  4. CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)

VRF water-cooled outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from each Daikin VRV-2-WATER (RWEYQ10-30MY1) water-cooled outdoor unit over BACnet: AirNet address, HP, suction, discharge, coil, subcooling, receiver, evaporating and condensing temperatures, EV openings, inverter frequency, fin temperature and current, compressor, heater, valve and pump states and retry and stepping-down flags (37 objects). Monitoring only.

This page lists 37 BACnet objects for the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)
Equipment
VRF water-cooled outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
37 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Daikin VRV W BACnet, CoolMasterNet Daikin, Daikin water cooled VRV BACnet, VRV-2-WATER, RWEYQ10-30MY1
Brands covered
Daikin
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 37 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)

Integration in brief

Use these objects to monitor Daikin outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operating states, temperatures, compressor data and the error state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 264Comp1InvInverter compressor runningRead
BI 288PumpPump output (Y2M)Read
PIV 284InvFrqInverter frequency, HzRead
IV 292EvTEvaporating temperature, °CRead
IV 291CndTCondensing temperature, °CRead
PIV 261DschTInvInverter discharge temperature, °CRead
PIV 263InvCurInverter current, ARead
BI 270ErrStateUnit error stateRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

37 of 37 shown
Type
Binary
Show
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) BACnet Points List
DescriptionStates
PIV256AirNetAirNet Addr.Read
PIV257HPHPhpRead
IV258SuctTSuction Temperature°CRead
PIV259EVOp1EV opening 1plsRead
PIV260EVOp2EV opening 2plsRead
PIVmin261DschTInvDisch. temp.(INV)°CRead
PIV262InvFinTInverter fin temp.°CRead
PIVmin263InvCurInverter currentARead
BImin264Comp1InvCompressor1(INV)Read
BI265OiRtrnOil returnRead
BI266HotGasHot GasRead
BI267CcH1CH1:Crankcase HeaterRead
BI268SoftStrtSoft startRead
BI269ResrtStbyRestart stand-byRead
BImin270ErrStateUnit Error statRead
BI271HiPRtryHigh pressure retryRead
BI272LoPRtryLow pressure retryRead
BI273DschPipRtryDisch. pipe retryRead
BI2744WayVlv4-way valveRead
BI2754WayVlv24-way valve 2Read
BI276HiPStpDnCtlH.P. stepping down cntlRead
BI277LoPStpDnCtlL.P. stepping down cntlRead
BI278InvDschStpDnCtlINV Disch. stepping down cntlRead
BI279InvOCStpDnCtlINV OC stepping down cntlRead
BI280InvFinStpDnCtlINV Fin stepping down cntlRead
IV281CoilTR4T :Coil temp.°CRead
IV282ScCilExtTSubcooling Coil exit Temp.°CRead
IV283RcvrLiqTReceiver Liquid Temp.°CRead
PIVmin284InvFrqInverter frequencyHzRead
BI285RcvrGasInSVL:Receiver gas inRead
BI286RcvrGasOutSVG:Receiver gas outRead
BI287StpUnLiqPipClsSVSL:StopUnit Liquid pipe closeRead
BImin288PumpY2M:PumpRead
BI289InvFinCoolM1F:INV_fin_coolRead
BI290OilRecoverY2S:Oil_recoveryRead
IVmin291CndTCondensing Temperature°CRead
IVmin292EvTEvaporating Temperature°CRead
Object ID lookup: CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)

How many BACnet points does the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) have?

This list has 37 BACnet objects: 23 binary inputs, 6 integer values, 8 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1) BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)?

Start with BI 264 Comp1Inv (Inverter compressor running); BI 288 Pump (Pump output (Y2M)); PIV 284 InvFrq (Inverter frequency, Hz); IV 292 EvT (Evaporating temperature, °C); IV 291 CndT (Condensing temperature, °C); PIV 261 DschTInv (Inverter discharge temperature, °C); PIV 263 InvCur (Inverter current, A); BI 270 ErrState (Unit error state).

How do I enable BMS control of the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.