VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from each Daikin VRV-2MA outdoor unit over BACnet: AirNet address, HP, suction, discharge, coil, receiver, ambient, evaporating and condensing temperatures, EV openings, inverter frequency, temperature and currents, three compressor states, heater, valve and multi-oil states, retry and drooping-control flags and fan step (55 objects). Monitoring only.

This page lists 55 BACnet objects for the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
55 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV-2MA
Brands covered
Daikin
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 55 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA

Integration in brief

Use these objects to monitor Daikin outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operating states, temperatures, compressor data and the error state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 264Comp1InvInverter compressor runningRead
BI 282DfrstDefrost activeRead
PIV 295InvFrqInverter frequency, HzRead
IV 299AmbTAmbient temperature, °CRead
IV 303EvTEvaporating temperature, °CRead
IV 302CndTCondensing temperature, °CRead
PIV 261DschTInvInverter discharge temperature, °CRead
PIV 263InvCurInverter current, ARead
BI 274ErrStateUnit error stateRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

55 of 55 shown
Type
Binary
Show
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA BACnet Points List
DescriptionStates
PIV256AirNetAirNet Addr.Read
PIV257HPHPhpRead
IV258SuctTSuction Temperature°CRead
PIV259EVOp1EV opening 1plsRead
PIV260EVOp2EV opening 2plsRead
PIVmin261DschTInvDisch. temp.(INV)°CRead
PIV262InvTInverter temp.°CRead
PIVmin263InvCurInverter currentARead
BImin264Comp1InvCompressor1(INV)Read
BI265Comp2Std1Compressor2(STD1)Read
BI266Comp3Std2Compressor3(STD2)Read
BI267OiRtrnOil returnRead
BI268HotGasHot GasRead
BI269CcH1CH1:Crankcase HeaterRead
BI270CcH2CH2:Crankcase HeaterRead
BI271CcH3CH3:Crankcase HeaterRead
BI272ResrtStbyRestart stand-byRead
BI273MulOiMulti oilRead
BImin274ErrStateUnit Error statRead
BI275EnrgyCutOutpEnergy cut outputRead
BI276HiPRtryHigh pressure retryRead
BI277LoPRtryLow pressure retryRead
BI278DschPipRtryDisch. pipe retryRead
BI2794WayVlv4-way valveRead
BI2804WayVlv24-way valve 2Read
BI281InjctInjectionRead
BImin282DfrstDefrostRead
BI283HiPDroCtlHigh pres. drooping cntl.Read
BI284LoPDroCtlLow pres. drooping cntl.Read
BI285InvDschDroCtlINV Disch. pipe drooping cntl.Read
BI286InvCurDroCtlINV current drooping cntl.Read
BI287InvFinDroCtlINV fin drooping cntl.Read
BI288Std1DschDroCtlStd1DschDroCtlRead
BI289Std1OCDroCtlStd1OCDroCtlRead
BI290Std2DschDroCtlStd2DschDroCtlRead
BI291Std2OCDroCtlStd2OCDroCtlRead
IV292CoilTR4T :Coil temp.°CRead
IV293ScCilExtTSubcooling Coil exit Temp.°CRead
IV294RcvrLiqTReceiver Liquid Temp.°CRead
PIVmin295InvFrqInverter frequencyHzRead
BI296InvStbyINV stand-byRead
BI297RcvrGasOutSVG:Receiver gas outRead
BI298StpUnLiqPipClsSVSL:StopUnit Liquid pipe closeRead
IVmin299AmbTAmbient temperature°CRead
PIV300DschTStd1Disch. temp.(STD1)°CRead
PIV301DschTStd2Disch. temp.(STD2)°CRead
IVmin302CndTCondensing Temperature°CRead
IVmin303EvTEvaporating Temperature°CRead
PIV304EVOpEV openingplsRead
PIV305CTSTD1CT1 (STD1)ARead
PIV306CTSTD2CT2 (STD2)ARead
PIV307InvFanCurINV FAN currentARead
PIV308FanStpFan stepRead
IV309CilGasMnTMain coil gas temp°CRead
IV310CilGasSbTSub coil gas temp°CRead
Object ID lookup: CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA

How many BACnet points does the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA have?

This list has 55 BACnet objects: 31 binary inputs, 9 integer values, 15 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA?

Start with BI 264 Comp1Inv (Inverter compressor running); BI 282 Dfrst (Defrost active); PIV 295 InvFrq (Inverter frequency, Hz); IV 299 AmbT (Ambient temperature, °C); IV 303 EvT (Evaporating temperature, °C); IV 302 CndT (Condensing temperature, °C); PIV 261 DschTInv (Inverter discharge temperature, °C); PIV 263 InvCur (Inverter current, A); BI 274 ErrState (Unit error state).

How do I enable BMS control of the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.