Short answer

With PRO functionality, CoolAutomation gateways publish service data from Samsung DVM S outdoor units over BACnet: operation mode and status, error code, capacity, power, compressor target/order/current frequencies, high, low and mid pressures, discharge and compressor-top temperatures, currents, EEV positions, fan step and compressor and valve states (49 objects). Monitoring only.

This page lists 49 BACnet objects for the CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Samsung DVM S outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
49 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Samsung DVM S BACnet, CoolMasterNet Samsung, Samsung outdoor unit BACnet, DVM-S
Brands covered
Samsung
Source document
BACnet Integration Guidelines - CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 0.5, 2019-04-29
Download CSV 49 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Samsung outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend the key temperatures, compressor data and error state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 258OpStatOperation statusRead
PIV 257OpModeOperation modeRead
AI 268HiPrsHigh pressure (value x 0.1 kg/cm2)Read
AI 270LoPrsLow pressure (value x 0.1 kg/cm2)Read
PIV 264CurFreq1Compressor 1 current frequency, HzRead
AI 278OutTOutdoor temperature (value x 0.1 °C)Read
AI 261CurPowPower (value x 0.001 kW)Read
PIV 259ErrCodeOutdoor unit error codeRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

49 of 49 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor System Type NameRead
PIVmin257OpModeOperation ModeRead
PIVmin258OpStatOperation StatusRead
PIVmin259ErrCodeError CodeRead
PIV260CapCapacityhpRead
AImin261CurPowControl Watt-meter (value x 0.001)kWRead
PIV262TrgFreq1Target Frequency1HzRead
PIV263OrdFreq1Order Frequency1HzRead
PIVmin264CurFreq1Current Frequency1HzRead
PIV265TrgFreq2Target Frequency2HzRead
PIV266OrdFreq2Order Frequency2HzRead
PIV267CurFreq2Current Frequency2HzRead
AImin268HiPrsHigh Pressure (value x 0.1)kg/cm2Read
IV269SatTPdSaturated T_Pd°CRead
AImin270LoPrsLow Pressure (value x 0.1)kg/cm2Read
IV271SatTPsSaturated T_Ps°CRead
AI272MidPrsMid Pressure (value x 0.1)kg/cm2Read
AI273DisT1Discharge1 (value x 0.1)°CRead
AI274DisT2Discharge2 (value x 0.1)°CRead
PIV275TstOpTest Operation(UP)Read
AI276CompTop1Comp Top1 (value x 0.1)°CRead
AI277CompTop2Comp Top2 (value x 0.1)°CRead
AImin278OutTOutdoor temperature (value x 0.1)°CRead
AI279CompCur1Compressor current1 (value x 0.1)ARead
AI280CompCur2Compressor current2 (value x 0.1)ARead
AI281IPM1TIPM1 temperature (value x 0.1)°CRead
AI282IPM2TIPM2 temperature (value x 0.1)°CRead
AI283CondOutTCondOut temperature (value x 0.1)°CRead
AI284LiqTubTLiquid tube temperature (value x 0.1)°CRead
AI285Suct1TSuction1 temperature (value x 0.1)°CRead
AI286Suct2TSuction2 temperature (value x 0.1)°CRead
PIV287MainEEVMain EEVRead
PIV288EviEEVEVI EEVRead
AI289EviInEVI IN (value x 0.1)°CRead
AI290EviOutEVI OUT (value x 0.1)°CRead
PIV291OutFnStOutdoor Fan StepRead
AI292PFCMPFCM Temperature (value x 0.1)°CRead
BI293Comp1Comp1Read
BI294Comp2Comp2Read
BI2954Way4Way valveRead
BI296HotGas1Hot Gas Bypass1Read
BI297HotGas2Hot Gas Bypass2Read
BI298MainCoolMain CoolingRead
BI299EEVVlvEEV ValveRead
BI300EviSol1EVI Solenoid Valve1Read
BI301EviSol2EVI Solenoid Valve2Read
BI302EviBpsEVI BypassRead
BI303CCH1Comp Coil Heater1Read
BI304CCH2Comp Coil Heater2Read
Object ID lookup: CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Samsung DVM S outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects have?

This list has 49 BACnet objects: 20 analog inputs, 12 binary inputs, 1 characterstring value, 2 integer values, 14 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 0.5, 2019-04-29, published free by CoolAutomation at https://coolautomation.com/Lib/doc/CoolMasterNet/manual/CoolMasterNet-BACnet-guidelines.pdf.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects?

Start with PIV 258 OpStat (Operation status); PIV 257 OpMode (Operation mode); AI 268 HiPrs (High pressure (value x 0.1 kg/cm2)); AI 270 LoPrs (Low pressure (value x 0.1 kg/cm2)); PIV 264 CurFreq1 (Compressor 1 current frequency, Hz); AI 278 OutT (Outdoor temperature (value x 0.1 °C)); AI 261 CurPow (Power (value x 0.001 kW)); PIV 259 ErrCode (Outdoor unit error code).

How do I enable BMS control of the CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Samsung DVM S outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 0.5, 2019-04-29. Object names, instances and units are reproduced as published; descriptions are our own.