- CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER
VRF water-cooled outdoor unit monitoring via BACnet gateway · BACnet points list
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet points list
Updated 12 November 2026
With PRO functionality, CoolAutomation gateways publish service data from each Daikin VRV-3W/4W water-cooled outdoor unit over BACnet: AirNet address, HP, suction, discharge, coil, subcooling, EV liquid pipe, evaporating and condensing temperatures, EV openings, inverter speed, fin temperature and current, compressor, heater, valve, pump and cooling-fan states, retry and stepping-down flags and fan step (40 objects). Monitoring only.
This page lists 40 BACnet objects for the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.
- Manufacturer
- CoolAutomation
- Model
- CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER
- Equipment
- VRF water-cooled outdoor unit monitoring via BACnet gateway
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 40 (0 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 64
- Also known as
- Daikin VRV W BACnet, CoolMasterNet Daikin, Daikin water cooled VRV BACnet, VRV-3W-WATER, RWEYQ8-30P, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER, RWEYQ8-10T7Y1B
- Brands covered
- Daikin
Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.
BMS integration notes: CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER
Use these objects to monitor Daikin outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operating states, temperatures, compressor data and the error state.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 264 | Comp1Inv | Inverter compressor running | Read |
| BI 286 | Pump | Pump output (Y2M) | Read |
| PIV 294 | InvRS | Inverter speed, rps | Read |
| IV 291 | EvT | Evaporating temperature, °C | Read |
| IV 292 | CndT | Condensing temperature, °C | Read |
| PIV 261 | DschTInv | Inverter discharge temperature, °C | Read |
| PIV 263 | InvCur | Inverter current, A | Read |
| BI 270 | ErrState | Unit error state | Read |
Enable & remote start
BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.
Network setup
- BACnet MS/TP: activate on line L3 with 'line type L3 BAC' (L4-L7 also possible on the CoolMaster product line); default frame 9600 8N1, change with 'line baud L3 <rate>_8N1'; MAC (TS) default 0x40 = 64, change with 'line myid L3 <hex>'. Reboot after each change.
- BACnet IP: enable with 'bacnet IP enable'; UDP port 47808 by default ('bacnet port <n>'). The server starts only once Ethernet is up with an IP address.
- Default device instance 64 (0x40); change with 'bacnet instance <n>'.
Watch out for
- The guide does not document how VAs are assigned to outdoor units; confirm instances with a BACnet discovery.
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| PIV | 256 | AirNet | AirNet Addr. | Read | ||
| PIV | 257 | HP | HP | hp | Read | |
| IV | 258 | SuctT | Suction Temperature | °C | Read | |
| PIV | 259 | EVOp1 | EV opening 1 | pls | Read | |
| PIV | 260 | EVOp3 | EV opening 3 | pls | Read | |
| PIVmin | 261 | DschTInv | Disch. temp.(INV) | °C | Read | |
| PIV | 262 | InvFinT | Inverter fin temp. | °C | Read | |
| PIVmin | 263 | InvCur | Inverter current | A | Read | |
| BImin | 264 | Comp1Inv | Compressor1(INV) | Read | ||
| BI | 265 | OiRtrn | Oil return | Read | ||
| BI | 266 | HotGas | Hot Gas | Read | ||
| BI | 267 | CcH1 | CH1:Crankcase Heater | Read | ||
| BI | 268 | SoftStrt | Soft start | Read | ||
| BI | 269 | ResrtStby | Restart stand-by | Read | ||
| BImin | 270 | ErrState | Unit Error stat | Read | ||
| BI | 271 | HiPRtry | High pressure retry | Read | ||
| BI | 272 | LoPRtry | Low pressure retry | Read | ||
| BI | 273 | DschPipRtry | Disch. pipe retry | Read | ||
| BI | 274 | 4WayVlv | 4-way valve | Read | ||
| BI | 275 | 4WayVlv2 | 4-way valve 2 | Read | ||
| BI | 276 | HiPStpDnCtl | H.P. stepping down cntl | Read | ||
| BI | 277 | LoPStpDnCtl | L.P. stepping down cntl | Read | ||
| BI | 278 | DmndStpDnCtl | Demand stepping down cntl | Read | ||
| BI | 279 | InvRtry | INV retry | Read | ||
| BI | 280 | InvDschStpDnCtl | INV Disch. stepping down cntl | Read | ||
| BI | 281 | InvOCStpDnCtl | INV OC stepping down cntl | Read | ||
| BI | 282 | InvFinStpDnCtl | INV Fin stepping down cntl | Read | ||
| BI | 283 | RcvrGasIn | SVL:Receiver gas in | Read | ||
| BI | 284 | RcvrGasOut | SVG:Receiver gas out | Read | ||
| BI | 285 | StpUnLiqPipCls | SVSL:StopUnit Liquid pipe close | Read | ||
| BImin | 286 | Pump | Y2M:Pump | Read | ||
| BI | 287 | OilRecover | Y2S:Oil_recovery | Read | ||
| BI | 288 | InvCoolFan | M1F:INV_cool_fan | Read | ||
| IV | 289 | CoilT | R4T :Coil temp. | °C | Read | |
| IV | 290 | ScCilExtT | Subcooling Coil exit Temp. | °C | Read | |
| IVmin | 291 | EvT | Evaporating Temperature | °C | Read | |
| IVmin | 292 | CndT | Condensing Temperature | °C | Read | |
| IV | 293 | EVLiqT | EV liquid pipe temp. | °C | Read | |
| PIVmin | 294 | InvRS | Inverter Revolution Speed | rps | Read | |
| PIV | 295 | FanStp | Fan step | Read |
No points match these filters.
Object ID lookup: CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER point IDs by name
PIV256AirNetPIV257HPIV258SuctTPIV259EVOp1PIV260EVOp3PIV261DschTInvPIV262InvFinTPIV263InvCurBI264Comp1InvBI265OiRtrnBI266HotGasBI267CcH1BI268SoftStrtBI269ResrtStbyBI270ErrStateBI271HiPRtryBI272LoPRtryBI273DschPipRtryBI2744WayVlvBI2754WayVlv2BI276HiPStpDnCtlBI277LoPStpDnCtlBI278DmndStpDnCtlBI279InvRtryBI280InvDschStpDnCtlBI281InvOCStpDnCtlBI282InvFinStpDnCtlBI283RcvrGasInBI284RcvrGasOutBI285StpUnLiqPipClsBI286PumpBI287OilRecoverBI288InvCoolFanIV289CoilTIV290ScCilExtTIV291EvTIV292CndTIV293EVLiqTPIV294InvRSPIV295FanStp
Integration notes
- Instance = VA x 256 + index (object identifier bits 21-8 = VA, 7-0 = index). Points shown for VA 1; the guide does not explain how outdoor units receive their VA.
- Access set to read-only: these are measured service values, although the guide's type table lists PIV as read/write.
- Object names are the guide's short names; descriptions are the guide's object descriptions with the bracketed unit moved to units.
- Table printed on page 45 of the guide (section 3.2.1.3).
- For the outdoor system objects the guide groups these series with VRV-M (REYQ8-48M), VRV-3R and VRV3C; that table matches site lists coolmasternet-daikin-vrv-system-vrvm-reyq8-48m and coolmasternet-daikin-vrv-system-vrv3r-vrv3c.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER
How many BACnet points does the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER have?
This list has 40 BACnet objects: 25 binary inputs, 6 integer values, 9 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER BACnet documentation?
The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.
What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER?
Start with BI 264 Comp1Inv (Inverter compressor running); BI 286 Pump (Pump output (Y2M)); PIV 294 InvRS (Inverter speed, rps); IV 291 EvT (Evaporating temperature, °C); IV 292 CndT (Condensing temperature, °C); PIV 261 DschTInv (Inverter discharge temperature, °C); PIV 263 InvCur (Inverter current, A); BI 270 ErrState (Unit error state).
How do I enable BMS control of the CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER?
BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.
How do I check these points on the real CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3W-WATER, VRV3C2-WATER, VRV-3Wx-WATER, VRV-4W-WATER?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More CoolAutomation BACnet points lists
- Multi-brand VRF / split AC BACnet gateway
CoolAutomation CoolMasterNet BACnet (indoor unit objects)
Indoor units of VRF and split systems connected to a CoolMasterNet or CooLink gateway (Daikin, Mitsubishi Electric, LG, Samsung, Gree and other supported brands).
Also known as: CoolMasterNet, CooLinkNet, CooLinkHub, CooLinkBridge, CoolAutomation BACnet, LG VRF BACnet gateway, Daikin VRV BACnet gateway, Mitsubishi Electric BACnet gateway, Samsung BACnet gateway, Gree GMV BACnet gateway - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - EXL (RSLYJ355-560)
Daikin EXL outdoor systems RSLYJ355-560 (KA/KC; printed "KA_KC") read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, EXL, RSLYJ355-560 - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - RXTA-A
Daikin RXTA-A outdoor systems read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, RXTA-A - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - Ve-up3Q (RQYP140-900A)
Daikin Ve-up3Q outdoor systems (RQYP140-900A) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, Ve-up3Q, RQYP140-900A - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV PLUS (RSEYP16-30KJY1)
Daikin VRV PLUS outdoor systems (RSEYP16-30KJY1) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV_PLUS, VRV Plus, RSEYP16-30KJY1 - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-K (RSEYP8-10KJ)
Daikin VRV-K outdoor systems (RSEYP8-10KJ) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-K, RSEYP8-10KJ - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin outdoor system (PRO) objects - VRV-L (RSXYP5-10L)
Daikin VRV-L outdoor systems RSXYP5-10L (JY1/Y1/YL) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-L, RSXYP5-10L - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV-3R, VRV3C
Daikin VRV outdoor systems (VRV-3R, VRV3C, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-3R, VRV3C - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV-4R
Daikin VRV outdoor systems (VRV-4R, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-4R - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV-M (REYQ8-48M)
Daikin VRV outdoor systems (VRV-M (REYQ8-48M), as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV-M (REYQ8-48M) - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV4S1, VRV4S2, mini-VRV, VRV-3S, VRV-M, VRV-3P
Daikin VRV outdoor systems (VRV4S1, VRV4S2, mini-VRV, VRV-3S, VRV-M, VRV-3P, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV4S1, VRV4S2, mini-VRV, VRV-3S, VRV-M, VRV-3P - VRF outdoor system monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor system (PRO) objects - VRV4S3, VRVX, VRV4-EU
Daikin VRV outdoor systems (VRV4S3, VRVX, VRV4-EU, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor system BACnet, VRV4S3, VRVX, VRV4-EU - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - mini-VRV, VRV-M
Daikin VRV outdoor units (mini-VRV, VRV-M, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, mini-VRV, VRV-M - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - Ve-up3Q (RQYP140-900A)
Daikin Ve-up3Q outdoor units (RQYP140-900A) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, Ve-up3Q, RQYP140-900A - VRF water-cooled outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2-WATER (RWEYQ10-30MY1)
Daikin water-cooled VRV units VRV-2-WATER (RWEYQ10-30MY1) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV W BACnet, CoolMasterNet Daikin, Daikin water cooled VRV BACnet, VRV-2-WATER, RWEYQ10-30MY1 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-2MA
Daikin VRV outdoor units of the series CoolAutomation calls VRV-2MA, read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV-2MA - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-3R, VRV3C
Daikin VRV outdoor units (VRV-3R, VRV3C, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV-3R, VRV3C - VRF water-cooled outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-4W3-WATER (RWEYQ8-14T9Y1B)
Daikin water-cooled VRV units VRV-4W3-WATER (RWEYQ8-14T9Y1B) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV W BACnet, CoolMasterNet Daikin, Daikin water cooled VRV BACnet, VRV-4W3-WATER, RWEYQ8-14T9Y1B - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV-M (REYQ8-48M)
Daikin VRV outdoor units (VRV-M (REYQ8-48M), as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV-M (REYQ8-48M) - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Daikin VRV outdoor unit (PRO) objects - VRV4S1, VRV4S2, VRV-3S, VRV-3P
Daikin VRV outdoor units (VRV4S1, VRV4S2, VRV-3S, VRV-3P, as grouped by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Daikin VRV BACnet, CoolMasterNet Daikin, Daikin outdoor unit BACnet, VRV4S1, VRV4S2, VRV-3S, VRV-3P - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Fujitsu AJ*GALH outdoor unit (PRO) objects
Fujitsu outdoor units AJHuGALH, AJHGALH, AOULBV, AJHGALBH, AJYGALBH, AJQGALAH, AJTuGALH, AJTGALH, AJTGBLH, AJYuGALH, AJYGALH, AJYGALDH and AJHGALDH (model codes exactly as printed by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Fujitsu VRF BACnet, CoolMasterNet Fujitsu, AJHGALH, AOULBV, AJHGALBH, AJYGALBH, AJQGALAH, AJTGALH, AJTGBLH, AJYGALH, AJYGALDH, AJHGALDH - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Fujitsu AJ*LALBH outdoor unit (PRO) objects
Fujitsu outdoor units AJY[72/90/108/126/144/162]LALBH, AOULBV1, AJGLNLBH, AJHLALBH, AJHLATBH, AJHLNLBH, AJHLNTBH, AJHLNTCH, AJHLALCH, AJQLALBH, AJYLATBH, AJYLNLBH, AJYLNTBH, AJYLNTCH, AJYLALCH, AJHLALDH and AJYLALDH (model codes as printed by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Fujitsu VRF BACnet, CoolMasterNet Fujitsu, AJY LALBH, AOULBV1, AJGLNLBH, AJHLALBH, AJHLATBH, AJHLNLBH, AJHLNTBH, AJHLNTCH, AJHLALCH, AJQLALBH, AJYLATBH, AJYLNLBH, AJYLNTBH, AJYLNTCH, AJYLALCH, AJHLALDH, AJYLALDH - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Fujitsu AJ*LCLAH outdoor unit (PRO) objects
Fujitsu outdoor units AJT[40/45/54]LCLAH, AJY[40/45/54]LCLAH, AJCLCTAH, AJHLCLAH, AJQLCLAH, AOURLAVS, AJYLCLDH and AJHLCLDH (model codes as printed by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Fujitsu VRF BACnet, CoolMasterNet Fujitsu, AJY LCLAH, AJT LCLAH, AJCLCTAH, AJHLCLAH, AJQLCLAH, AOURLAVS, AJYLCLDH, AJHLCLDH - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Fujitsu AJ*NLAH outdoor unit (PRO) objects
Fujitsu outdoor units AJHLNLAH, AJHLNLAHU, AJHLNTAH, AJQLBLH, AJYLNLAH, AJYLNTAH and AOUuRLBV (model codes as printed by CoolAutomation) read through a CoolAutomation gateway with PRO functionality.
Also known as: Fujitsu VRF BACnet, CoolMasterNet Fujitsu, AJHLNLAH, AJHLNLAHU, AJHLNTAH, AJQLBLH, AJYLNLAH, AJYLNTAH, AOUuRLBV - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV5 HR (heat recovery) outdoor unit (PRO) objects
Gree GMV5 HR (heat recovery) VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV5 BACnet, CoolMasterNet Gree, Gree outdoor unit BACnet, GMV5 HR - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects
Gree GMV5 mini VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV5 mini BACnet, CoolMasterNet Gree, GMV5 mini - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV5 outdoor unit (PRO) objects
Gree GMV5 VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV5 BACnet, CoolMasterNet Gree, Gree outdoor unit BACnet, GMV5 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV5C outdoor unit (PRO) objects
Gree GMV5C VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV5C BACnet, CoolMasterNet Gree, GMV5C - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree GMV6 mini U.H. outdoor unit (PRO) objects
Gree GMV6 mini U.H. VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree GMV6 mini BACnet, CoolMasterNet Gree, GMV6 mini U.H. - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree VRF6 HR outdoor unit (PRO) objects
Gree VRF6 HR (heat recovery) VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree VRF6 HR BACnet, Gree VRF6 heat recovery BACnet, CoolMasterNet Gree, VRF6 HR - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects
Gree VRF6 (heat pump) VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Gree VRF6 BACnet, Gree GMV6 BACnet, CoolMasterNet Gree, VRF6 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG Multi V III HR master outdoor unit (PRO) objects
LG Multi V III heat recovery VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality (LGMV section of the guide).
Also known as: LG Multi V III heat recovery BACnet, CoolMasterNet LG, MultiV III HR Master, LGMV - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG Multi V III master outdoor unit (PRO) objects
LG Multi V III VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality (LGMV section of the guide).
Also known as: LG Multi V III BACnet, CoolMasterNet LG, MultiV III Master, LGMV - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG MULTIV_S master outdoor unit (PRO) objects
LG Multi V S VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: LG Multi V S BACnet, LG MULTIV_S BACnet, CoolMasterNet LG, MULTIV_S Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG SUPER5 master outdoor unit (PRO) objects
LG VRF outdoor units of the SUPER5 type (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: LG Multi V 5 BACnet, LG SUPER5 BACnet, CoolMasterNet LG, SUPER5 Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG VRF outdoor unit (PRO) objects
LG VRF outdoor units read through a CoolAutomation gateway with PRO (service data) functionality.
Also known as: LG VRF BACnet, LG BACnet points list, LG outdoor unit BACnet, CoolMasterNet LG - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet LG WATER5 master outdoor unit (PRO) objects
LG water-source VRF outdoor units of the WATER5 type (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: LG Multi V Water 5 BACnet, LG WATER5 BACnet, CoolMasterNet LG, WATER5 Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Midea CR-HP master outdoor unit (PRO) objects
Midea VRF heat pump outdoor units of the CR-HP type (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Midea CR-HP VRF BACnet, CoolMasterNet Midea, CR-HP Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Midea CR-HR master outdoor unit (PRO) objects
Midea VRF heat recovery outdoor units of the CR-HR type (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Midea CR-HR VRF BACnet, Midea heat recovery VRF BACnet, CoolMasterNet Midea, CR-HR Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Midea V6 master outdoor unit (PRO) objects
Midea V6 VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Midea V6 VRF BACnet, CoolMasterNet Midea, V6 Master - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Midea V8 master outdoor unit (PRO) objects
Midea V8 VRF outdoor units (master unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Midea V8 VRF BACnet, CoolMasterNet Midea, V8 Master - VRF branch controller monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric BC controller (JA/KA) (PRO) objects
Mitsubishi Electric City Multi BC controllers of the types CoolAutomation calls BC(JA) and BC(KA), read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BC controller BACnet, CoolMasterNet Mitsubishi Electric, BC(JA), BC(KA) - Air-to-water heat pump monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric CAHV heat pump (PRO) objects
Mitsubishi Electric CAHV units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi CAHV BACnet, CoolMasterNet Mitsubishi Electric, CAHV - VRF branch controller monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric CMB-WP/CMB-WM branch controller (PRO) objects
Mitsubishi Electric CMB-WP [capacity] V-GA1 and CMB-WM [capacity] V-AA branch controllers read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Hybrid City Multi BACnet, CoolMasterNet Mitsubishi Electric, CMB-WP V-GA1, CMB-WM V-AA - Multi-split outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric MXZ series outdoor unit (PRO) objects
Mitsubishi Electric MXZ series multi-split outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi MXZ BACnet, CoolMasterNet Mitsubishi Electric, MXZ series, PUMY series - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PUHV-P CM-E outdoor unit (PRO) objects
Mitsubishi Electric PUHV-P [capacity] CM-E outdoor units (the guide heading ends in "CM-E/..." without naming the other suffixes) read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHV-P CM-E - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-M YNW-A1 outdoor unit (PRO) objects
Mitsubishi Electric City Multi PUHY-M [capacity] YNW-A1 outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHY-M YNW-A1 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P CM-E(1) outdoor unit (PRO) objects
Mitsubishi Electric City Multi PUHY-P [capacity] CM-E(1) outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHY-P CM-E, PUHY-P CM-E1 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects
Mitsubishi Electric City Multi PUHY-P [capacity] TGMU-A outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHY-P TGMU-A - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PURY-M YNW-A/A1 outdoor unit (PRO) objects
Mitsubishi Electric City Multi PURY-M [capacity] YNW-A/A1 outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PURY-M YNW-A, PURY-M YNW-A1 - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Electric PURY-P ZKMU-A outdoor unit (PRO) objects
Mitsubishi Electric City Multi PURY-P [capacity] ZKMU-A outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PURY-P ZKMU-A - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries JL4C outdoor unit (PRO) objects
Mitsubishi Heavy Industries VRF outdoor units of the series CoolAutomation calls JL4C, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, JL4C - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries K1RC outdoor unit (PRO) objects
Mitsubishi Heavy Industries VRF outdoor units of the series CoolAutomation calls K1RC, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, K1RC - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries KV1C outdoor unit (PRO) objects
Mitsubishi Heavy Industries VRF outdoor units of the series CoolAutomation calls KV1C, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, KV1C - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries KV2C outdoor unit (PRO) objects
Mitsubishi Heavy Industries VRF outdoor units of the series CoolAutomation calls KV2C, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, KV2C - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Mitsubishi Heavy Industries L3SC / KYWC outdoor unit (PRO) objects
Mitsubishi Heavy Industries single-compressor VRF outdoor units of the series CoolAutomation calls L3SC and KYWC, read through a CoolAutomation gateway with PRO functionality.
Also known as: Mitsubishi Heavy VRF BACnet, MHI KX BACnet, CoolMasterNet MH, L3SC, KYWC - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung DVM S Eco 4/5/6 HP outdoor unit (PRO) objects
Samsung DVM S Eco 4, 5 and 6 HP VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung DVM S Eco BACnet, CoolMasterNet Samsung, DVM-S Eco 4/5/6HP - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung DVM S Eco 7/8/9 HP outdoor unit (PRO) objects
Samsung DVM S Eco 7, 8 and 9 HP VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung DVM S Eco BACnet, CoolMasterNet Samsung, DVM-S Eco 7/8/9HP - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung DVM S outdoor unit (PRO) objects
Samsung DVM S VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung DVM S BACnet, CoolMasterNet Samsung, Samsung outdoor unit BACnet, DVM-S - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung DVM S Water HR outdoor unit (PRO) objects
Samsung DVM S Water heat recovery (water-source) VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung DVM S Water BACnet, CoolMasterNet Samsung, DVM-S Water HR - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Samsung FJM outdoor unit (PRO) objects
Samsung FJM (free joint multi) outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Samsung FJM BACnet, Samsung free joint multi BACnet, CoolMasterNet Samsung, FJM - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects
Toshiba SMMS VRF outdoor units (header unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Toshiba SMMS BACnet, Toshiba VRF BACnet, CoolMasterNet Toshiba, SMMS Header - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Toshiba SMMS-Mini outdoor unit (PRO) objects
Toshiba Mini-SMMS VRF outdoor units read through a CoolAutomation gateway with PRO functionality.
Also known as: Toshiba SMMS Mini BACnet, Toshiba Mini-SMMS BACnet, CoolMasterNet Toshiba, SMMS-Mini - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Toshiba SMMSe header outdoor unit (PRO) objects
Toshiba SMMSe VRF outdoor units (header unit) read through a CoolAutomation gateway with PRO functionality.
Also known as: Toshiba SMMSe BACnet, Toshiba VRF BACnet, CoolMasterNet Toshiba, SMMSe Header - VRF outdoor unit monitoring via BACnet gateway
CoolAutomation CoolMasterNet Toshiba SMMSu outdoor unit (PRO) objects
Toshiba SMMSu (SMMS-u) VRF outdoor units read through a CoolAutomation gateway with PRO functionality (SMMSu outdoor section of the guide).
Also known as: Toshiba SMMSu BACnet, Toshiba SMMS-u BACnet, CoolMasterNet Toshiba, SMMSu
Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.