VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Gree GMV5 mini outdoor units over BACnet: rated capacity, protocol versions, outdoor temperature, compressor and fan frequencies, module high and low pressure, discharge, defrost, subcooler and separator temperatures, EXV positions, compressor and valve states and drive currents, voltages and module temperatures, plus compressor drive status, target frequencies and absolute pressures in kPa (48 objects). Monitoring only.

This page lists 48 BACnet objects for the CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
48 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Gree GMV5 mini BACnet, CoolMasterNet Gree, GMV5 mini
Brands covered
Gree
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 48 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Gree outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend compressor, pressure and temperature data.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 272Comp1Compressor 1 runningRead
PIV 262Comp1OpFreqCompressor 1 frequency, HzRead
IV 261AmbTOutdoor temperature, °CRead
IV 263MdlHiPrsModule high pressure valueRead
IV 264MdlLoPrsModule low pressure valueRead
IV 265Comp1DisTCompressor 1 discharge temperature, °CRead
AI 282Comp1CurCompressor 1 current, ARead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

48 of 48 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
AI257RatedCapRated capacitykWRead
PIV258GenVerGeneral protocol versionRead
PIV259UnitVerUnit protocol versionRead
PIV260PwrTpPower typeRead
IVmin261AmbTOutdoor ambient temperature°CRead
PIVmin262Comp1OpFreqCompressor 1 operation frequencyHzRead
IVmin263MdlHiPrsModule high pressure°CRead
IVmin264MdlLoPrsModule low pressure°CRead
IVmin265Comp1DisTCompressor 1 discharge temperature°CRead
IV266DfrsT1Defrosting temperature 1°CRead
IV267SbclLiqOutTSubcooler liquid outlet temperature°CRead
IV268SbclGsOutTSubcooler gas outlet temperature°CRead
IV269GsSepInTubTGas separator inlet tube temperature°CRead
IV270GsSepOutTubTGas separator outlet tube temperature°CRead
PIV271HtEXVODU heating EXVPlsRead
BImin272Comp1Compressor 1 statusRead
BI2734WayVlv14-way valve1 statusRead
BI274OiRtVlv1Oil return valve 1Read
BI275RefgnRcvyRefrigerant recoveringRead
BI276GsBpsVlvGas bypass valve statusRead
BI277SolVlvASolenoid valve ARead
BI278SolVlvBSolenoid valve BRead
BI279Comp1E-HtCompressor 1 e-heaterRead
BI280ChasE-HtChassis e-heaterRead
BI281RstComplReset completedRead
AImin282Comp1CurCompressor 1 currentARead
PIV283Comp1BsbVCompressor 1 busbar voltageVRead
IV284Comp1MdlTCompressor 1 module temperature°CRead
PIV285SbclEXVSubcooler EXVPlsRead
BI286Comp1WkMgCompressor 1 weak magnetismRead
BI287Comp1LimFreqCompressor 1 drive module limited frequencyRead
BI288Comp1LoFreqCompressor 1 drive module lower frequencyRead
BI289Comp1PwrSrcCompressor 1 drive AC input power sourceRead
AI290DistCabDistribution capabilitykWRead
PIV291Comp1TgtFreqComp1 target frequencyHzRead
PIV292Fan1TgtFreqFan1 target frequencyHzRead
PIV293Fan2TgtFreqFan2 target frequencyHzRead
PIV294MdlAbsHpModule absolute high pressurekPaRead
PIV295MdlAbsLpModule absolute low pressurekPaRead
IV296HtExGsOutTHeat exchanger gas outlet temperature°CRead
AI297Comp1InCurComp1 input currentARead
PIV298Comp1UCurComp1 U phase currentARead
PIV299Comp1VCurComp1 V phase currentARead
IV300Comp1PfcTCompressor 1 drive PFC temperature°CRead
IV301Comp1EBoxTCompressor 1 drive electric box temperature°CRead
PIV302Comp1DevCompressor 1 device statusRead
PIV303Comp1WrkCompressor 1 work statusRead
Object ID lookup: CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects have?

This list has 48 BACnet objects: 4 analog inputs, 14 binary inputs, 1 characterstring value, 13 integer values, 16 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects?

Start with BI 272 Comp1 (Compressor 1 running); PIV 262 Comp1OpFreq (Compressor 1 frequency, Hz); IV 261 AmbT (Outdoor temperature, °C); IV 263 MdlHiPrs (Module high pressure value); IV 264 MdlLoPrs (Module low pressure value); IV 265 Comp1DisT (Compressor 1 discharge temperature, °C); AI 282 Comp1Cur (Compressor 1 current, A).

How do I enable BMS control of the CoolAutomation CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Gree GMV5 mini outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.