnStOutdoor Fan StepRead
BI282Comp1Comp1Read
BI2834Way4Way valveRead
BI284HotGas1Hot Gas Bypass1Read
BI285EviSol1EVI Solenoid Valve1Read
BI286EviBpsEVI BypassRead
BI287CCH1Comp Coil Heater1Read
CSV288SNSerial NumberRead
Object ID lookup: CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects have?

This list has 33 BACnet objects: 12 analog inputs, 6 binary inputs, 2 characterstring values, 2 integer values, 11 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects?

Start with PIV 257 OpMode (Operation mode code); PIV 258 OpStat (Operation status code); PIV 263 CurFreq1 (Compressor 1 current frequency, Hz); AI 271 OutT (Outdoor temperature, °C); AI 264 HiPrs (High pressure, kg/cm2); AI 266 LoPrs (Low pressure, kg/cm2); AI 268 DisT1 (Compressor 1 discharge temperature, °C); PIV 259 ErrCode (Error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.