VRF water-cooled outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from each Daikin VRV-3W/4W water-cooled outdoor unit over BACnet: AirNet address, HP, suction, discharge, coil, subcooling, EV liquid pipe, evaporating and condensing temperatures, EV openings, inverter speed, fin temperature and current, compressor, heater, valve, pump and cooling-fan states, retry and stepping-down flags and fan step (40 objects). Monitoring only.

This page lists 40 BACnet objects for the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER
Equipment
VRF water-cooled outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
40 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Daikin VRV W BACnet, CoolMasterNet Daikin, Daikin water cooled VRV BACnet, VRV-3W-WATER, RWEYQ8-30P, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER, RWEYQ8-10T7Y1B
Brands covered
Daikin
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 40 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER

Integration in brief

Use these objects to monitor Daikin outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operating states, temperatures, compressor data and the error state.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 264Comp1InvInverter compressor runningRead
BI 286PumpPump output (Y2M)Read
PIV 294InvRSInverter speed, rpsRead
IV 291EvTEvaporating temperature, °CRead
IV 292CndTCondensing temperature, °CRead
PIV 261DschTInvInverter discharge temperature, °CRead
PIV 263InvCurInverter current, ARead
BI 270ErrStateUnit error stateRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

40 of 40 shown
Type
Binary
Show
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet Points List
DescriptionStates
PIV256AirNetAirNet Addr.Read
PIV257HPHPhpRead
IV258SuctTSuction Temperature°CRead
PIV259EVOp1EV opening 1plsRead
PIV260EVOp3EV opening 3plsRead
PIVmin261DschTInvDisch. temp.(INV)°CRead
PIV262InvFinTInverter fin temp.°CRead
PIVmin263InvCurInverter currentARead
BImin264Comp1InvCompressor1(INV)Read
BI265OiRtrnOil returnRead
BI266HotGasHot GasRead
BI267CcH1CH1:Crankcase HeaterRead
BI268SoftStrtSoft startRead
BI269ResrtStbyRestart stand-byRead
BImin270ErrStateUnit Error statRead
BI271HiPRtryHigh pressure retryRead
BI272LoPRtryLow pressure retryRead
BI273DschPipRtryDisch. pipe retryRead
BI2744WayVlv4-way valveRead
BI2754WayVlv24-way valve 2Read
BI276HiPStpDnCtlH.P. stepping down cntlRead
BI277LoPStpDnCtlL.P. stepping down cntlRead
BI278DmndStpDnCtlDemand stepping down cntlRead
BI279InvRtryINV retryRead
BI280InvDschStpDnCtlINV Disch. stepping down cntlRead
BI281InvOCStpDnCtlINV OC stepping down cntlRead
BI282InvFinStpDnCtlINV Fin stepping down cntlRead
BI283RcvrGasInSVL:Receiver gas inRead
BI284RcvrGasOutSVG:Receiver gas outRead
BI285StpUnLiqPipClsSVSL:StopUnit Liquid pipe closeRead
BImin286PumpY2M:PumpRead
BI287OilRecoverY2S:Oil_recoveryRead
BI288InvCoolFanM1F:INV_cool_fanRead
IV289CoilTR4T :Coil temp.°CRead
IV290ScCilExtTSubcooling Coil exit Temp.°CRead
IVmin291EvTEvaporating Temperature°CRead
IVmin292CndTCondensing Temperature°CRead
IV293EVLiqTEV liquid pipe temp.°CRead
PIVmin294InvRSInverter Revolution SpeedrpsRead
PIV295FanStpFan stepRead
Object ID lookup: CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER

How many BACnet points does the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER have?

This list has 40 BACnet objects: 25 binary inputs, 6 integer values, 9 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER?

Start with BI 264 Comp1Inv (Inverter compressor running); BI 286 Pump (Pump output (Y2M)); PIV 294 InvRS (Inverter speed, rps); IV 291 EvT (Evaporating temperature, °C); IV 292 CndT (Condensing temperature, °C); PIV 261 DschTInv (Inverter discharge temperature, °C); PIV 263 InvCur (Inverter current, A); BI 270 ErrState (Unit error state).

How do I enable BMS control of the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.