VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Mitsubishi Electric City Multi PUHY-P TGMU-A outdoor units over BACnet: type, control and operation mode, compressor and fan frequencies, total cooling and heating capacity, LEV positions, compressor currents and bus voltage, 63HS/63LS pressures, thermistor, subcooling, superheat, condensing and evaporating temperatures and solenoid valve and demand states (44 objects). Monitoring only.

This page lists 44 BACnet objects for the CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
44 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Mitsubishi City Multi BACnet, CoolMasterNet Mitsubishi Electric, PUHY-P TGMU-A
Brands covered
Mitsubishi Electric
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 44 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Mitsubishi Electric equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the block's VA and trend operation mode, compressor frequency and pressures.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
PIV 258OpeMOperation mode codeRead
PIV 257CtrlMControl mode codeRead
PIV 285F1Compressor 1 frequency, HzRead
AI 26863HSHigh pressure, kg/cm2Read
AI 26963LSLow pressure, kg/cm2Read
AI 281TcCondensing temperature, °CRead
AI 282TeEvaporating temperature, °CRead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

44 of 44 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIVmin257CtrlMControl ModeRead
PIVmin258OpeMOperation ModeRead
IV259F(Hz)All temporary frequenciesHzRead
PIV260FANFan outputHzRead
PIV261QjCTotal capacity CoolRead
PIV262QjHTotal capacity HeatRead
PIV263LEV1LEV1 Linear expansion valveplsRead
AI264IdcDirect currentARead
AI265IuU-Phase current effective valueARead
AI266IwW-Phase current effective valueARead
AI267VdcCOMP bus voltageVRead
AImin26863HSHigh pressure sensorkg/cm2Read
AImin26963LS63LS Pressure sensorkg/cm2Read
AI270TH5Thermistor 5°CRead
AI271TH6Thermistor 6°CRead
AI272TH7Thermistor 7°CRead
AI273TH8Thermistor 8°CRead
AI274TH11Thermistor 11°CRead
AI275TH12Thermistor 12°CRead
AI276FAN-VerFan1 SW versionRead
PIV277SaveCapacity save signal%Read
AI278SCoHeat exchanger outlet subcooling°CRead
AI279SCcCoil outlet subcooling°CRead
AI280SHbCoil bypass outlet superheat°CRead
AImin281TcCondensing temperature°CRead
AImin282TeEvaporating temperature°CRead
AI283THHS1THHS1°CRead
AI284THHS5THHS5°CRead
PIVmin285F1Temporary frequency of No.1 COMPHzRead
PIV286F2F2HzRead
IV287AKHeat exchanger capacityRead
BI288DmndDemandRead
BI289SV1SV1Read
BI290Dmnd2Demand2Read
BI291SnowSnowRead
BI292NgtNightRead
BI29321S4a21S4aRead
BI29421S4b21S4bRead
BI295SV5bSV5bRead
BI296PwrPower source frequencyRead
BI297RepRepeater outputRead
BI29852F52FRead
BI299LEV3LEV3 PulseplsRead
Object ID lookup: CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects have?

This list has 44 BACnet objects: 20 analog inputs, 12 binary inputs, 1 characterstring value, 2 integer values, 9 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects?

Start with PIV 258 OpeM (Operation mode code); PIV 257 CtrlM (Control mode code); PIV 285 F1 (Compressor 1 frequency, Hz); AI 268 63HS (High pressure, kg/cm2); AI 269 63LS (Low pressure, kg/cm2); AI 281 Tc (Condensing temperature, °C); AI 282 Te (Evaporating temperature, °C).

How do I enable BMS control of the CoolAutomation CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Mitsubishi Electric PUHY-P TGMU-A outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.