VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Gree VRF6 outdoor units over BACnet: rated capacity, protocol versions, outdoor temperature, compressor and fan frequencies, module high and low pressure, discharge, defrost, subcooler and separator temperatures, EXV positions, compressor and valve states and drive currents, voltages and module temperatures (49 objects). Monitoring only.

This page lists 49 BACnet objects for the CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Gree VRF6 outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
49 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Gree VRF6 BACnet, Gree GMV6 BACnet, CoolMasterNet Gree, VRF6
Brands covered
Gree
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 49 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Gree outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the outdoor block's VA and trend compressor, pressure and temperature data.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 282Comp1Compressor 1 runningRead
PIV 265Comp1OpFreqCompressor 1 frequency, HzRead
IV 264AmbTOutdoor temperature, °CRead
IV 269MdlHiPrsModule high pressure valueRead
IV 270MdlLoPrsModule low pressure valueRead
IV 271Comp1DisTCompressor 1 discharge temperature, °CRead
AI 291Comp1CurCompressor 1 current, ARead

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

49 of 49 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
AI257RatedCapRated capacitykWRead
PIV258MsSlMaster-Slave statusRead
PIV259GenVerGeneral protocol versionRead
PIV260UnitVerUnit protocol versionRead
PIV261PwrTpPower typeRead
PIV262FanTpFan typeRead
PIV263FanEmergFan emergency statusRead
IVmin264AmbTOutdoor ambient temperature°CRead
PIVmin265Comp1OpFreqCompressor 1 operation frequencyHzRead
PIV266Comp2OpFreqCompressor 2 operation frequencyHzRead
PIV267Fan1OpFreqFan1 operation frequencyHzRead
PIV268Fan2OpFreqFan2 operation frequencyHzRead
IVmin269MdlHiPrsModule high pressure°CRead
IVmin270MdlLoPrsModule low pressure°CRead
IVmin271Comp1DisTCompressor 1 discharge temperature°CRead
IV272Comp1TpCvrTCompressor 1 top cover temperature°CRead
IV273Comp2DisTCompressor 2 discharge temperature°CRead
IV274Comp2TpCvrTCompressor 2 top cover temperature°CRead
IV275DfrsT1Defrosting temperature 1°CRead
IV276SbclLiqOutTSubcooler liquid outlet temperature°CRead
IV277SbclGsOutTSubcooler gas outlet temperature°CRead
IV278GsSepInTubTGas separator inlet tube temperature°CRead
IV279GsSepOutTubTGas separator outlet tube temperature°CRead
PIV280HtEXVODU heating EXVPlsRead
PIV281FanStcPrsMdOutdoor fan static pressure modeRead
BImin282Comp1Compressor 1 statusRead
BI283Comp2Compressor 2 statusRead
BI2844WayVlv14-way valve1 statusRead
BI285LoPrsMsrVlvLow pressure measure valveRead
BI286OiRtVlv1Oil return valve 1Read
BI287OiRtVlv2Oil return valve 2Read
BI288AuxOiRtVlv1Auxiliary oil return valve 1Read
BI289SbclSolVlvSubcooler solenoid valveRead
BI290HtGsBpsVlvHot-gas by-pass valveRead
AImin291Comp1CurCompressor 1 currentARead
PIV292Comp1BsbVCompressor 1 busbar voltageVRead
IV293Comp1MdlTCompressor 1 module temperature°CRead
AI294Fan1CurFan1 currentARead
PIV295Fan1BsbVFan1 busbar voltageVRead
IV296Fan1MdlTFan1 module temperature°CRead
AI297Comp2CurCompressor 2 currentARead
PIV298Comp2BsbVCompressor 2 busbar voltageVRead
IV299Comp2MdlTCompressor 2 module temperature°CRead
AI300Fan2CurFan2 currentARead
PIV301Fan2BsbVFan2 busbar voltageVRead
IV302Fan2MdlTFan2 module temperature°CRead
PIV303SbclEXVSubcooler EXVPlsRead
IV304SbclGsInTSubcooler gas inlet temperature°CRead
Object ID lookup: CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Gree VRF6 outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects have?

This list has 49 BACnet objects: 5 analog inputs, 9 binary inputs, 1 characterstring value, 17 integer values, 17 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects?

Start with BI 282 Comp1 (Compressor 1 running); PIV 265 Comp1OpFreq (Compressor 1 frequency, Hz); IV 264 AmbT (Outdoor temperature, °C); IV 269 MdlHiPrs (Module high pressure value); IV 270 MdlLoPrs (Module low pressure value); IV 271 Comp1DisT (Compressor 1 discharge temperature, °C); AI 291 Comp1Cur (Compressor 1 current, A).

How do I enable BMS control of the CoolAutomation CoolMasterNet Gree VRF6 outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Gree VRF6 outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.