VRF outdoor unit monitoring via BACnet gateway · BACnet points list

CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects BACnet points list

Updated 12 November 2026

Short answer

With PRO functionality, CoolAutomation gateways publish service data from Toshiba SMMS header outdoor units over BACnet: unit HP, compressor speeds, fan mode, high and low pressure, discharge, heat exchanger, liquid, suction, outdoor and oil temperatures, check codes, compressor currents, PMV positions and valve states (39 objects). Monitoring only.

This page lists 39 BACnet objects for the CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from CoolAutomation’s own free documentation, linked below.

Manufacturer
CoolAutomation
Model
CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects
Equipment
VRF outdoor unit monitoring via BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
39 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
64
Also known as
Toshiba SMMS BACnet, Toshiba VRF BACnet, CoolMasterNet Toshiba, SMMS Header
Brands covered
Toshiba
Source document
BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06
Download CSV 39 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against CoolAutomation’s current documentation and the live device before use. Not official CoolAutomation information. Terms of use.

BMS integration notes: CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects

Integration in brief

Use these objects to monitor Toshiba outdoor equipment only; control stays on the CoolMasterNet indoor-unit objects. Map the header unit's VA and trend pressures, compressor speed and check codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 259Comp(1)Compressor 1 speed, HzRead
AI 272TOOutdoor air temperature, °CRead
AI 263Pd[psi]High pressure, psiRead
AI 264Ps[psi]Low pressure, psiRead
AI 265TD1Discharge temperature 1, °CRead
PIV 277CheckCd1Check (error) code 1Read

Enable & remote start

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

Network setup

Watch out for

CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

39 of 39 shown
Type
AnalogBinary
Show
CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects BACnet Points List
DescriptionStates
CSV256TypeOutdoor Unit Type NameRead
PIV257StPriStarting PriorityRead
PIV258HPOutdoor Unit HPRead
AImin259Comp(1)Comp(1) HzHzRead
AI260Comp(2)Comp(2) HzHzRead
IV261FanModeOutdoor Unit FanModeRead
BI2624wayVlv4way ValveRead
AImin263Pd[psi]Pd:High PressurepsiRead
AImin264Ps[psi]Ps:Low PressurepsiRead
AImin265TD1TD1 Discharge Temp°CRead
AI266TD2TD2 Discharge Temp°CRead
AI267TETE:Heat Exchanger Temp°CRead
AI268TLTL:Liquid Pipe Temp°CRead
AI269TGTG:High Pressure Temp°CRead
AI270TSTS Suction Temp°CRead
AI271TUTU Low Pressure Temp°CRead
AImin272TOTO Outdoor Air Temp°CRead
AI273TK1TK1:Oil Temp1°CRead
AI274TK2TK2:Oil Temp2°CRead
AI275TK3TK3:Oil Temp3°CRead
AI276TK4TK4:Oil Temp4°CRead
PIVmin277CheckCd1Check Code1Read
PIV278CheckCd2Check Code2Read
PIV279OilLvCk1Oil Level Check1Read
PIV280OilLvCk2Oil Level Check2Read
BI281CompBUp1Comp BackUp1Read
BI282CompBUp2Comp BackUp2Read
AI283I1I1ARead
AI284I2I2ARead
IV285PMV1+2Pulse Motor Valve1+2Read
BI286SV2SV2:Hot Gas BypassRead
BI287SV5SV5 ON/OFFRead
BI288SV3ASV3A:Oil Supply ON/OFFRead
BI289SV3BSV3B:Oil Return ON/OFFRead
BI290SV3CSV3C:Gas Pressure ON/OFFRead
BI291SV3DSV3D:Separator OpenRead
BI292SV3ESV3E:Oil Balance ON/OFFRead
BI293SV41SV41:Comp Start AssistRead
BI294SV42SV42:Comp Start AssistRead
Object ID lookup: CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects

How many BACnet points does the CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects have?

This list has 39 BACnet objects: 18 analog inputs, 12 binary inputs, 1 characterstring value, 2 integer values, 6 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects BACnet documentation?

The source is BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge, revision Rev 1.0.4, 2026-07-06, published free by CoolAutomation at https://support.coolautomation.com/hc/en-us/article_attachments/38262832368157.

What are the minimum BACnet points to integrate the CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects?

Start with AI 259 Comp(1) (Compressor 1 speed, Hz); AI 272 TO (Outdoor air temperature, °C); AI 263 Pd[psi] (High pressure, psi); AI 264 Ps[psi] (Low pressure, psi); AI 265 TD1 (Discharge temperature 1, °C); PIV 277 CheckCd1 (Check (error) code 1).

How do I enable BMS control of the CoolAutomation CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects?

BACnet must be enabled on the gateway; these objects belong to its PRO (service data) functionality.

How do I check these points on the real CoolMasterNet Toshiba SMMS header outdoor unit (PRO) objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More CoolAutomation BACnet points lists

Source: BACnet Integration Guidelines - CoolMaster Product Line, CooLinkNet, CooLinkHub, CooLinkBridge · rev. Rev 1.0.4, 2026-07-06. Object names, instances and units are reproduced as published; descriptions are our own.